Lift the wall support, lining
up the drilling points A with
the lower holes on the wall
support. Mark the 2 drilling
points B with a pen.
3
Drill the 4 holes and insert the plugs which are suitable for
your wall (e.g. plasterboard, concrete). Position the wall
support and screw in.
1.3.3 - Appliance connection
To facilitate connection, this appliance has been designed to remain
upright during connection.
Connection rule
- The appliance must be supplied with 230V 50 Hz.
- The radiator's power supply must be connected directly to
the network after the single-pole disconnection mechanism, in
accordance with the installation rules. The radiator will be connected
to the mains with a 3-wire cable (Brown = Live, Blue = Neutral,
Black = Pilot wire) via a connection box.
- In damp rooms such as kitchens and bathrooms, the connection
box must be installed at least 25 cm from the ground. The installation
must be equipped with a 30mA differential circuit breaker-type
protection device.
-
Connection to the earth is prohibited. Do not connect the
pilot wire (black) to the earth.
- If the power cable is damaged, it must be replaced by the
manufacturer, their after-sales service or any suitably quali
fi
ed
person, in order to avoid any danger.
- If the pilot or piloted appliance is protected by a 30mA differential
(e;g.: bathroom), the pilot wire supply to this differential must be
protected.