background image

         AUBER INSTRUMENTS

  

 

 

 

 

 

 

 

         

WWW.AUBERINS.COM  

 

 

         2020.06                                                                   

   

                                                       P9/10 

 

7.3.

 

Controlling a 24V valve 

TC

N

1 13 14 6

2

3

4
5

7

8

9

10

L

120VAC

SYL-5342P

+

-

S

24VAC

Solenoid valve

 

Figure 8. Controller a solenoid valve with SYL-5342P.  
 
This is a typical wiring set up for a 24V gas valve, hot water valve, or a contactor 
with  24V  coil  voltage.  A  separate  24V  power  is  needed  to  drive  the  valve. 
Temperature is measured with a thermocouple input on pin 4 and 5.   
 

7.4.

 

Cooling and heating with the same controller (single step mode) 

TC

N

1

13 14

6

2

7

8

9

10

L

120VAC

Refrigerator

SYL-5342P

3

4

5

Bulb

+

-

Figure 9. A refrigerator connected to SYL-5342P directly. 
 
This is an example for beer fermentation. The refrigerator is driven by the internal 
relay  of  the  controller  directly. 

Please  note  that  the  internal  relay  output 

(terminals 7 and 8) is not powered by itself. 

A power supply 

must 

be used to 

drive the external relay. The refrigerator must consume less current than the 

internal relay’s maximum rating (7A at 240V AC and 10A at 120V AC). 

The bulb 

(less than 100 - 300 W) is for heating. The example is setup to have the heater 
to turn on when temperature drops to below 62° F. The refrigerator will turn on 
when temperature is above 69° F and turn off at 65° F. 

 
Set up for the controller: 

1). RUN = 0. Single step mode. 
2). COOL = 1. Set the controller to cooling mode. 
3). CF = 1. Set the controller to Fahrenheit temperature unit display. 
4). P = 0. ON/OFF mode for cooler.  
5). AL1 = 62 & ALP = 2. Set the low limit alarm to 62 ° F. Heater will be on at 
62° F (AL1) and off at 62.5 ° F (AL1 + 0.5). 
6). Hy = 2.0. Set hysteresis band for cooler to 2 degree. 
7). SP = 67. Refrigerator will be on at 69 ° F (SP + Hy) and off at 65 ° F (SP - Hy). 
8). T = 60. To prevent refrigerator from cycling on/off frequently, output cycle 
time is recommended to set as 60s or longer.  

 
7.5.

 

Controlling the load via external contactor in a 240V system.  

L2

TC

+

-

1

13

14

6

2

3

4

5

7

8

9

10

L1

240VAC

Heater

Contactor
240V Coil

L2

L1

C1

C2

T1

T2

L1

L2

 

Figure 10. SYL-5342P with an external contactor to control the heating element 
in a 240V system. 
 

This  example  is  very  similar  to  example  7.2,  but  both  the  controller  and  the 

contactor’s coil are drove by 240VAC power.   

 

 

8.

 

Programming Examples 

Programs in the SYL-53X2P series controllers (including SYL-5342P and SYL-
5342P)  have  a  uniform  format  of  ramp  time-soak  time-temperature.  The 
temperature set point of the last step will linearly ramp to the set point of the 
current step over the ramp time of current step. Then the set point of current step 
will be held over the soak time of current step (optional). Due to the parameter 
SSb,  even  your  program  a  ramp  step  that  is  faster  than  what  is  the  system 
capable  of  achieving,  which  will  result  in  actual  temperature  fall  behind  the 
schedule,  this  controller  will  automatically  pause  its  timer  to  wait  (see  note 
5.3.19). The time units are in minutes by default. To change timer unit in seconds, 
please see note 5.3.16.  
 

8.1.

 

Example 1: holding the oven temperature at 800° C for 2 hours. 

Assuming that the heater is able to heat the oven from ambient (25° C) to 
800° C within 30 minutes, we can write a program like this: 
 

Step 1: r01 = 2000, t01 = 0, C01 = 25. 

Initial step. 

 

Step 2: r02 = 30, t02 = 120, C02 = 800. 

Ramp up from 25° C to 800° C in 30 

minutes, then hold there for 120 minutes. 

 

Step 3: r03 = 0, t03 = 0, C03 = 0. 

End of the program. 

 
The temperature profile is shown below in Figure 11.  

25

Time (min)

800

Temp

(° C)

30

150

1. Ramp

2. Soak

3. Natural cooling

 

Figure  11.  Temperature  profile  of  an  oven  that  is  programmed  to  hold 
temperature at 800° C for 2 hours. The solid line is the temperature when the 
oven is capable of ramping up from 25° C to 800° C in 30 min; the dashed line is 
the temperature profile when the oven needs longer time to ramp up to 800° C.   
 

Note 1: 

To turn off the heater after the  program, change  LOOP to 0, so the 

program will not auto restart. 

 

 

Note 2

: The value of C[n] is the end temperature of step n. For instance, C01 is 

always the temperature at the end of step 1, and C02 is the end temperature of 
step 2. Usually C01 should be the ambient temperature, and r02 is the ramp time 
from step 1 to step 2. 
 

Note 3

: If the heater is not capable of heat the oven from 25° C to 800° C in 30min, 

the actual oven temperature can fall behind the schedule. Safety start band will 
be triggered to pause the timer until the reading temperature gets close. The 
timer for step 2 (the soak section) will start even when temperature is still a little 
bit below 800° C; and so the actual soaking time will be less than 2 hours. Please 
see the dashed line in Figure 11.  
 

8.2.

 

Example 2: program alarm relay actions  

The following example includes 4 steps: linear temperature heating, maintaining 
a constant temperature, linear temperature cooling and maintaining a constant 
temperature. At the end of all steps, the controller will jump to step 1 and restart 
the program.  

Содержание SYL-5342P-S

Страница 1: ...FILt 0 Display resolution 1 C 1 F or 0 1 C 0 1 F Control mode Fuzzy logic enhanced PID control On off control Output mode Relay contact NO 250VAC 7A 120V 10A 24VDC 10A Alarm relay rating Relay contact...

Страница 2: ...stall The relay outputs AL1 and AL2 are dry single pole switches They do not provide power by themselves Please see Figure 7 and 8 for how they are wired when 120V power is supplied The wiring diagram...

Страница 3: ...e is 1 or 2 press SET and hold for roughly 2 seconds until the parameter setup menu is displayed display mode 3 Please refer to 5 3 for how to set the parameters 5 2 Setup flow chart While in the para...

Страница 4: ...cting in range alarm PV SP AL1 and PV SP AL1 PV SP AL1 0 5 or PV SP AL1 0 5 Legend PV current reading temperature AL1 Value of parameter AL1 SP Set temperature in current step SV 5 3 2 Input offset Pb...

Страница 5: ...20 seconds To drive external relay or contactor output it should be set longer to prevent contacts from wearing out too soon Normally 20 40 seconds 5 3 5 Input digital filter FILt If measurement input...

Страница 6: ...point This mode is suitable for the applications in which power failure does not affect production PdE 3 After power is turned on this controller will jump to the beginning of the program step 1 and r...

Страница 7: ...if this controller is locked Please see section 5 3 9 for the details of LOCK parameter Even the controller is under single step mode RUN 0 user can still get access to all the ramp soak settings tho...

Страница 8: ...the controller will run from step 1 automatically 6 2 11 Check the Step Number and Jump the Program To check at which step the program is running press the SET key once The upper window will show StEP...

Страница 9: ...ature The temperature set point of the last step will linearly ramp to the set point of the current step over the ramp time of current step Then the set point of current step will be held over the soa...

Страница 10: ...igure 12 Temperature profile and relay AL1 AL2 actions in the example program 8 3 Example 3 powder coating oven A powder coating oven needs to heat up to 375 F at its maximum speed Then hold the tempe...

Отзывы: