Installation & Servicing instructions
AT
AG XL
30
7.5.2
Collective flue gas outlet over-pressure
An installation with a collective flue gas outlet over-pressure in combination
with individually controlled boilers (e.g. 0-10 V control), where no bus cable
AX00600U is connected, is NOT allowed.
Diameter and venting lengths of the flue gas outlet/air supply:
-
Open system with over-pressure.
Table
7.5.2.a
Diameter and venting lengths of the flue gas outlet/air supply:
-
Closed system with over-pressure.
Please contact ATAG Heating Ltd.
d
d
h
=d
=d
d
d
d
d
h
Output (P)
kW at
80/60°C
70 110 140 h = 2 - 5 h = 6 - 10 h = 11 - 15 h = 16 - 20
152 1
1
100
100
110
110
180 1
1
120
120
130
130
212
1
1
120
130
130
150
240
2
120
130
150
150
272 1
1
1
150
150
180
180
300 1
2
150
180
180
180
332
1
2
180
180
180
180
360
3
180
180
180
180
392 1
1
2
180
180
180
200
424
2
2
200
200
200
220
452
1
3
200
220
220
220
480
4
200
220
220
220
512 1
1
3
200
220
220
220
544
2
3
220
230
230
230
572
1
4
230
230
250
250
600
5
230
230
250
250
632 1
1
4
230
230
250
250
660 1
5
250
250
250
250
692
1
5
260
260
260
260
720
6
280
280
280
280
752 1
1
5
280
280
280
280
784
2
5
280
280
280
280
812
1
6
280
280
280
280
840
7
280
280
280
280
872 1
1
6
280
280
280
280
900 1
7
280
280
280
300
932
1
7
300
300
300
300
960
8
300
300
300
300
Pa = 50Pa
Type XL
Dimensions cascade flue ATAG XL
Open system, overpressure, parallel
d = minimum diameter Ø in mm
NOTE!
1. IPX0D at flue category B
23
and B
33
2. Only with bus cable AX00600U connected!
3. Adjust parameter 102 to 2