- 45 -
Line
Function
Setting range or display
Setting
increment
Basic
setting
3197
I
Compressor electrical power
0.1...60
0.1 kW
See table below
3197 parameter setting according to outdoor unit used
Heat pump
Outdoor Unit Model
Parameter 3197
Aurea M 5
Aurea 5
1.28
Aurea M 8
Aurea 8
1.78
Aurea M 10
Aurea 10
2.32
Aurea M 16
Aurea 16
4.10
Additional generator (Boiler connection)
3692
S
With DHW charging
Locked, Substitute,
Complement, Instantly
Substitute
- DHW Instantly :
When DHW request, the HP and the boiler are put into operation. The HP will stop when the primary
return temperature is over 55 °C.
- DHW Substitute :
If the outdoor temperature is above 2 °C, the operation of the HP when DHW request last 5 minutes
at least. The HP operating time can be extended depending on the outdoor temperature. The boiler will activate then.
3700
S
Release below outdoor temperature
-50... 50 °C
1 °C
2 °C
3701
S
Release above outdoor temperature
-50... 50 °C
1 °C
--
3705
S
Overrun time
0... 120 min
1 min
20 min
3720
S
Switching integral (for boiler relief)
0... 500 °Cmin
1 °Cmin
100 °Cmin
3723
S
Locking time
1... 120 min
1 min
30 min
DHW tank
If the installation is equipped with the DHW kit (only appears with the DHW kit option).
5024
S
Switching differential
0... 20 °C
1 °C
7 °C
5030
S
Charging time limitation
10... 600 min
10 min
90 min
(with dynamic radiator => set to 40 min)
Installation configuration
5710
S
Heating circuit 1
Off, On
On
5711
S
Cooling circuit 1
Off, 4 pipe system, 2 pipe system
Off
Set the parameter to
" 2-pipe system cooling "
with the cooling kit.
5715
S
Heating circuit 2
Off, On
Off
5716
S
Cooling circuit 2
Off, 4 pipe system, 2 pipe system
Off
Set the parameter to
" 2-pipe system cooling "
with the cooling kit. If the installation consists of 2 heating circuits.
5740
S
K6 water elec resist output
-- kW
5740 = Value of the DHW electrical backup - kW
5806
I
Start electrical resistance type
3 speeds, 2 exclusive speeds,
2 back-up speeds, modulating UX
2 back-up
speeds
5891
I
Relay output
QX2
None
0: None
, 1 to 3 : Not used,
4: Electric immersion heater 1 flow K25
, 5 to 29: Not used,
30: Heat demand K27
,
31 to 81: Not used
5892
I
Relay output
QX3
None
0: None
, 1 to 4 : Not used,
5: Electric immersion heater 2 flow K26
, 6 to 38: Not used,
39: Suppl source control K32
,
40 to 81: Not used
5980
S
EX1 input function
E6 elec. reading
forced stop
0: Without, 1: E6 elec. reading forced stop 2: E5 electricity reduced tariff, 3: ---, 4: Evapor. overload E14,
5: Evaporat. pressure sensor E26, 6: E15 evap flow controller, 7: E24 consumption flow control, 8: E17 manual defrosting,
9: E20 HP alarm summary, 10: E25 progress start fault, 11: ---, 12: Pressure sensor BP E9, 13: Pressure sensor HP E10,
14: Compress overload 1 E11, 15: Error/alarm message, 16: E21 sector monitoring, 17: ---, 18: E28 defrosting diff pressure,
19: Eva int circ pressure sensor E29, 20: E30 evap int circt rate contr, 21: Smart grid E61, 22: Smart grid E62, 23: ---,
24: ---, 25: HC rate switching, 26: DHW forcing.
Aurea M / Installation / 1883 - EN