8
Technical description
Sales text ATAG XL
-
W 105
ATAG XL
-
W 105
Wall
-
hung condensing gas boiler
Overview of features:
•
compact, pre
-
assembled construction and ready for connection
•
stainless steel heat exchanger
•
Insulation in expanded polypropylene
•
premixed burner in material ceramic for continuous adjustment of power
•
Control unit ACP for combustion management, modulation and safety pump modulation management and
flow measurement via the ACP unit
•
combustion control with the ionization principle
•
automatic temperature control
•
0
-
10 V DC input for connection to an external regulation system
•
alarm output or operating status
•
connections for the flow probe of the heating circuit, DHW and external probe
•
ACP control unit with LCD display capacitive touch with led indication status: active / standby / lock, oper-
ating mode selection DHW or central heating, cascade manager integrated, chimney sweep mode with
power selection minimum / maximum regardless of outside temperature, regulation of the heating flow tem-
perature, DHW temperature regulation, e
-
bus2 connections for connection with accessories from the ATAG
offer
•
Ready for connection to BMS systems supported protocols Modbus, bacnet, lonworks, KNX with dedicated
accessory
•
Ready for systems management, solar thermal through dedicated accessory
•
Possibility of pump management DHW circuit via diverter valve or storage heating pump, single heating
zone management via power supply pump and modulation
•
Operating hours counter, alarm and fault history
•
support for wall mounting included
•
automatic air vent valve
•
flue non return valve
•
modulating pump pre
-
mounted in the boiler modulating with flow measurement and diagnostics
Nominal
thermal
power
at
full
load
with 80/60°C: 89.4 kW
with 50/30°C: 99.0 kW
Nominal heat input full load Net: 92.3 kW
Gross seasonal efficiency: 95,.2%
Type
of gas:
natural
gas
Gas inlet pressure max/min: 25
-
17mbar
NOx: < 24 mg/kWh
BREEAM credits: 2
Electrical
connection: 230 V (50 Hz)
Dimensions
(HxWxD): 1050x530x675 mm
Weight: 80 kg
Fittings
-
air /
flue gas: 100/100 mm
-
water: R 2 ''
-
gas: R 1/2 ''
Efficiency class: A / A
SSIGA approval:
For water quality information refer to the instruction booklet
Содержание XL-W 105
Страница 2: ...2...
Страница 27: ...27 Technical description Declaration of conformity...
Страница 44: ...44 Boiler Installation Electrical connection...
Страница 45: ...45 Boiler Installation Electrical connection...
Страница 52: ...52 Boiler Installation Electrical connection Cascade control...
Страница 68: ...68 Accessories Hydraulics Single boiler Dimensional sketch for 3905173 LLH dT10 20K WALL HUNG TLPLUS...