ATEG Automation GmbH
|
Intzestraße 50
|
42859 Remscheid
|
Germany
|
Tel.: +49 (0)2191 / 591457-0
|
|
www.ateg.de
Datenblatt
Zeitrelais H3DT
H3DT
17
Twin Timer
H3DT-F
• Switch between flicker-OFF or flicker-ON start mode.
• Independent ON time and OFF time settings.
• Eight time ranges from 0.1 s to 1,200 h.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
LR
*
*
CSA conformance evaluation by UL.
Ordering Information
List of Models
Model Structure
*
Certification is pending for DNV GL.
Specifications
Time Ranges
Ratings
*1.
When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.5 A. Allow for this inrush current when turning
ON and OFF the power supply to the Timer with device with a solid-state output, such as a sensor.
*2.
DC ripple: 20% max.
Operating modes
Supply voltage
Control output
H3DT-F
Flicker OFF start/flicker ON start
24 to 240 VAC/DC
Contact output: SPDT
Model
H3DK-F
Model
Operating modes
Terminal block
Output type
Mounting method
Safety standards
H3DT-F
Flicker OFF start/flicker ON start
6 terminals
Relay, SPDT
DIN Track mounting
cULus
(UL508 CSA C22.2 No. 14)
CCC
LR
DNV GL
*
EN 61812-1
IEC 60664-1 4 kV/2
Time range setting
0.1 s
1 s
10 s
1 min
10 min
1 h
10 h
100 h
Set time range
0.1 to 1.2 s
1 to 12 s
10 to 120 s
1 to 12 min
10 to 120 min
1 to 12 h
10 to 120 h
100 to 1,200 h
Scale numbers
12
Power supply voltage
*
1
24 to 240 VAC/DC, 50/60 Hz
*
2
Allowable voltage fluctuation range
85% to 110% of rated voltage
Power reset
Minimum power-OFF time: 0.1 s
Reset voltage
10% of rated voltage
Power consumption
H3DT-F
At 240 VAC: 1.9VA max., at 240 VDC: 0.6W max., at 24 VDC: 0.3W max.
Rated Insulation Voltage
250 VAC
Control output
Contact output: 5 A at 250 VAC with resistive load (cos
= 1),
5 A at 30 VDC with resistive load,
0.15 A max. at 125 VDC with resistive load,
0.1 A max. at 125 VDC with L/R of 7 ms.
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Contact materials : Ag-alloy
(Recommended fuse: BLN5 (Littelfuse) or 0216005MXEP)
Ambient operating temperature
20 to 60
C (with no icing)
Storage temperature
40 to 70
C (with no icing)
Surrounding air operating humidity
25% to 85%
Erstellt am 04.09.2021 um 04:38 Uhr | Alle Angaben ohne Gewähr, Irrtümer und Änderungen vorbehalten!