![AUMA NORM SQ 05.2 Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/auma/norm-sq-05-2/norm-sq-05-2_operation-and-instruction-manual_3016450017.webp)
5.2.3.
Terminal compartment: close
Figure 11: Example: Version S
[1]
Cover
[2]
Screws for cover
[3]
O-ring
[4]
Screws for socket carrier
[5]
Socket carrier
[6]
Cable entry
[7]
Blanking plug
[8]
Cable gland (not included in delivery)
Short-circuit due to pinching of cables!
Risk of electric shock and functional failures.
→
Carefully fit socket carrier to avoid pinching the cables.
1.
Insert the socket carrier [5] into the cover [1] and fasten with screws [4].
2.
Clean sealing faces of cover [1] and housing.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5.
Fit cover [1] and fasten screws [2] evenly crosswise.
6.
Fasten cable glands [8] applying the specified torque to ensure the required
enclosure protection.
5.3.
Accessories for electrical connection
— Option —
5.3.1.
Parking frame
Application
Parking frame for safe storage of a disconnected plug.
For protection against touching the bare contacts and against environmental
influences.
17
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Electrical connection