28
1. GENERAL MAINTENANCE INSTRUCTIONS
1.1 Construction characteristics
The structure is freestanding, the panels are 50mm double skin steel plates free of thermal bridges. The outside
panels are made out of pre-painted steel and the inside panels of galvanized steel. Thermal and acoustical
insulation is carried out by fireproof rock wool (Euroclass A1, EN 13501), in conformity with the European
environment standards, inserted between layers.
The HRglobal is mounted on a steel frame and is mono-structured.
All the access doors to the ventilators and filters are equipped with handles.
Air tightness:
Internal: Class 1 as per EN 13141-7.
External: Class 2 as per EN 13141-7.
1.2 TAC technology fans
The HRglobal series is equipped with TAC technology centrifugal ventilators. The TAC5 (DG or DT) control is
specifically developed to take advantage of this technology. Verify that the supplied voltage corresponds to the
specification of the ventilators and that the connection is made according to the supplied wiring instructions. See
www.lemmens.com
for more information on the advantages of the TAC technology.
Warning! : The starting up / stopping of the unit must be activated by using the softstop function on
K1/K2/K3 or via the RC/GRC/MODBUS/KNX, and not by shutting off the power supply.
Always check the following electrical specifications:
Power supply voltage: 230VAC (210V<V<250V).
Power supply frequency: 50/60 Hz.
Grounding the unit is compulsory
The motor is self-protected against overloading. It is thus NOT necessary to install an electrical overload protection
device. See section 3.2 for detailed wiring instructions.
Insulation class
Fans/HRg: IP44.
Nominal temperatures: -10°C/+55°C.
Conformity: CE (motors are also UL approved).
Before starting the unit
- Verify if the fan wheel is rotating properly, without resistance?
- Verify if the installation and the connections are made according to the applicable European standards.
- Are the precautionary measures to avoid an accident taken? (Wiring, rotating parts, security measures,)
Operating conditions
The temperature over the fan motor cannot be lower than -10°C, or superior to 55°C. The unit is not designed to
operate in an aggressive or an explosive environment. It is strongly not advised to stop and start the unit more
often than every 5 minutes.
1.3 About the counterflow AIR/AIR heat exchanger
Protect the heat exchanger by regularly cleaning or replacing the filters.
To protect from frosting, the TAC5 control is as standard delivered with an inbuilt heat exchanger antifreeze
system (by unbalancing the in and out airflows). There is also the modality of antifrosting protection of the
modulating by-pass and the pre-heater options available to accomplish this if deemed necessary (KWin and BAin).
The HRglobal units are specified not to exceed a frontal air speed on the heat exchanger of 2,2m/s.
Содержание HRg 1200
Страница 1: ...KLIMAATTECHNIEK Als het om lucht gaat T 0320 28 61 81 www auerhaan klimaattechniek nl ...
Страница 38: ......