Installation & Servicing instructions
AT
AG XL
59
Annex A
Technical specifications
Boiler type
XL70
XL110
XL140
Type heat exchanger
OSS4
OSS4
OSS4
OSS2
OSS4
Input Hs CH
kW
68,5
107,9
136,4
Qn Input Hi CH
kW
61,8
97,3
123
Efficiency class according BED
Efficiency (50/30°C low load, Hi)
%
110,2
110,3
110,2
Efficiency according EN677 / EN15417 * (36/30°C part load, Hi)
%
109,8
109,2
108,9
Efficiency according EN677 / EN15417 * (80/60°C full load, Hi)
%
97,3
97,6
97,6
Modulation range CH (capacity 80/60°C)
kW
8,8 - 60,1
14,8 - 95,0
17,6 - 120,0
Modulation range CH (capacity 50/30°C)
kW
9,9 - 65,0
16,8 - 102,3
19,8 - 130,0
Flue gas pressure
Pa
175
195
195
Nox class EN483
Nox according to EN483 and EN15420 (year measurement)
mg/kWh
34,02
35,15
36,23
Nox at 0% O
2
according to EN483 and EN15420
mg/m
3
38,02
40,07
41,30
Nox at 3% O
2
according to EN483 and EN15420
mg/m
3
33,34
34,45
35,51
O
2
%
CO
ppm
Flue gas non-return valve present
yes
yes
yes
Flue gas temp. CH (80/60°C on full load)
°C
76
73
77
Flue gas temp. CH (50/30°C on low load)
°C
30
30
30
Gas consumption G20 CH (at 1013 mbar/15°C)
m
3
/h
6,53
10,29
13,01
Gas category
Boiler flue category
Electr. power consumption max.
W
161
250
322
Electr. power consumption part load
W
44
86
88
Electr. power consumption stand by
W
2,5
3,7
3,7
Current
V/Hz
230/50
230/50
230/50
Degree of protection acc. EN 60529
Weight (empty)
kg
65
83
87
Mounting weight
kg
54
72
76
Width
mm
660
660
660
Height
mm
1065
1065
1065
Depth
mm
460
460
460
Mounting height (excl. flue connection)
mm
1715
1715
1715
Water content CH
l
7
12
14
Overrun time pump CH
min
2
2
2
P
MS
Water pressure min./max.
bar
0,7 / 4
0,7 / 4
0,7 / 4
Flow temperature max.
°C
85
85
85
Type pump Grundfos UPM**
OSS4
OSS2
GEO 25-85
-
GEO 25-85
2 25-60
GEO 25-85
GEO 25-85
Label
CE product identification number (PIN)
Technical specifications Propane gas
Boiler type
XL70
XL110
XL140
Type heat exchanger
OSS4
OSS4
OSS4
OSS2
OSS4
CO
2
%
10,5
10,5
10,5
O
2
%
5,1
5,1
5,1
Restriction plate diameter
mm
5,7
-
5,7 (OSS4)
5,2 (OSS2)
5,7
5,7
Pre-pressure
mbar
Load(H
i
)
kW
61,8
94,9
123
Gas consumption G31 (1015mbar, 15°C)
kg/h
4,80
7,37
9,54
m
3
/h
2,52
3,87
5,01
Modulation range (80/60°C)
kW
30,3-60,1
45,9-95,0
60,5-120,0
Modulation range (50/30°C)
kW
33,0-65,0
50,7-102,3
66,0-130,0
ErP specifications according to European Directive 2010/30/EU
Boiler type
XL70
XL110
XL140
Seasonal space heating energy efficiency class
A
Rated heat output of preferential heater (P
n
)
kW
60
95
120
Annual energy consumption (Q
HE
)
GJ
20
30
39
Seasonal space heating energy efficiency of the preferential heater
(η
s
)
%
94
94
94
Sound power level, indoors (L
WA
)
dB
51
52
53
* EN15417 = Specific requirements for condensing boilers with a nominal heat input exceeding 70 kW up to 1000 kW.
** There are no pump height values specified because the XL boiler should always be connected to a low velocity header.
100
4,7
IPX4D (IPX0D for B
23
& B
33
)
6
Technical specifications Natural gas
see data plate propane
ATAG XL-Series
ATAG XL-Series
II2H3P
B23 B33 C13 C33 C43 C53 C63 C83 C93
0063CM3648