AUBER INSTRUMENTS
WWW.AUBERINS.COM
2020.06
P3/10
8
0
0
8
0
0
Display mode 1
PV
SV
^
SET
3s
sp
8
0
0
Display mode 6: Set Temp Menu
(Single Step Mode)
PV
SV
Figure 3-3. Display mode 6, showing how to change set temp in single step
mode.
Display mode 1: normal operating mode.
When the power is turned on, the
upper display window shows the measured value (PV) and the lower window
shows the four-digit set value (SP).
Display mode 2: checking the step status.
Press the DOWN arrow key once
to change the display from mode 1 to mode 2. The upper display window shows
your current reading temp, and the lower window shows the current step
segment number
starting at “P”
. Press DOWN arrow key to go back. Then press
DOWN arrow key again to show the timer information. The upper display window
shows your current reading temp, and lower window shows the time which
current step has run
starting at “F”
. This timer unit depends on parameter SEC
(note 5.3.16.). It can be either by minute (SEC = 0) or by second (SEC = 1).
Press DOWN arrow key again to return to the display mode 1.
Display mode 3
:
Ramp soak step settings.
Press and hold SET key and A/M
keys together for 3 seconds to change the display from mode 1 to mode 3. This
mode is used for step program settings and step control parameters.
Display mode 4: Parameter setting mode.
Press and hold the SET key for 3
seconds to enter the display mode 4. The top window shows the name of a
parameter and the bottom window shows its value. Use the UP and DOWN arrow
key the change the value; use the SET key to save the change and go to the
next parameter.
Display mode 5: Step jumping.
Press and hold A/M key for 3 seconds and you
will see current reading temp on the top and current step segment number on
bottom. The decimal point on the right bottom display is flashing. Use UP and
DOWN arrow keys to change the step segment number, then press and hold
A/M key for 3 seconds to confirm and jump.
Display mode 6: Change set temp (single step mode only).
For single step
mode (RUN = 0), user can change set temperature by pressing and holding UP
arrow keys for 3 seconds. Then use UP and DOWN arrow key to change its
value. Press SET key once to confirm and exit.
5.
Parameter Settings
5.1.
Parameter setup mode
When the display mode is 1 or 2, press SET and hold for roughly 2 seconds until
the parameter setup menu is displayed (display mode 3). Please refer to 5.3 for
how to set the parameters.
5.2.
Setup flow chart
While in the parameter setup mode, use
▲
and
▼
to modify a digit and use A/M
to select the digit that needs to be adjusted. Press the A/M and SET key at the
same time to exit the parameter setup mode; otherwise, the instrument will
automatically exit if no key is pressed for 10 seconds. Figure 4 is the setup flow
chart. Please note that changed parameter will be automatically registered
without pressing the SET key. If the controller is locked (see 7.16), only limited
parameters (or no parameters) can be changed.
5.3.
List of system parameters
Table 2. System parameters.
System Parameter Menu
Press & Hold SET Key for 3s to Enter
Code
Description
Setting Range
Initial
Setting
Remarks
AL1
Alarm 1 Setting
-1999 ~ +9999
200
See 5.3.1
AL2
Alarm 2 Setting
0 ~ 200
10
Pb
Input offset
± 20.0
0
See 5.3.2
P
Proportional
Constant
0 ~ 5000
0
See 5.3.3
I
Integral Time
0 ~ 3000
500
D
Derivative Time
0 ~ 2000
100
t
Cycle Time
2 ~ 120
10
See 5.3.4
FILt
Digital Filter
0 ~ 50
20
See 5.3.5
Hy
Hysteresis Band
0.1 ~ 50.0
0.5
See 5.3.6
dP
Decimal Point
Position
0 ~ 1
1
See 5.3.7
OUTH
Output High Limit
outL ~ 200%
200%
See 5.3.8
OUTL
Output Low Limit
0 ~ outH
0
At
Auto Tuning
0 ~ 1
0
See 5.3.3,
section 3)
LocK
Configuration
Privilege
0 ~ 50
0
See 5.3.9
Sn
Input Sensor Type
K
See 5.3.10
OP-A
Reserved
CF
Display Temp Unit
C, F
C/0
See 5.3.11
ALP
Alarm Output
Definition
0 ~ 10
1
See 5.3.1
COOL
System Function
Selection
0 ~ 1
0
See 5.3.12
PuH
Display High Limit
PuL ~ 9999
1300
See 5.3.13
PuL
Display Low Limit
-1999 ~ PuH
0
Addr
Communication
address
0 ~ 255
1
See 5.3.14
bAud
Communication baud
rate
3 for
9600
Set Temp Menu (Single Step Mode Only, RUN = 0)
Press & Hold Up Arrow Key for 3s to Enter
Code
Description
Setting Range
Initial
Setting
Remarks
SP
Set Point
PuL ~ PuH
100
See 5.3.15
Ramp Soak Step Menu
Press & Hold SET and A/M Keys Together for 3s to Enter
Code
Description
Setting Range
Initial
Setting
Remarks
SEC
Timer Unit
0 ~ 1
0 for min.
See 5.3.16
LOOP
Program Cycling
0 ~ 1
1
See 5.3.17
PDE
Power Outage Mode
0 ~ 3
2
See 5.3.18
SsB
Safety Start Band
0 ~ 100.0
100
See 5.3.19
RUN
Program Control
0 ~ 3
0
See 5.3.20
PRO
Program Step Jump
0 ~ 64
0
See 5.3.21
R01
Ramp Time 1
0 ~ 2000
0
See Section 6
T01
Soak Time 1
0 ~ 9999
0
C01
Set Temp 1
PuL ~ PuH
0
…
R32
Ramp Time 32
0
T32
Soak Time 32
0
C32
Set Temp 32
0