VII.3.6 Unit start/stop or LS/HS forced on through the Corrigo or the remote control

 

 

You can stop 

(7) (stop) 

the unit with the Corrigo control or do a forced LS 

(7) (Manual speed 1/2) 

or HS 

(7)

 start 

(manual 

speed 1/1). 

As standard, the unit operates in Automatic mode through the clocks 

(7) (Auto)

 

 

Move the cursor to the menu below as given in chapter VII.2.

 

  

 
Once on this menu:  

 

 

 

 

 

                          press the OK key (Auto = start by clock)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

            (Stop = stop the unit) 

 

 

 

 

 

 

 

 

 

 

 

 

 

                       (manual speed 1/2 = MFPV) 

 

 

 

 

 

 

 

 

 

 

 

 

 

             (manual speed 1/ = MFGV)  

 



Enter the desired mode.  



Validate by pressing the OK key to go to the next field.  



Once all the modes are updated, press on the left arrow to return to the welcome screen.

 

 

 
 

 

An alarm appears from the time that you are not in Auto mode. The manual Speed 1/1 and  

                     manual speed 1/2 modes should be used only for commissioning and repairs. Another setting  
                    would necessarily result in a malfunction of the unit.

 

 

VII.3.7 Special parameter settings (control type modification and Night Cooling % modification)

 

 

These  parameter  settings  require  access  to  the  Configuration  menu.  For  this  you  should  get  the  "Service"  level  access 
rights. Follow the procedure given below.

 

 

 

Enter the code 

2222

 with the help of the directional keys and then validate with the OK key. Press twice on left arrow to ac-

cess the menus. In case of an operating error, press twice on the C key and restart the operation

 

Once this step is completed, you will get access to the configuration menu where you will be able to modify the type of con-
trol 

(NOTE: if you want to control the unit based on ambient temperature, selected the "Return air" control mode. 

All other choices will make the unit malfunction) 

and the speed of the fan in % during the Night Cooling period.

 

Words written normally = view only /    

Words in bold underlined 

= Modification possible with password 3333    /    . = not 

used or not accessible.

 

 

       Access rights

  

CARMA 
Year:month:day 

Time

 

System:Start or stop 
SP: T°C Set point Act: T°C current

 

 

          Enter

 

 

       

 

Enter password of the desired  
authorisation level: ****

 

Current lev.: None

  

 

       

Configuration 

 

 
 
 

CARMA 
Year:month:day 

Time

 

System:Start or stop 
SP: T°C Set point Act: T°C current

 

 

   

      Regulation function 
 
 
 
 
 
        Cooling

 

 

 
 

Regul. function 
Mode : 

Supply air + outdoor comp 

 

Fan output 
During cooling 
AS Vent: 

85%

 

AR Vent: 

85%

 

 

NOTE: Do not change parameters other than those shown in bold.  

Else, no After Sales Service can be included.

 

 

Operating mode 

Auto  

 
  

Содержание GTDHR FIRST

Страница 1: ...GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT OPERATING AND MAINTENANCE INSTRUCTIONS MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 1 36...

Страница 2: ...8 36 VI 3 Connection of the probes P 8 36 VI 4 Electric board s terminal P 9 to 11 36 VI 4 1 Power terminal connection 9008 to 9070 P 9 36 VI 4 2 Control terminal connection 9008 to 9070 P 10 and 11...

Страница 3: ...3 3 c CARMA MAC2 and QUATTRO EC P 23 36 VII 3 4 Temperature set point modification P 24 36 VII 3 5 CO2 set point modification P 24 36 VII 3 6 Unit start stop or forced LS HS start through the Corrigo...

Страница 4: ...ed into the environment I 3 Storing The equipment must be stored in shade in a dry place at a temperature between 20 C and 40 C II INSTALLATION II 1 Handling The units must only be moved in their inst...

Страница 5: ...ipe A siphon can only be used for one drainage system Note the si phon must be connected in accordance with Best Practices in order that the condensates are removed as efficiently as possible The heig...

Страница 6: ...dry contact NO Supply air temperature management with outdoor compensation air relationship III 5 CARMA MAC2 EC 1 or 2 CONSTANT flow rates as required m3 h Adjustment of 1 or 2 constant flow rates LS...

Страница 7: ...by AR 7 36 NEW AIR RETURN AIR VS Supply Air Fan VR Return Air Fan DEP FS Filter Pressure Switch only for new air PT1000 PROBES and Servomotors SSG Supply Air Duct Probe SDG Duct Defrost Probe SEG Exte...

Страница 8: ...Agnd 33 and AI4 35 SBD Defrost Battery Probe on Agnd 36 and AI4 37 for INFINITE BE or a 1000 Ohms resistance for FIRST and PRE MIUM GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A...

Страница 9: ...ns mitter in case of the LOBBY EC QUATTRO EC MAC2 EC option In this case do not connect any thing to these terminals SUPPLY AND RETURN AIR MOTOR 31 32 33 34 35 36 40 41 According to De CARMA size see...

Страница 10: ...ut available if the CARMA unit is associated with the LOBBY EC option for opening the dampers during Night Cooling period see chapter VI 9 DX 2 DO7 24V output available for starting a direct expansion...

Страница 11: ...BE PREMIUM BE and INFINITE BE versions the K1 auxiliary contact is factory connected FIRST version if you install an additional BE module to the CARMA unit to be connected to the C and 2 terminals of...

Страница 12: ...CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 12 36 CARMA 9008 SUPPLY AIR POWER CONTROL CONTROL GREEN YELLOW BLUE BROWN BLUE YELLOW GREEN YELLOW BLUE BROWN WHITE BROWN SHIELDING GREE...

Страница 13: ...INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 13 36 GTDHR 9016 9023 CONTROL POWER SUPPLY AIR POWER CONTROL RETURN AIR RETURN AIR GTDHR 9035 9048 GTD...

Страница 14: ...emperature set point the water battery valve will open or the electric battery will start In summer FREE COOLING The Bypass closes when the outside temperature is higher than the inside temperature to...

Страница 15: ...n the hot water battery is already installed in the unit The Anti frost Thermo stat is connected However you should wire the 3 way valve For all other versions also connect the THA Anti frost Thermost...

Страница 16: ...lectric battery housing follow the diagram as given below VI 15 Heating electric battery CARMA PREMIUM BE and INFINITE BE In PREMIUM BE and INFINITE BE version the electric battery is already installe...

Страница 17: ...d INFINITE BC version the defrost battery is already installed in the unit The control is also connected GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created...

Страница 18: ...enus The Up and Down keys are also used to increase or decrease the value of a parameter when it is accessible whereas the Left and Right keys are also used to navigate within the same parameter The O...

Страница 19: ...to 7 Operating period Vent AS 00 0 Hours Viewing the alarm log use the bottom arrow to scroll the log Alarm report Inputs outputs Analogue inputs AI1 AS Temp supply air AI2 Ext Temp outdoor AI3 Def Te...

Страница 20: ...2 OR QUATTRO EC Actual 4178m3 h example Set point 5000m3 h 5 Frequency control AS manual vent Output 1 1 75 5 Output 1 2 50 5 CO2 CARMA DIVA EC OR QUATTRO EC Actual 654ppm example Set point 1000ppm 6...

Страница 21: ...y 3 Per 1 12 00 14 00 Per 2 18 00 00 00 Etc up to Sunday and vacations Vacations mm dd up to 24 periods 4 1 01 01 01 01 example 1 January 2 12 25 12 25 example 25 December 1 Time Date Day Setting see...

Страница 22: ...d pgr or Reduced speed pgr menu as indicated in chapter VII 2 Once on this menu press the OK key Fill in the desired value Validate by pressing the OK key to go to the next field Use the down arrow to...

Страница 23: ...the welcome screen VII 3 3 b CARMA LOBBY EC 5 chapter VII 2 You can change the constant pressure of your unit for each fan to set your flow rates To set your initial HS flow rate force the system int...

Страница 24: ...t changeable If you increase or decrease a value all the others should be increased by the same value to comply with this air relationship principle Validate by pressing the OK key to go to the next f...

Страница 25: ...to the Configuration menu For this you should get the Service level access rights Follow the procedure given below Enter the code 2222 with the help of the directional keys and then validate with the...

Страница 26: ...ll be able to enable the MODBUS and modify the PLA and ELA addresses 1 Activation of MODBUS Inactive as standard 2 PLA ELA address addressing of the regulator as standard PLA 254 ELA 254 Access rights...

Страница 27: ...on VII 3 8 c LON Communication if CORRIGO with LON option No parameter is to be set in the Corrigo you will find the required files at the following address ftp ftpserver regin se Communication 20vari...

Страница 28: ...d AR vent fault Return air fan not working A 30s 120s for LOBBY MAC2 QUAT TRO EC The pressure switch is wrongly connected the pressure switch should be set at 30Pa The motor is not working The pressur...

Страница 29: ...rror Defrost temperature probe error C 5s The defrost temperature probe SDG is not working or is wrongly wired see chapter V Supp temp regulator error Defrost battery probe error C 5s The defrost batt...

Страница 30: ...is described below A condenser is used to back up the memory and to operate the clock for about 10 minutes after the current has been dut If the battery change operation takes less than 10 minutes the...

Страница 31: ...transmitted to the external items unit and regulation Check the electrical connections every year Filtration do not damage the filtering media Classification Filtration efficiency EUROVENT Reference W...

Страница 32: ...GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 32 36 X NOTES Date Observations...

Страница 33: ...setting LS Factory setting HS Factory setting LS 90 80 40 MIN GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 33 36 Flow rate m3 h...

Страница 34: ...setting HS Factory Setting LS 80 100 40 MIN GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 34 36 Flow rate m3 h Static pressure p...

Страница 35: ...ing HS Factory Setting LS Factory Setting HS Factory Setting LS GTDHR FIRST PREMIUM INFINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 35 36 Flow rate m3...

Страница 36: ...FINITE ENERGY RECOVERY UNIT MS CDF 001 A Ind A update 01 07 2011 Created by JC Validated by AR 36 36 http www airtradecentre com 90 70 60 50 40 80 Factory setting Factory setting 100 Flow rate m3 h St...

Отзывы: