Temperature input
Minimum
setting
Nominal
setting
Maximum
setting
Water inlet temperature of energy recovery
˚C
0
50
99
Water inlet temperature of energy recovery
˚F
32
122
210
Energy recovery water outlet temperature
˚C
0
60
99
Energy recovery water outlet temperature
˚F
32
60
210
To modify a setting, consult the relevant section in the description of the controller.
Recoverable energy
The recoverable energy can be calculated from:
RECOVERED ENERGY (kW) = 4.2 x water flow (l/s) x water temperature rise (˚C)
In the tables below, typical examples are given.
Data for low temperature rise/high water flow systems
Parameter
Unit
GA 11
+
GA 15
+
GA 18
+
GA 22
+
GA 26
+
GA 30
Recoverable energy
kW
9.7
13.2
15.8
19.4
22.9
26.4
Recoverable energy
hp
13.2
18
21.5
26.3
31.1
35.9
Water flow
l/min
13.9
18.9
22.7
27.8
32.8
37.9
Pressure drop
mbar
50
75
150
170
250
330
Water flow
cfm
0.5
0.7
0.8
1
1.2
1.3
Pressure drop
in WC
20
30
60
68
100
132
Temperature at inlet
˚C
50
50
50
50
50
50
Temperature at inlet
˚F
122
122
122
122
122
122
Temperature at outlet
˚C
60
60
60
60
60
60
Temperature at outlet
˚F
140
140
140
140
140
140
Data for high temperature rise/low water flow systems
Parameter
Unit
GA 11
+
GA 15
+
GA 18
+
GA 22
+
GA 26
+
GA 30
Recoverable energy
kW
9.7
13.2
15.8
19.4
22.9
26.4
Recoverable energy
hp
13.2
18
21.5
26.3
31.1
35.9
Water flow
l/min
3.5
4.7
5.7
6.9
8.2
9.5
Pressure drop
mbar
10
25
25
25
35
35
Water flow
cfm
0.1
0.1
0.2
0.2
0.3
0.3
Pressure drop
in WC
4
10
10
10
14
14
Temperature at inlet
˚C
20
20
20
20
20
20
Temperature at inlet
˚F
68
68
68
68
68
68
Temperature at outlet
˚C
60
60
60
60
60
60
Temperature at outlet
˚F
140
140
140
140
140
140
Instruction book
92
2920 7118 31
Содержание GA 11+
Страница 1: ...INSTRUCTION BOOK OIL INJECTED ROTARY SCREW COMPRESSORS GA 11 GA 15 GA 18 GA 22 GA 26 GA 30 ...
Страница 2: ......
Страница 44: ... BOOT Software nr Instruction book 42 2920 7118 31 ...
Страница 81: ...5 4 Pictographs Description Pictographs 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Instruction book 2920 7118 31 79 ...
Страница 99: ...Prefilter components Reference Name 1 4 Prefilter Instruction book 2920 7118 31 97 ...
Страница 109: ...7 6 Stopping Control panel Elektronikon Touch Control panel Elektronikon Swipe Instruction book 2920 7118 31 107 ...
Страница 151: ......