5
Product description
The ATAG XL W is a condensing and
modulating gas boiler with one or two
pre-mix burners, which is attached to a
wall. It is characterized by the following
features:
-
A large modulation range that
guarantees a long burner service
life, while minimizing standby
losses, start-up emissions and
material wear-and-tear.
-
Flue gas temperature below 80°C
-
Also suitable for room sealed
conditions
-
Control panel with all operational
elements
-
Microprocessor, with multi-
functional display
-
Automated ignition, with repetition
and ionization monitoring
-
Water pressure monitoring
- Energy-saving
pump
-
Stainless steel heat exchanger
with smooth tube condenser
- Very
maintenance-friendly
-
Ready for weather-dependent
control (accessory)
-
Cascadecontroller up to 8 boilers
-
External controls (accessory) by
RQRႇH%XVRU9
-
Modern metal panelling,
stove-enamelled
Functional description
7KHFRQWUROXQLWPRGL¿HVWKHKHDWLQJ
performance to the current heating
requirements, by changing the
default values of the fan rotating
VSHHG,QWKLVUHJDUGWKHERLOHUÀRZ
temperature is continually measured
via a sensor. In case of a deviation
of the actual temperature from the
target temperature, the control unit
reacts immediately and adjusts the
RPM of the fan, and with that the boiler
performance via the gas armature.
A deviation can be due to:
-
A changed default value of the
boiler temperature, via the boiler
heating control unit
-
A change on the outdoor
temperature
-
Request for Domestic Hot Water
-
Changed heating curve
By means of the integration of the
individual components in a system,
and within the control range of the
equipment, it is ensured that the boiler
performance always corresponds to the
actual heating requirements.
Delivery scope
The boiler, which has been assembled
at the factory and is ready to use,
is delivered in cardboard packaging.
The following is contained in the
delivery scope of the ATAG XL W :
0RGXODWLQJKLJKHႈFLHQF\
JDV¿UHGERLOHUWRN:
+LJKHႈFLHQF\SXPSV
- Boiler/Cascade
controller
Accessories:
%RLOHUFRQQHFWLRQ¿WWLQJV
- Headers for 2 and 3 boilers
- Low loss headers up to 1600kW
- Plate heat exchanger up to 800kW
- Insulation packs
- Boiler frames for free standing units
([KDXVWSLSHFRQQHFWLRQ¿WWLQJV
- Control for 3 extra heating zones
- Open bus interface
For detailed information see the
chapter “delivery scope”.
Legend:
1. heat exchanger 1 (see table)
2. heat exchanger 2 (see table)
3. ignition electrode
4. detection electrode
5. fan unit
6. venturi
7. gas valve
8.
automatic air vent
9. manual air vent
10. main switch 230V
11. boiler control unit
12. control unit HMI
13. connection terminal
14. connection terminal cascade
bus communication
15. connection terminal pc
16. dirt collector
17. circulation pump
18. water no return valve
ÀXHFRQQHFWLRQ
20. air supply
FROOHFWLYHÀXHSLSH
22. data plate
23. drainage cap
24. clip 3 zone (optional)
DLUÀXHFRQQHFWLRQFRQFHQWULF
(optional for ATAG XL W
75-105-125-150)
26. water pipe connection
1 1/2" (optional)
27. gas pipe connection
1" (optional)
7 ÀRZVHQVRU
7D VHFRQGDU\ÀRZVHQVRU
T2 return sensor
P1 water pressure sensor
APS Air Pressure Switch
HV high voltage electrical supply
LV low voltage electrical supply
G gas pipe
$ ÀRZSLSH&+
R return pipe CH
C condensate drain pipe
Product description
ATAG XL W
Boiler type
([FKDQJHU
([FKDQJHU
75
iCon XL1
-
105
iCon XL2
-
125
iCon XL1
iCon XL1
150
iCon XL1
iCon XL1
180
iCon XL2
iCon XL1
210
iCon XL2
iCon XL2