background image

- 1 -

AS-224

Staircase timer

with counter-blockade

Staircase timer AS-224 serves to keep switch-ON lighting of stair-

case, corridor, or any other object for the set time and to switch-

OFF this lighting automatically, upon elapse of this set time.

Turned ON staircase timer supports the lighting during set time 

by potentiometer (from 0.5 min. to 10 min.) and upon elapse of 

this set time a reduction by half of lighting brightness follows 

for about 30 seconds, after that OFF follows (thus an occurrence 

of a sudden darkness is avoided, enabling safe approach to the 

switch). After switching OFF the lighting there is possibility to 

switch it ON again. Function of counter blockade does not allow 

to keep the light-ON in case of staircase switch blocking (after 

blocking the pushbutton, for example by match, the timer will 

count the set time and switch OFF the lighting). Next switching 

ON can be after removing the blockade.

Purpose

Functioning

F&F Filipowski sp. j.

Konstantynowska 79/81, 95-200 Pabianice, POLAND

phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71

www.fif.com.pl; e-mail: [email protected]

Do not dispose of this device in the trash along with other waste! 

According to the Law on Waste, electro coming from households free of charge and can 

give any amount to up to that end point of collec� on, as well as to store the occasion of 

the purchase of new equipment (in accordance with the principle of old-for-new, regar-

dless of brand). Electro thrown in the trash or abandoned in nature, pose a threat to the 

environment and human health.

Содержание AS-224

Страница 1: ...itch it ON again Function of counter blockade does not allow to keep the light ON in case of staircase switch blocking after blocking the pushbutton for example by match the timer will count the set time and switch OFF the lighting Next switching ON can be after removing the blockade Purpose Functioning F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 ...

Страница 2: ...ls 1 3 in accordance with markings 4 Timer switches which were connect with parallel connect to terminal 6 and to cable which is connecting to terminal 3 5 Connect the power L to terminal 10 The supplied receivers lamps which were connect with parallel connect to terminal 12 and cable N Mounting Wiring diagram ...

Страница 3: ...contact 12 output closing contact active power supply 21 27 V AC DC maximum load current AC 1 16 A activation delay 0 1 0 2 s deactivation delay adjustable 0 5 10 min power consumption 0 6 W terminal 2 5mm screw terminals tightening torque 0 4 Nm working temperature 25 50 C dimensions 1 module 18 mm mounting on TH 35 rail ingress protection IP20 Technial data ...

Страница 4: ...ww fif com pl The F F products are covered by a warranty of the 24 months from the date of purchase Effective only with proof of purchase Contact your dealer or directly with us F F Filipowski sp j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of...

Отзывы: