5-8
Trouble & Possible Cause Symptom & Remedy
D.
No temperature pull up.
1.
No power to heater.
2.
Power to heater.
REMEDY: Check overload and system
pressure.
1a. No power to chamber.
REMEDY: Check fuse or circuit breaker in
your line.
1b. Temperature controller defective.
REMEDY: Replace controller.
1c. Heat switch defective.
REMEDY: Replace switch.
1d. Relay defective (applies only for models
having relays.)
REMEDY: Replace relay.
1e. Heater connection loose or heater
defective.
REMEDY: Check connection to heater or
replace heater.
1f. Heat link open.
REMEDY: Replace heat link (do not attempt
to repair and do not short it out.)
2a. Heater connection broken.
REMEDY: Correct connection.
2b. Heater burned out.
REMEDY: Replace heater.
Содержание SD-302
Страница 3: ......
Страница 7: ......
Страница 11: ......
Страница 27: ...OPERATION 4 12 Sample Profile ...
Страница 31: ......
Страница 32: ...MAINTENANCE 5 1 GENERAL MAINTENANCE TROUBLE ANALYSIS AND SERVICE GUIDE ...
Страница 43: ......