35
4. TAC5 CONTROL SYSTEM
The TAC5 control device manages the following features:
-
Fan airflow management (accurate knowledge of fan’s working point)
-
Management of time slots
-
Automatic bypass control (freecooling)
-
Heat exchanger anti-freeze protection control
-
Automatic motorized inlet and exhaust damper control (option)
-
Electrical pre-heater control (option)
-
Water or electrical Post-heater (option)
-
Control of external post-coil (option)
-
RTU or TCP/IP MODBUS Communication (option)
The TAC5 control circuit is factory pre-wired.
There are 5 ways to ‘communicate’ with the TAC5 control:
•
RC (LCD remote control)
•
GRC (graphic touchscreen display, can control up 247 units)
•
MODBUS RTU network (usually to connect to a BMS)
•
MODBUS TCP/IP protocol (to connect to a BMS or to interface with EOLE 4 App for smartphone, tablet and
PC using operating systems Android, IOS or Windows 7/8/10).
•
KNX network
The following options can be combined with TAC5 control:
-
RC Option: remote control to setup, control and visualize the parameters.
Please refer to TAC5 – RC installation and user’s manual for detailed information
-
GRC Option: graphic remote touchscreen to setup, control and visualize the parameters.
Please refer to TAC5 – GRC installation and user’s manual for detailed information
-
SAT BA/KW Option:
Regulation of 2 external heat exchangers (electrical/water, hot and/or cold)
please refer to SAT BA/KW installation and user’s manual for detailed information
•
The SAT3 Option is a Circuit with 2 relays (2 SAT3 can be plugged)
•
When plugged in position OR1/OR2: status of “Fan On” warning and of “Pressure alarm” warning
and/or
•
When plugged in position OR3/OR4 : status of NV option circulator and of «bypass»
Please refer to SAT3 installation and user’s manual for detailed information
-
Communication option (only possible one at a time):
•
SAT MODBUS option: MODBUS RTU communication, enables the GRC option – graphic
touchscreen display.
•
SAT ETHERNET Option: communication with MODBUS TCP/IP protocol on Ethernet network over
twisted pair 10 BASE T/100Base-TX IEEE 802.3.
•
SAT WIFI Option: communication with MODBUS TCP/IP protocol o
on wireless Wi-Fi network.
•
SAT KNX Option: KNX communication.
Each one of these communication configuration is fully described in a separate installation manual
Содержание HRg 1200
Страница 1: ...KLIMAATTECHNIEK Als het om lucht gaat T 0320 28 61 81 www auerhaan klimaattechniek nl ...
Страница 38: ......