Installation & Servicing instructions
AT
AG XL
29
7.5.1
Collective flue gas outlet under-pressure
Diameter and venting lengths of the flue gas outlet/air supply:
-
Open system, with under-pressure
(calculated with thermal draft)
under atmospheric circumstances.
Table
7.5.1.a
Diameter and venting lengths of the flue gas outlet/air supply:
-
Closed system, with under-pressure
(calculated with thermal draft)
under atmospheric circumstances.
Table
7.5.1.b
d
d
h
=d
=d
d
d
d
d
h
Output (P)
kW at
80/60°C
70
110 140 h = 2 - 5 h = 5 - 9 h = 9 - 13 h = 13 - 17
152
1
1
210
200
190
190
180
1
1
210
200
190
190
212
1
1
210
200
190
190
240
2
210
200
190
190
272
1
1
1
300
270
260
250
300
1
2
300
270
260
250
332
1
2
300
270
260
250
360
3
300
270
260
250
392
1
1
2
360
330
310
300
424
2
2
360
330
310
300
452
1
3
360
330
310
300
480
4
360
330
310
300
512
1
1
3
440
380
360
340
544
2
3
440
380
360
340
572
1
4
440
380
360
340
600
5
440
380
360
340
632
1
1
4
470
420
400
380
660
1
5
470
420
400
380
692
1
5
470
420
400
380
720
6
470
420
400
380
752
1
1
5
550
470
430
410
784
2
5
550
470
430
410
812
1
6
550
470
430
410
840
7
550
470
430
410
872
1
1
6
600
510
470
440
900
1
7
600
510
470
440
932
1
7
600
510
470
440
960
8
600
510
470
440
Assumptions: Trega-cap on flue outlet, cross-cap on air intake.
In case of open outlet or diffuser pressures will be better.
Tinside, Toutside= + 20C, O2= 4,7%, Trg=50C.
Dimensions cascade flue ATAG XL
Open system, underpressure
Type XL
d = minimum diameter Ø in mm
Output (P)
kW at
80/60°C
70 110 140 h = 2 - 5 h = 5 - 9 h = 9 - 13 h = 13 - 17
152 1
1
240
220
220
220
180 1
1
240
220
220
220
212
1
1
240
220
220
220
240
2
240
220
220
220
272 1
1
1
330
300
290
270
300 1
2
330
300
290
270
332
1
2
330
300
290
270
360
3
330
300
290
270
392 1
1
2
390
370
350
330
424
2
2
390
370
350
330
452
1
3
390
370
350
330
480
4
390
370
350
330
512 1
1
3
460
410
390
380
544
2
3
460
410
390
380
572
1
4
460
410
390
380
600
5
460
410
390
380
632 1
1
4
500
460
440
420
660 1
5
500
460
440
420
692
1
5
500
460
440
420
720
6
500
460
440
420
752 1
1
5
550
500
470
460
784
2
5
550
500
470
460
812
1
6
550
500
470
460
840
7
550
500
470
460
872 1
1
6
600
540
510
490
900 1
7
600
540
510
490
932
1
7
600
540
510
490
960
8
600
540
510
490
Assumptions: Trega-cap on flue outlet, cross-cap on air intake.
In case of open outlet or diffuser pressures will be better.
Tinside, Toutside= + 20C, O2= 4,7%, Trg=50C.
Type XL
d = minimum diameter Ø in mm
Dimensions cascade flue ATAG XL
Closed system, underpressure, parallel
NOTE!
1. IPX0D at flue category B
23
and B
33