Installation & Servicing Instructions ATAG E-Series
37
18 Error indication
A detected error is indicated on the display by means of a blocking or error messages.
A distinction should be made between these two messages due to the fact that blocking
can be of a temporary nature, however, error messages are fixed lockings. The control
will try its utmost to prevent locking and will temporarily switch off the boiler by blocking
it. Below is a list of some of the messages.
Blocks
with a number in the last 2 positions.
Block 60:
Incorrect parameter setting of the minimum or maximum power.
Block 67:
A
'
T has been detected between flow and return sensor whereas the burner is not in operation. After
the
'
T has disappeared the block will disappear.
Block 80:
Maximum flue gas temperature has been exceeded (if present). The block will not be cancelled until
the flue gas temperature has lowered to a correct figure.
Block 81:
The flue gas sensor is not connected although it was connected to the control. The burner is blocked
until the flue gas sensor is reconnected.
Block 82:
The flue gas sensor has short-circuited, heat requirement blocked and pump capacity at minimum.
Block 85:
The control has not detected a water flow. The venting cycle is started. If during this cycle water
flow is detected, the venting cycle is ended and the burner is released.
Block 86:
The frequence of the power supply deviates more than 2,5Hz (<47,5Hz, >52,5Hz)
Error
with a number in the last two positions.
Error 00:
Poor flame-forming
Error 01:
short-circuit of 24 volt circuit
Error 02:
no flame-forming
Error 04:
the control unit has detected an error
Error 05:
fault control unit
Error 12:
fuse 24 volt/3AT faulty
Error 19:
fault control
Error 28:
number of revolutions not reported back from fan