![Atlantic alfea hybrid duo gas Скачать руководство пользователя страница 59](http://html.mh-extra.com/html/atlantic/alfea-hybrid-duo-gas/alfea-hybrid-duo-gas_installation-and-commissioning-instructions_2999736059.webp)
Line
Function
6HWWLQJUDQJHRUGLVSOD\
6HWWLQJ
increment
%DVLFVHWWLQJ
8412
U
Heat pump start temperature
0... 140 °C
--
Heat pump ref. value (start)
--
8413
U
Compressor modulation
0... 100%
--
8414
I
Electrical resistance modulation
0... 100%
--
8425
S
Condenser temperature difference
-50... 140 °C
--
8450
S
Hours run compressor 1
h
--
8454
S
Heat pump locking start
Reset? (return to zero) No, Yes
0... 2730 h
--
8455
S
Heat pump counter locking
Reset? (return to zero) No, Yes
0... 65535
--
8456
S
Hours of operation of electrical start
Reset? (return to zero) No, Yes
0... 2730 h
--
8457
S
Counter for n° of electrical starts
Reset? (return to zero) No, Yes
0... 65535
--
8499
S
Function not used
8505
S
Function not used
8510
S
Function not used
8511
S
Function not used
8512
S
Function not used
8513
S
Function not used
8515
S
Function not used
Consumer diagnostic
8700
U
Outdoor temperature
-50... 50 °C
--
8701
U
Minimum outdoor temperature
Reset? (return to zero) No, Yes
-50... 50 °C
--
8702
U
Maximum outdoor temperature
Reset? (return to zero) No, Yes
-50... 50 °C
--
8703
I
Attenuated outdoor temperature
Reset? (return to zero) No, Yes
-50... 50 °C
--
This is the average outdoor temperature over a 24 hour period.
This value is used for automatic summer / winter switching (line 730).
8704
I
Mixed outdoor temperature
-50... 50 °C
--
The mixed outdoor temperature is a combination of the "current outdoor temperature" and the "mean outdoor temperature"
calculated by the regulator. This value is used to calculate the start temperature.
8730
I
Heating circuit 1 circulator
Stop, Start
No function
8731
I
Heating circuit 1 mixing valve open
Stop, Start
No function
8732
I
Heating circuit 1 mixing valve closed
Stop, Start
No function
8740
U
Ambient temperature 1
0... 50 °C
--
Ambient temperature value 1
&
8743
U
Start temperature 1
0... 140 °C
--
Start temperature ref. value 1
--
8756
U
Cooling start temperature 1
0... 140 °C
--
Cooling temperature value 1
--
8760
I
Heating circuit 2 pump
Stop, Start
No function
8770
I
Ambient temperature 2
0... 50 °C
--
Ambient temperature value 2
&
Installation and commissioning instructions "1485 - EN"
- 59 -
Heat pump alféa hybrid duo gas