8.
Signals
8.1.
Feedback signals from actuator
Information
Switches can be provided as single switches (1 NC and 1 NO), as tandem switches
(2 NC and 2 NO) or as triple switches (3 NC und 3 NO). The precise version is indic-
ated in the terminal plan or on the order-related technical data sheet.
Type and designation in terminal plan
Feedback signal
Setting via limit switching
Switches: 1 NC and 1 NO (standard)
End position OPEN/CLOSED
reached
Limit switch, closing, clockwise rotation
LSC (WSR)
Limit switch, opening, counterclockwise rotation
LSO
Setting via DUO limit switching
Switches: 1 NC and 1 NO (standard)
Intermediate position reached
(option)
DUO limit switch, clockwise rotation
LSA
DUO limit switch, counterclockwise rotation
LSB (WDL)
Setting via torque switching
Switches: 1 NC and 1 NO (standard)
Torque OPEN/CLOSED
reached
Torque switch, closing, clockwise rotation
TSC
Torque switch, opening, counterclockwise rotation
TSO (DÖL)
Thermoswitches or PTC thermistors, depending on the version
Motor protection tripped
Thermoswitches
F1, Th
PTC thermistors
R3
Switches: 1 NC (standard)
Running indication (option)
Blinker transmitter
S5, BL
Depending on version either with potentiometer or electronic position transmitter EWG/RWG
Valve position (option)
Potentiometer
R2
Potentiometer in tandem arrangement (option)
R2/2
3-wire or 4-wire system (0/4– 20 mA)
B1/B2,
EWG/RWG
2-wire system (4 – 20 mA)
B3/B4,
EWG/RWG
Switches
Manual operation active (op-
tion)
21
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
Signals