Excessive power consumption (power consumption will increase exponentially to an increase in pressure
drop, for a constant airflow)
•
A damaged filter allows unfiltered air to enter heat exchanger (risk of clogging) and into ventilated room.
See above for list of replacement filters
3. Inspection and cleaning of the inside of the unit:
- Vacuum clean any accumulation of dust in the unit.
- Inspect and gently vacuum clean if need be the heat exchanger. Use brush accessory to protect fins.
- Clean the possible condensation marks and possible accumulations in the drain pan.
- Clean drain pan
- Clean the inside of the bypass. To access interior of bypass it is necessary to force-open it, proceed as
follows: jump terminals IN4 and +12V on the TAC5 circuit board. The bypass is now open, independently of
temperature conditions.
- Remember to remove jump between terminals IN4 and +12V once cleaning of bypass is done
4. Fan maintenance:
Check again if power supply is shut down and fans are not running.
Check cleanness of fan. Clean if necessary, be careful not to alter balancing of the fan wheel (do not remove
balancing clips). Dismount fans if necessary.
5. Check airtightness of unit:
Particularly check that side access panels are well closed and that airtightness seals are in a good state.
Replace if necessary.
_____________________________________________________________________________________
Although we put a lot of care in the making of our documentation, we cannot be held responsible for any error and/or
omissions that could have slipped in.
Содержание HRg 1200
Страница 1: ...KLIMAATTECHNIEK Als het om lucht gaat T 0320 28 61 81 www auerhaan klimaattechniek nl ...
Страница 38: ......