INSTALLATION
PILOT
-C14-
MANUAL
-
18
6.4 - List of parameters which can be set
Parameter N°
Description
Unit
Range of setting
Factory
setting
P202
Maximum exterior temperature (warmest day for heat curve)
°C
11
to
25
20
P203
Minimum exterior temperature ( (coldest day for heat curve))
°C
-
30
to
10
-
5
P204
Summer/winter changeover: choice of changeover method
-
auto
: changeover is done automatically based on the
exterior temperature
manu
: changeover is done manually by the user
manu
P205
Summer/winter time delay: time period for observation
of the exterior temperature before automatic season
changeover. Only used if automatic changeover is activated.
hour
0
to
48
12
P206
Reactivity: the temperature for heating takes into account
the ambient temperature to accelerate heating time when
heating is switched on or restarted.
-
yes
: reactivity activated
no
: reactivity deactivated
no
P207
Anticipation of heating: heating restarted before return
from holidays (for getting a home already at the set
temperature on return)
-
yes
: anticipation activated
no
: anticipation deactivated
no
P208
Minimum exterior temperature for operation using only the
HP.
The back-up is authorised to operate in colder temperatures.
°C
P209
to
20
2
P209
Maximum exterior temperature for operation using only the
back-up.
The heat pump is authorised to operate in warmer
temperatures.
°C
-
20
to
P323
-
20
P210
Operation in peak hours
(HP/HC contact open)
-
0
: no operation allowed
1
: HP limited to 1st power stage
2
: HP limited to 2nd power stage
3
: full HP without back-up
4
: HP + 1 stage back-up (2kW)
5
: HP + 2 stages back-up (4kW)
6
: Full authorization: HP + 3 stages back-up (6kW)
7
: back-up (6kW or boiler) without HP
8
: anti-frost confort level
9
: eco
10
: do not use
6
P212
Type of back-up
-
no
: no backup
Elec
: electrical back-up
BOIL
: back-up boiler
no
P213
Heat pump time-out: allows the heat pump to continue
running for a period of time after intervention of the back-
up
min.
1
to
20
5
P214
Diff erence in temperature between the back-up and the
heat pump
°K
0
to
7
Elec : 4
BOIL : 7
P215
Presence of a heat pump
-
0
: operation without heat pump
1
: presence of a heat pump
1
P216
to
p225
Not concerned
-
Do not change the setting
0.5
P221
Choix du compresseur en fonctionnement
-
0
to
2
0