Datenblatt
Zeitrelais H3DT
H3DT
21
Star-delta Timer
H3DT-G
• Set two time ranges between 1 and 120 s with one Timer.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
LR
*
*
CSA conformance evaluation by UL.
Ordering Information
List of Models
Model Structure
*
Certification is pending for DNV GL.
Specifications
Time Ranges
Ratings
Operating modes
Supply voltage
Control output
H3DT-G
Star-delta Timer
24 to 240 VAC/DC
Contact outputs
Delta circuit: SPDT, Star circuit: SPDT
Model
H3DT-G
Model
Terminal block
Operating/resetting method
Output type
Mounting method
Safety standards
H3DT-G
8 terminals
Time-limit operation/
self-resetting
Time-limit (relay)
Star circuit: SPDT
Delta circuit: SPDT
DIN Track mounting
cULus
(UL 508 CSA C22.2 No. 14)
CCC
LR
DNV GL
*
EN 61812-1
IEC 60664-1 4 kV/2
Time range setting
t1x1
t1x10
Star set time (t1) range
1 to 12 s
10 to 120 s
Star-Delta transfer time (t2)
Select from 0.05, 0.1, 0.25, or 0.5 s.
Power supply voltage
*
1
24 to 240 VAC/DC, 50/60 Hz
*
2
Allowable voltage fluctuation range
85% to 110% of rated voltage
Power reset
Minimum power-OFF time: 0.1 s
Reset voltage
10% of rated voltage
Power consumption
H3DT-G
At 240 VAC: 1.9 VA max., at 240 VDC: 0.6 W max.,
at 24 VDC: 0.3 W max.
Rated Insulation Voltage
250 V
Control output
Contact output:
5 A at 250 VAC with resistive load (cos
= 1),
5 A at 30 VDC with resistive load
0.15 A max at 125 VDC with resistive load,
0.1 A max at 125 VDC with L/R of 7 ms.
The minimum applicable load is 10 mA at 5 VDC (P reference
value).
Contact materials : Ag-alloy
(Recommended fuse: BLN5 (Littelfuse) or 0216005MXEP)
Ambient operating temperature
20 to 60
C (with no icing)
Storage temperature
40 to 70
C (with no icing)
Surrounding air operating humidity
25% to 85%
*1.
When using a 24-VDC power supply voltage,
there will be an inrush current of approximately
0.5 A. Allow for this inrush current when turning
ON and OFF the power supply to the Timer with
device with a solid-state output, such as a
sensor.
*2.
DC ripple: 20% max.