- 29 -
Running hours adjust
This menu is used to adjust the amount of running
hours. The running hours can only be raised, not
lowered.
Service timer 2 reset
Service timer 1 reset
These menus are used to reset the service timers.
When a service timer alarm occurs and is
acknowledged, the service timer will be reset
automatically.
Unit menu
This menu is used to select the units into which
pressures and temperatures will be shown.
Language selection
Icons is the default factory set language, but 6 other
languages can be selected: English, French, German,
Italian, Spanish and Cyrillic (Russian). All
information in the Parameter List display is always in
English.
MF high frequency
This menu is used to set the maximum limit for the
mains frequency, in % of the nominal frequency (in
AMF-Auto).
MF low frequency
This menu is used to set the minimum limit for the
mains frequency, in % of the nominal frequency (in
AMF-Auto).
Running Time
Cur. 168 20000
St 2 Reset
No No Yes
St 1 Reset
No No Yes
Unit
C/bar C/bar F/psi
Language
English
MF high freq
100% 110 120%
MF low freq
80% 90 100%