VI.4.2 Control terminal connection 9008 to 9070
* direct connection on CORRIGO
GTDHR FIRST / PREMIUM / INFINITE
ENERGY RECOVERY UNIT
MS-CDF-001 A
Ind A
update 01/07/2011
Created by JC
Validated by AR
10 / 36
7
15
1
16
2
17
18
4
19
20
6
2
1
22
8
3
5
243
9
24
10
25
26
12
27
28
14
11
13
Control terminal
(on lower DIN rail)
Name
Termi-
nals
Connection
RMS
1
DO3*
To be connected on terminals 1 and 2 of the Motorised Supply Air Damper
(GMA
121.1E)
RMR
2
DO4*
To be connected on terminals 1 and 2 of the Motorised Return Air Damper
(GMA
121.1E)
AL
3
DO5*
To be connected on the terminals of a remote alarm indicator (2A 24VAC MAX)
DBE (INFINITE
only)
4
DO6*
To be connected on the terminals of the defrost battery's static switch (Detachable)
(see chapter VI.16)
NC (Night cooling)
(LOBBY
®
EC)
2
DO7*
24V output available if the CARMA® unit is associated with the LOBBY EC option for
opening the dampers during
N
ight Cooling period. (see chapter VI.9)
DX
2
DO7*
24V output available for starting a direct expansion module (should be specified in
the order) (see chapter VI.13)
ADP
5
6
To be connected on the NF contact of the Remote Firefighter's Stop button. As its
name states, this contact should be used only in a firefighter's stop function since it
directly stops the system and shunts all the safeties.
REPEATER
7
8
B-A-N*
To be connected on the repeater if you would like to shift the remote control more
than 10m away. (see chapter VI.17)
MF HS
9-10
To be connected to the terminals of a NO contact provided for the High Speed
Forced Operation
MF LS
11-12
To be connected to the terminals of a NO contact provided for the Low Speed Forced
Operation
AR EXT
13-14
To be connected to the terminals of a NO contact provided for the Forced External
Stop (Note: if contact closed, unit is at stop)