- 65 -
▼
Start-up
OK
Non-compliant
•
Starting up (
see chapter
“
Start-up”, page 28
and
“List of function lines”, page 35
)
Push in the installation's general circuit breaker (outdoor unit power )
2 hours before the tests => Compressor pre-heating.
Push in the on/off switch => Few seconds' initialisation.
Operation of the heating circulator
The outdoor unit starts after 4 min.
Configure the Time, Date and Heating Circuit, hourly programmes if different from
the default values.
Configure the hydraulic circuit (parameter 5700):
Select the outdoor unit (parameter 3197).
Set the heating slope (720 / 1020).
Adjust the maximum start setting (
741 / 1041).
Configuration, operations, checks.
Adjust the heating circuit setpoints if different than default values
(710 - 714 / 1010 - 1014).
•
Outdoor unit checks
Operation of the fan(s), compressor.
Intensity measurement.
After a few minutes, measure the difference in air T°.
Condensation and evaporation pressure / temperature check.
• Hydraulic unit checks
After 15 minutes of operation.
Difference in primary water T°.
Heating operation, etc.
• Usage explanations
The heat pump is ready for operation!
Aurea M / Installation / 1883 - EN