 FAULT FINDING INFORMATION 

 

 UNVENTED CYLINDER 

Symptoms 

Possible causes 

Follow up action 

Cylinder appears to leak 
from within the case. 

Loose cylinder Connection. 

Check all connection points including 
immersion heaters to ensure integrity 
of joint and remake any suspect joints. 

Expansion valve operates 
and water is visible at the 
Tundish. 

Possible fault at Pressure Reducing 
valve. 

Follow fault finding information for 
Inlet Control Group. 

Back pressure from the system. 

Check all mixer type outlets are served 
by a balanced cold service. Where not 
re-pipe or install bespoke pressure 
reducing valve to offending outlet. 

Expansion valve operates 
when cylinder is heated. 

Possible fault at Expansion Vessel. 

Follow fault finding information for 
Expansion Vessel. 

Noise when operating tap 
outlet. 

Insecure pipework. 

Increase the number of pipe clips. 

Reduced Water flow. 

External work to public mains. 

Wait for works to be completed. 

Debris from water mains. 

Strip & Clean or replace Inlet Control 
Group. 

Pressure reducing valve sticking. 

Strip & Clean or replace Inlet Control 
Group. 

No hot water available. 

Immersion heater failure. 

Follow fault finding information for 
immersion heater. 

Boiler failure. 

Check operation of the boiler and its 
controls. 

 

 EXPANSION VESSEL 

Symptoms 

Possible causes 

Follow up action 

Discharge of water from the 
relief valve. 

Expansion Vessel is too small. 

Vessel needs resizing and installation by 
appropriately qualified engineers. 

Pre-charge set incorrectly on vessel 
installation. 

Pre-charge requires setting while 
system is de-pressurised according to 
cylinder manufacturer’s 
recommendations. 

Membrane is ruptured and may require 
replacement. 

Replace membrane or entire vessel. 
Inspect Shrader valve for leaks or 
damage. 

Membrane may be partially  
de-pressurised due to natural losses 
and require re-pressurisation. 

Re-pressurise or consider replacement 
depending on ae of vessel and amount 
of pressure lost. Inspect Shrader valve 
for leaks or damage. 

Leak from flange or water 
connection. 

Failure of Flange Plate. 

Replace Flange Plate or entire vessel. 

Loss of torque in Flange retaining bolts. 

Re-tighten bolts as needed. 

Ruptured membrane has caused 
corrosion of vessel body resulting in 
pinhole leak. 

Entire vessel must be replaced. Inspect 
Shrader valve for leaks or damage. 

Vessel appears to be full of 
liquid when system is cold. 

Membrane is de-pressurised. 

Replace membrane or entire vessel. 
Inspect Shrader valve for leaks or 
damage. 

Water is discharged from 
vessel when Shrader pin is 
de-pressed for inspection of 
air pressure. 

Membrane is ruptured. 

Membrane or vessel requires 
replacement. 

 

Содержание iSteel 120

Страница 1: ...iSteel INSTALLATION MANUAL ISSUE 2015 V1 FOR MORE INFORMATION GO TO www atagheating co uk...

Страница 2: ...eir G3 unvented qualification The installation of this product is also notifiable under the national Building Regulations ONCE COMPLETED THIS INSTRUCTION MANUAL IN ITS ENTIRETY SHOULD BE LEFT WITH THE...

Страница 3: ...ditional upstream pressure reducing device should be fitted A minimum of 22mm supply pipe work should ideally be provided and existing 1 2 15mm cold mains pipe work may need to be upgraded Hard water...

Страница 4: ...e Sealed or vented primary circuits can be used to comply with normal installation practice the primary pressure should not exceed 3 bar although the coil in the iSteel is suitable for up to 7 bar if...

Страница 5: ...nd maintenance of services supplying water for domestic use within buildings and their curtilages Have a vertical section of pipe at least 300mm long below the tundish before any elbows or bends in th...

Страница 6: ...the solar heat source Either primary coil connection may be used for flow or return The solar cylinder sensor supplied is inserted into the lower thermostat pocket and the energy cut out into the upp...

Страница 7: ...6 N 3 Port Mid Position E HTG ON DHW ON DHW OFF L N E SL 1 2 3 1 2 3 L N E N L N E 2 3 2 Port Heating Cutout combined Duostat 2 Port DHW PUMP Wiring Centre Room Stat Programmer Boiler G Grey Bl Blue...

Страница 8: ...your discharge pipework is free from debris and is carrying the water away without spillage over the tundish and release the valves and check that they re seat properly GENERAL Servicing should only...

Страница 9: ...ou have a problem in the first year contact the plumber who fitted the unit Thereafter contact the plumber who carries out the annual servicing for you If your iSteel develops a leak we will supply yo...

Страница 10: ...n of the boiler and its controls EXPANSION VESSEL Symptoms Possible causes Follow up action Discharge of water from the relief valve Expansion Vessel is too small Vessel needs resizing and installatio...

Страница 11: ...INLET CONTROL GROUP Fault Finding Information...

Страница 12: ...TUNDISH Fault Finding Information...

Страница 13: ...T P RELIEF VALVE Fault Finding Information...

Страница 14: ...DUAL THERMOSTAT Fault Finding Information...

Страница 15: ...IMMERSION HEATER Fault Finding Information...

Страница 16: ...ENERGY CUT OUT Fault Finding Information...

Страница 17: ......

Страница 18: ......

Страница 19: ...to third parties in the normal course of business In this respect the Buyer shall act in the capacity of the Companies commission agent and the proceeds of such sale 6 6 1 shall be held in trust for u...

Страница 20: ...ary Pressure Indirect Only 3 Bar Cylinder Data Table Capacity Weight Kg Empty iSteel 90 Direct 90 21 Indirect 88 27 iSteel 120 Direct 120 25 Indirect 118 31 iSteel 150 Direct 150 30 Indirect 148 35 Tw...

Отзывы: