background image

 ENERGY CUT OUT AND CYLINDER THERMOSTAT (INDIRECT ONLY) 

As a requirement of Building Regulations the iSteel units are fitted with a thermal cut-out in addition to the normal control 
thermostat. This unit should be fitted to the dedicated boss on the cylinder and wired to the two port valve controlling 
the primary flow (see wiring diagram). 

 DISCHARGE ARRANGEMENT 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
This guidance is available as a download of the G3 Approved Document from www.planningportal.gov.uk. 
 
The discharge from both the temperature relief and expansion relief valves can be joined together via a 15mm end feed 
tee.  
 
It is important that any discharge water does not collect in this pipe-work and can run freely to the tundish. 
 
The tundish should be mounted in a vertical and visible position located in the same space as the unvented hot water 
storage system and be fitted as close as possible and within 600mm of the safety device e.g. the temperature relief valve. 
The discharge pipe-work from the tundish must be routed in accordance with Part G3 of the Building Regulations.  
 
The discharge pipe from the tundish should terminate in a safe place where there is no risk to persons in the vicinity of 
the discharge, be of metal and: 

 

Be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic 
resistance exceeds that of a straight pipe 9m long i.e. discharge pipes between 9m and 18m equivalent resistance 
length should be at least two sizes larger than the nominal outlet size of the safety device, between 18 and 27m 
at least 3 sizes larger, and so on. Bends must be taken into account in calculating the flow resistance. An alternative 
approach for sizing discharge pipes  would be to follow BS6700 Specification for design installation, testing and 
maintenance of services supplying water for domestic use within buildings and their curtilages. 

 

Have a vertical section of pipe at least 300mm long, below the tundish before any elbows or bends in the pipework. 

 

Be installed with a continuous fall. 

 

It is preferable for the discharge to be visible at both the tundish and the final point of discharge but where this is 
not possible or practically difficult there should be clear visibility at one or other of these locations. 

 
Examples of acceptable discharge arrangements are: 

1.

 

Ideally below the fixed grating and above the water seal in a trapped gulley. 

2.

 

Downward discharges at a low level; i.e. up to 100mm above external surfaces such as car parks, hard standings, 
grassed  areas  etc.  are  acceptable  providing  that  where  children  play  or  otherwise  come  into  contact  with 
discharges, a wire cage or similar guard is positioned to prevent contact whilst maintaining visibility. 

3.

 

Discharges at a high level; e.g. in to metal hopper and metal down pipe with the end of the discharge pipe clearly 
visible (tundish visible or not) or onto a roof capable of withstanding high temperature discharges of water and 
3m from any plastic guttering systems that would collect such discharges (tundish available). 

4.

 

Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited 
to not more than 6 systems so that any installation can be traced reasonably easily. The single common discharge 
pipe should be at least one pipe size larger than the largest individual discharge pipe to be connected. If unvented 
hot water storage systems are installed where discharges from safety devices may not be apparent i.e. in dwellings 
occupied by blind, infirm or disabled people, consideration should be given to the installation of an electronically 
operated device to warn when discharge takes place. 

 

Any queries with regard to discharge arrangement contact your local council planning office. 

600 mm Max 

Содержание iSteel 120

Страница 1: ...iSteel INSTALLATION MANUAL ISSUE 2015 V1 FOR MORE INFORMATION GO TO www atagheating co uk...

Страница 2: ...eir G3 unvented qualification The installation of this product is also notifiable under the national Building Regulations ONCE COMPLETED THIS INSTRUCTION MANUAL IN ITS ENTIRETY SHOULD BE LEFT WITH THE...

Страница 3: ...ditional upstream pressure reducing device should be fitted A minimum of 22mm supply pipe work should ideally be provided and existing 1 2 15mm cold mains pipe work may need to be upgraded Hard water...

Страница 4: ...e Sealed or vented primary circuits can be used to comply with normal installation practice the primary pressure should not exceed 3 bar although the coil in the iSteel is suitable for up to 7 bar if...

Страница 5: ...nd maintenance of services supplying water for domestic use within buildings and their curtilages Have a vertical section of pipe at least 300mm long below the tundish before any elbows or bends in th...

Страница 6: ...the solar heat source Either primary coil connection may be used for flow or return The solar cylinder sensor supplied is inserted into the lower thermostat pocket and the energy cut out into the upp...

Страница 7: ...6 N 3 Port Mid Position E HTG ON DHW ON DHW OFF L N E SL 1 2 3 1 2 3 L N E N L N E 2 3 2 Port Heating Cutout combined Duostat 2 Port DHW PUMP Wiring Centre Room Stat Programmer Boiler G Grey Bl Blue...

Страница 8: ...your discharge pipework is free from debris and is carrying the water away without spillage over the tundish and release the valves and check that they re seat properly GENERAL Servicing should only...

Страница 9: ...ou have a problem in the first year contact the plumber who fitted the unit Thereafter contact the plumber who carries out the annual servicing for you If your iSteel develops a leak we will supply yo...

Страница 10: ...n of the boiler and its controls EXPANSION VESSEL Symptoms Possible causes Follow up action Discharge of water from the relief valve Expansion Vessel is too small Vessel needs resizing and installatio...

Страница 11: ...INLET CONTROL GROUP Fault Finding Information...

Страница 12: ...TUNDISH Fault Finding Information...

Страница 13: ...T P RELIEF VALVE Fault Finding Information...

Страница 14: ...DUAL THERMOSTAT Fault Finding Information...

Страница 15: ...IMMERSION HEATER Fault Finding Information...

Страница 16: ...ENERGY CUT OUT Fault Finding Information...

Страница 17: ......

Страница 18: ......

Страница 19: ...to third parties in the normal course of business In this respect the Buyer shall act in the capacity of the Companies commission agent and the proceeds of such sale 6 6 1 shall be held in trust for u...

Страница 20: ...ary Pressure Indirect Only 3 Bar Cylinder Data Table Capacity Weight Kg Empty iSteel 90 Direct 90 21 Indirect 88 27 iSteel 120 Direct 120 25 Indirect 118 31 iSteel 150 Direct 150 30 Indirect 148 35 Tw...

Отзывы: