• When pressed during normal operation, it starts the manual drain test.
• When pressed during an alarm, it resets the control logic.
• By pressing the Test button for at least 5 seconds, the self diagnosis routine will start.
LED explanation
Green and red LED alternating on/off for 6 seconds after switching on.
Drain is powered.
Green LED on
Normal operation, drain is in standby and awaiting condensate.
Green LED blinking
Normal operation, drain valve is open to drain water.
Green LED fading on/off
Water is not flowing in to the drain‘s tank. If the floater does not reach the upper level for 3
hours, the solenoid is energized for 2 seconds. This cycle is repeated for 5 times (so up to 15
hours). Afterwards, the green light starts fading on/off.
Causes:
• No condensate entering the tank.
• Float mounted incorrectly (upside down).
Checks:
• Is any condensate reaching the drain? Does the water separation take place in the heat
exchanger?
• Is the floater mounted in its correct position, for instance after maintenance?
Solution:
• Although this LED sign does not indicate any kind of failure, the drain can be reset by
pushing the test button (T) for 5 seconds.
Red LED blinking slowly: cleaning routine 1
The drain’s tank is filled and the water cannot be drained or can only be drained very slowly.
In normal operation, the drain gets 20 seconds time to drain all water. If the drain is not
emptied within this time frame, a (first) cleaning routine is activated, alternatively opening and
closing the valve for 2 seconds, during maximum 30 cycles. This routine is started in an
attempt to unblock the drain.
If this first unlock routine is unsuccessful, a second routine will be started.
Causes:
• Filter mesh clogged.
• Not enough pressure on drain.
• Internal problem with the drain.
Checks:
• Is the filter clean and in good condition?
• Is there a minimum pressure of 0.2 bar (2.8 psi) in the drain?
Press the test button (T) for at least 5 seconds to reset the drain.
Instruction book
2920 7118 31
19
Содержание GA 11+
Страница 1: ...INSTRUCTION BOOK OIL INJECTED ROTARY SCREW COMPRESSORS GA 11 GA 15 GA 18 GA 22 GA 26 GA 30 ...
Страница 2: ......
Страница 44: ... BOOT Software nr Instruction book 42 2920 7118 31 ...
Страница 81: ...5 4 Pictographs Description Pictographs 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Instruction book 2920 7118 31 79 ...
Страница 99: ...Prefilter components Reference Name 1 4 Prefilter Instruction book 2920 7118 31 97 ...
Страница 109: ...7 6 Stopping Control panel Elektronikon Touch Control panel Elektronikon Swipe Instruction book 2920 7118 31 107 ...
Страница 151: ......