ATEG Automation GmbH
|
Intzestraße 50
|
42859 Remscheid
|
Germany
|
Tel.: +49 (0)2191 / 591457-0
|
|
www.ateg.de
Datenblatt
Zeitrelais H3DT
H3DT
H3DT-N/H3DT-L
3
Specifications
Time Ranges
Ratings
Time range setting
0.1 s
1 s
10 s
1 min
10 min
1 h
10 h
100 h
Set time range
0.1 to 1.2 s
1 to 12 s
10 to 120 s
1 to 12 min
10 to 120 min
1 to 12 h
10 to 120 h
100 to 1,200 h
Scale numbers
12
Power supply voltage
*
1
24 to 240 VAC/DC, 50/60 Hz
*
2
Allowable voltage fluctuation
range
85% to 110% of rated voltage
Power reset
Minimum power-OFF time: 0.1 s
Reset voltage
10% of rated voltage
Voltage input
24 to 240 VAC/DC
High level: 20.4 to 264 VAC/DC, Low level: 0 to 2.4 VAC/DC
*
3
Power
consumption
H3DT-N2/-L2
At 240 VAC: 2.3 VA max., at 240 VDC: 1.0 W max.,
at 24 VDC: 0.3 W max.
H3DT-N1/-L1
At 240 VAC: 2.0 VA max., at 240 VDC: 0.9 W max.,
at 24 VDC: 0.3 W max.
Rated Insulation Voltage
250 VAC
Control output
Contact output: 5 A at 250 VAC with resistive load (cos
= 1),
5 A at 30 VDC with resistive load
*
5,
0.15 A max. at 125 VDC with resistive load,
0.1A max. at 125 VDC with L/R of 7 ms.
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Contact materials : Ag-alloy + Gold plating
(Recommended fuse: BLN5 (Littelfuse) or 0216005MXEP)
Ambient operating
temperature
20 to 60
C (with no icing)
Storage temperature
40 to 70
C (with no icing)
Surrounding air operating
humidity
25% to 85%
*1.
When using a 24-VDC power supply voltage,
there will be an inrush current of approximately
0.5 A. Allow for this inrush current when
turning ON and OFF the power supply to the
Timer with device with a solid-state output,
such as a sensor.
*2.
DC ripple: 20% max.
*3.
The power consumption is for after the Timer
times out in mode F2 for the H3DT-N and
mode A for the H3DT-L.
The maximum power consumption is given,
including the current consumed by the input
circuit.
Erstellt am 04.09.2021 um 04:38 Uhr | Alle Angaben ohne Gewähr, Irrtümer und Änderungen vorbehalten!