- 24 -
Following LEDs are used on the
Qc2002™
START:
Is used to start the unit in
Manual Operation.
STOP:
Is used to stop the unit in
Manual or Automatic Operation
(without cooldown). When the unit is
stopped with the STOP button in
Automatic Operation, it will
automatically go to Manual
Operation.
MAINS CONTACTOR:
Is used to open or close the
Mains contactor, if the
Qc2002™ is in Manual
Operation.
.
GENERATOR
CONTACTOR:
Is used to
open or close the Generator
contactor, if the Qc2002™
is in Manual Operation
G
Power
Green LED indicates that the unit is
powered up.
Automatic
Green LED indicates that the
Qc2002™ is in Automatic
Operation.
Start/Stop
Green LED indicates that the
Qc2002™ receives running
feedback (via the W/L input, via the
RPM value at the Canbus, or via the
AC frequency).
Generator
contactor
Green LED indicates that the
voltage and the frequency of the
alternator are within certain limits
for a certain time. It will be possible
to close the Generator Contactor
(both in Island and in AMF mode),
if the Mains contactor is open.
Qc2002
145
G
Power
Alarm
Start
Automatic
Generator
Contactor
Mains
Contactor
Stop
Mains
contactor
Green LED indicates that it is
possible to close the Mains
Contactor (only in AMF mode), if
the Generator contactor is open.
Alarm
Flashing red LED indicates that an
alarm is present. A continuous red
LED indicates that the alarm has
been acknowledged by the user. The
exact alarm is shown on the display.