36
Parallel boiler connection
The boiler comes as standard with a
SDUDOOHOFRQQHFWLRQIRUWKHÀXHJDV
outlet and air supply system.
For the air supply opening (1) diameter
DQGWKHÀXHJDVRXWOHWFRQQHFWLRQ
see table below.
The air supply channel can be
connected to it, or, if it is installed as an
“open device” (Drainage category B),
DQDLU¿OWHUPXVWEH¿WWHG
Concentric boiler connection
The boilers 75-105-125-150 can be
converted into a concentric connection
using the parallel/concentric adapter
100/150 (optional) and carrying out the
following tasks:
-
Open and remove the front panel
and the top panel (follow the
instruction on page 42.
-
Lift the parallel connection.
-
Disconnect the main switch 230V
connection and remove it.
-
Replace the parallel connection
with parallel concentric adapter.
&RQQHFWDQG¿WWKHPDLQVZLWFK
230V according to previous
FRQ¿JXUDWLRQ
The air supply opening has a diameter
of ø150mm.
7KHÀXHJDVRXWOHWFRQQHFWLRQKDVD
diameter of ø100mm.
7KHÀXHJDVRXWOHWDLUVXSSO\V\VWHP
is then connected to the concentric
connection component.
Installation
Connections
$LUÀXHJDVGXFWVIRULQGLYLGXDOERLOHUV
The ATAG XL W-boilers can be used
both in an “open” and in “room sealed”
system.
Open system
The required combustion air is taken
from the immediate environment
(boiler room). For this purpose, please
comply with the applicable boiler room
ventilation regulations.
When using boiler category B23 or
B33 as an ‘open boiler’, the protection
degree of the boiler will be IPX0D
instead of IPX4D.
$QDLU¿OWHUPXVWEH¿WWHGRQWKHDLU
intake of the boiler (available as an
accessory on pages 15-17.
Room sealed system
The required combustion air is sucked
in from the outside through a duct.
This improves installation possibilities
within a building. In general, outside air
is cleaner than air from the boiler room.
:KHQWKHERLOHULVZRUNLQJLW
produces a white plume of water
vapour. This plume is harmless but
PD\FDXVHVRPHLQFRQYHQLHQFH
particularly in the case of wall
WHUPLQDO$VDUHVXOWURRIWHUPLQDOV
are preferred.
,QDURRPVHDOHGLQVWDOODWLRQURRI
terminals should be at the same
KHLJKWSUHYHQWLQJÀXHJDVIURP
being sucked in by an other boiler
(recirculation). Outlets in recesses
and near erected walls may also
EULQJDERXWÀXHJDVUHFLUFXODWLRQ
Recirculation has to be prevented at
all times.
Boiler type
$LUGXFWÀXHJDVGLDPHWHU
XL75W
100 - 100
XL105W
100 - 100
XL125W
100 - 100
XL150W
100 - 100
XL180W
130 - 130
XL210W
130 - 130
2
1
2
4
1
3
Fan settings correction
By setting parameter (21-2-4) it is
possible to compensate for a higher
ÀXHJDVSUHVVXUHGLႇHUHQFH,WLV
required to have a pressure drop
FDOFXODWLRQRIWKHDSSOLHGÀXHJDV
system.
According the calculated pressure
drop, the correct value for parameter
(21-2-4) has to be chosen from the
table below.
For setting parameters see the
applicable chapter.
Flue Gas System pressure drop
Parameter
(21-2-4)
XL75
XL105
XL125
XL150
XL180
XL210
0 - 600
156
243
143
200
215
265
700
204
295
177
230
280
321
800
224
350
207
275
313
370
900
250
405
240
300
375
-
1000
278
457
260
304
375
-