Display mode 1

PV

SV

^

SET

3s

sp

8

 

0

 

0

Display mode 6: Set Temp Menu 

(Single Step Mode)

PV

SV

 

Figure 3-3. Display mode 6, showing how to change set temp in single step 

mode.  

  

Display mode 1: normal operating mode.

 When the power is turned on, the 

upper display window shows the measured value (PV) and the lower window 
shows the four-digit set value (SP). 
 

Display mode 2: checking the step status.

 Press the DOWN arrow key once 

to change the display from mode 1 to mode 2. The upper display window shows 
your  current  reading  temp,  and  the  lower  window  shows  the  current  step 
segment number 

starting at “P”

. Press DOWN arrow key to go back. Then press 

DOWN arrow key again to show the timer information. The upper display window 
shows  your  current  reading  temp,  and  lower  window  shows  the  time  which 
current step has run 

starting at “F”

. This timer unit depends on parameter SEC 

(note 5.3.16.). It can be either by minute (SEC = 0) or by second (SEC = 1). 
Press DOWN arrow key again to return to the display mode 1. 
 

Display mode 3

Ramp soak step settings. 

Press and hold SET key and A/M 

keys together for 3 seconds to change the display from mode 1 to mode 3. This 
mode is used for step program settings and step control parameters.  
 

Display mode 4: Parameter setting mode.

 Press and hold the SET key for 3 

seconds  to  enter  the  display  mode  4.  The  top  window  shows  the  name  of  a 
parameter and the bottom window shows its value. Use the UP and DOWN arrow 
key the change the value; use the SET key to save the change and go to the 
next parameter.   
 

Display mode 5: Step jumping.

 Press and hold A/M key for 3 seconds and you 

will see current reading temp on the top and current step segment number on 
bottom. The decimal point on the right bottom display is flashing. Use UP and 
DOWN arrow keys to change the step segment number, then press and hold 
A/M key for 3 seconds to confirm and jump.  

 
Display mode 6: Change set temp (single step mode only). 

For single step 

mode (RUN = 0), user can change set temperature by pressing and holding UP 
arrow keys for 3 seconds. Then use UP and DOWN arrow key to change its 
value. Press SET key once to confirm and exit. 

 

 
5.

 

Parameter Settings 

5.1.

 

Parameter setup mode 

When the display mode is 1 or 2, press SET and hold for roughly 2 seconds until 
the parameter setup menu is displayed (display mode 3). Please refer to 5.3 for 
how to set the parameters. 
 

5.2.

 

Setup flow chart 

While in the parameter setup mode, use 

 and 

 to modify a digit and use A/M 

to select the digit that needs to be adjusted. Press the A/M and SET key at the 
same  time  to  exit  the  parameter  setup  mode;  otherwise,  the  instrument  will 
automatically exit if no key is pressed for 10 seconds. Figure 4 is the setup flow 
chart.  Please  note  that  changed  parameter  will  be  automatically  registered 
without pressing the SET key. If the controller is locked (see 7.16), only limited 
parameters (or no parameters) can be changed. 
 

5.3.

 

List of system parameters 

Table 2. System parameters. 
 
 
 

System Parameter Menu 

Press & Hold SET Key for 3s to Enter 

Code 

Description 

Setting Range 

Initial 

Setting 

Remarks 

AL1 

Alarm 1 Setting 

-1999 ~ +9999 

200 

See 5.3.1 

AL2 

Alarm 2 Setting 

0 ~ 200 

10 

Pb 

Input offset 

± 20.0 

See 5.3.2 

Proportional 

Constant 

0 ~ 5000 

See 5.3.3 

Integral Time 

0 ~ 3000 

500 

Derivative Time 

0 ~ 2000 

100 

Cycle Time 

2 ~ 120 

10 

See 5.3.4 

FILt 

Digital Filter 

0 ~ 50 

20 

See 5.3.5 

Hy 

Hysteresis Band 

0.1 ~ 50.0 

0.5 

See 5.3.6 

dP 

Decimal Point 

Position 

0 ~ 1 

See 5.3.7 

OUTH 

Output High Limit 

outL ~ 200% 

200% 

See 5.3.8 

OUTL 

Output Low Limit 

0 ~ outH 

At 

Auto Tuning 

0 ~ 1 

See 5.3.3, 

section 3) 

LocK 

Configuration 

Privilege 

0 ~ 50 

See 5.3.9 

Sn 

Input Sensor Type 

 

K

 

See 5.3.10 

OP-A 

Reserved 

CF 

Display Temp Unit 

C, F 

C/0 

See 5.3.11 

ALP 

Alarm Output 

Definition 

0 ~ 10 

See 5.3.1 

COOL 

System Function 

Selection 

0 ~ 1 

See 5.3.12 

PuH 

Display High Limit 

PuL ~ 9999 

1300 

See 5.3.13 

PuL 

Display Low Limit 

-1999 ~ PuH 

Addr 

Communication 

address 

0 ~ 255 

See 5.3.14 

bAud 

Communication baud 

rate 

 

3 for 

9600 

 

Set Temp Menu (Single Step Mode Only, RUN = 0) 

Press & Hold Up Arrow Key for 3s to Enter 

Code 

Description 

Setting Range 

Initial 

Setting 

Remarks 

SP 

Set Point 

PuL ~ PuH 

100 

See 5.3.15 

 

Ramp Soak Step Menu 

Press & Hold SET and A/M Keys Together for 3s to Enter 

Code 

Description 

Setting Range 

Initial 

Setting 

Remarks 

SEC 

Timer Unit 

0 ~ 1 

0 for min. 

See 5.3.16 

LOOP 

Program Cycling 

0 ~ 1 

See 5.3.17 

PDE 

Power Outage Mode 

0 ~ 3 

See 5.3.18 

SsB 

Safety Start Band 

0 ~ 100.0 

100 

See 5.3.19 

RUN 

Program Control 

0 ~ 3 

See 5.3.20 

PRO 

Program Step Jump 

0 ~ 64 

See 5.3.21 

R01 

Ramp Time 1 

0 ~ 2000 

See Section 6 

T01 

Soak Time 1 

0 ~ 9999 

C01 

Set Temp 1 

PuL ~ PuH 

… 

 

R32 

Ramp Time 32 

 

 

T32 

Soak Time 32 

 

 

C32 

Set Temp 32 

 

 

 

Содержание SYL-5342P-S

Страница 1: ...FILt 0 Display resolution 1 C 1 F or 0 1 C 0 1 F Control mode Fuzzy logic enhanced PID control On off control Output mode Relay contact NO 250VAC 7A 120V 10A 24VDC 10A Alarm relay rating Relay contact...

Страница 2: ...stall The relay outputs AL1 and AL2 are dry single pole switches They do not provide power by themselves Please see Figure 7 and 8 for how they are wired when 120V power is supplied The wiring diagram...

Страница 3: ...e is 1 or 2 press SET and hold for roughly 2 seconds until the parameter setup menu is displayed display mode 3 Please refer to 5 3 for how to set the parameters 5 2 Setup flow chart While in the para...

Страница 4: ...cting in range alarm PV SP AL1 and PV SP AL1 PV SP AL1 0 5 or PV SP AL1 0 5 Legend PV current reading temperature AL1 Value of parameter AL1 SP Set temperature in current step SV 5 3 2 Input offset Pb...

Страница 5: ...20 seconds To drive external relay or contactor output it should be set longer to prevent contacts from wearing out too soon Normally 20 40 seconds 5 3 5 Input digital filter FILt If measurement input...

Страница 6: ...point This mode is suitable for the applications in which power failure does not affect production PdE 3 After power is turned on this controller will jump to the beginning of the program step 1 and r...

Страница 7: ...if this controller is locked Please see section 5 3 9 for the details of LOCK parameter Even the controller is under single step mode RUN 0 user can still get access to all the ramp soak settings tho...

Страница 8: ...the controller will run from step 1 automatically 6 2 11 Check the Step Number and Jump the Program To check at which step the program is running press the SET key once The upper window will show StEP...

Страница 9: ...ature The temperature set point of the last step will linearly ramp to the set point of the current step over the ramp time of current step Then the set point of current step will be held over the soa...

Страница 10: ...igure 12 Temperature profile and relay AL1 AL2 actions in the example program 8 3 Example 3 powder coating oven A powder coating oven needs to heat up to 375 F at its maximum speed Then hold the tempe...

Отзывы: