![Atlantic AEYC-0639U-AT Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/atlantic/aeyc-0639u-at/aeyc-0639u-at_installation-manual_2999728016.webp)
- 16 -
►
the hydraulic unit
▼
Installation precautions
The choice of the position for installation is
particularly important insofar as any later
movement is a delicate operation requiring the
intervention of a qualified person.
• Choose the site of the heat pump and the hydraulic
unit after discussion with the customer.
• The room where the appliance operates must comply
with the regulations in force.
• To ease maintenance operations and provide access
to the various parts, sufficient space should be left
around the hydraulic unit.
• Be careful to keep the heat pump away from
inflammable gas during installation, in particular when
it requires brazing. The appliances are not fireproof
and should therefore not be installed in a potentially
explosive atmosphere.
▼
Positioning the hydraulic unit
-
Secure the support (4 screws and plugs) to a flat,
sturdy wall (not a light-weight partition) ensuring that
it is correctly levelled.
-Hook the appliance onto its support.
350 mm
mini
1000 mm
300 mm
mini
118 mm
(S)
538 mm
mini
418 mm
mini
300 mm
mini
350 mm
mini
188 mm
fig. 15 - Mounting bracket