41
Flue gas system
Connections
Collective flue gas outlet overpressure
Diameter and venting lengths of the flue gas outlet/air supply:
Closed system with over
-
pressure.
Closed system, overpressure, parallel
Output (80/60)
d = minimum diameter Ø in mm
[kW]
h = 2
-
5
h = 6
-
10
h = 11
-
15
h = 16
-
20
114
–
285
150
150
150
150
285
-
524
150
200
200
200
524
-
1440
180
300
300
300
Содержание XL-W 105
Страница 2: ...2...
Страница 27: ...27 Technical description Declaration of conformity...
Страница 44: ...44 Boiler Installation Electrical connection...
Страница 45: ...45 Boiler Installation Electrical connection...
Страница 52: ...52 Boiler Installation Electrical connection Cascade control...
Страница 68: ...68 Accessories Hydraulics Single boiler Dimensional sketch for 3905173 LLH dT10 20K WALL HUNG TLPLUS...
Страница 77: ...77 Accessories Cascade Low loss headers Dimensional sketch for 3905176 LLH DN100 DUO...