55
EN
Language selection:
There is an option to select the following languages: Slovak, Eng-
lish, German, Italian, French, Czech.
Setting of the output range:
The burner can operate in the output range of 8 – 12 kW, or
14 – 30 kW, according to the range selected by this parameter.
Adjustment of the pellet dosing:
The most important parameter of the control system!
Here
you can set the pellet ration supplied by the feeder at the full
operation. To set the pellet ration, you need a plastic sack and a
very exact weighing machine. After entering into the parameter, you have to set the Heat value
(kWH/kg) as the first. Then, the text „Put on the sack“ is displayed (pellet feeder should be filled
with pellets up to the bore). Put the sack on the feeder and press the „S“ button.
Check countdown on display now, while the feeder works for 6 minutes. Then, enter the weight
of the pellets fallen by pressing „+“ and „−“ buttons and confirm/save by „S“ button.
Ventilator setting:
By this parameter it is possible to adjust the flue gas adequately
to the flue gas analyzer for the content of CO and O2 in flue gas.
Operation time of the feeder:
Here you can see, how long did the pellet feeder work. You can
use it to calculate the energy consumption, etc.
Test:
To be used by troubleshooting. Here you can manually or auto-
matically control the components.
This function is very helpful by troubleshooting with particular
components. In the manual mode you can test every component individually, by pressing „S“ for
start and „ESC“ for stop. For step forwards to the required part, press „+/−“. They are displayed in
the following order:
Ventilator
(during the test of ventilator, the displayed rotations per minute should stabilize at 2 000);
Pellet feeder
(start/stop by the buttons „S“/„ESC“);
Ignition coil
(activated by „S“ and stopped by „ESC“);
Grate
(moves out by „S“ and moves back by „ESC“. Here you can see, how many mA are con-
sumed by unit during the shift, which should not exceed 1 800 mA – limit to start the error
“Grate blockage”).
Other displayed options: Current temperature, if the thermal probe is connected; current photo-
cell value; shows light (On/Off); closing of this application.
LANGUAGE
ENTER
< > EXIT
EFFECT SPAN
ENTER
< > EXIT
FEEDER ADJUST.
ENTER
< > EXIT
VENTILATOR.
ENTER
< > EXIT
OPERATION TIME OF
FEEDER.
ENTER
< > EXIT
MENU/TEST
ENTER
< > EXIT
Содержание ATTACK DPX 25 COMBI Pellet
Страница 1: ...www attack sk EN 07 2019 ATTACK DPX COMBI PELET Instructions for use EN ...
Страница 2: ......
Страница 66: ...65 EN 13 ELECTRICAL SCHEMES 13 1 ATTACK DPX 25 30 35 COMBI PELLET ...
Страница 68: ...67 EN 13 2 ATTACK DPX 40 45 50 COMBI PELLET ...
Страница 83: ...11 ...
Страница 98: ......
Страница 99: ......