3. Electrical Connections and Final Setup Continued
Step 5:
Adjust Closing Position Magnet (See Fig. 3) - With door in
the closed position, use finger to slide Closed Position
Magnet so it aligns directly with the Reed Switch.
Step 6:
Adjust Open Position Magnet - Use fingers to slide Open
Position Magnet 180° from Open Position Magnet.
Step 7:
Flip Breaker Switch to “RESET” to turn power on. Jump
terminals 1 and 2 (as shown in Fig. 2) to activate door. Note
open position of the door. Allow door to close.
Step 8:
Use finger to readjust the Open Position Magnet to desired
door open position.
Step 9:
Repeat Step 7 to verify door open position.
Step 10:
Make all connections necessary for any accessories to the
4-position Accessory Terminal (see Pages 9 - 11).
Step 11:
Make necessary adjustments to inverter (see Page 9).
Replace cover and cover screws.
Reed Switch
Closed Position
Magnet
Open Position
Magnet
Position Ring
Figure 3
Low Voltage
Control
Wiring
Incoming
Power
Input Power Configurations
CONCEALED WIRING
SURFACE WIRING
Optional Bracket
(for surface wiring)
Ground
Lead
Power
Leads
Ground
Screw
(Green)
Cable
Clamps
Conduit
by Others
(from top)
“T1” Power
Input
Terminal
Ground Wire Connection
– Ground wire must be secured to backplate
under head of (green) ground screw nearest to “T1” Power Input
Terminal. Screw labeled “GND”.
Terminal
Description
HOT
25
23
24
22
COM
Common power lead
Hot power lead
Circuit Breaker
Switch
Circuit Breaker
Common connection to Circuit Breaker /
Inverter
Thread conduit fitting(s) into backplate as shown. A second
conduit fitting is required for low voltage control wiring. CHECK
LOCAL CODES. Pull conduit out of header and attach to conduit
fittings before mounting Operator to door frame. Attach
incoming ground wire to backplate with ground screw as
illustrated in “Surface Wiring” illustration to the Right.
An optional bracket is provided for use with surface wiring.
Remove the two cable clamps screws and slip the bracket under
the cable clamps. Push the cable clamp screw through the
bracket holes and tighten. ½” conduit fittings can now be
installed on the bracket. Attach incoming ground wire to
backplate with ground screw as illustrated below.
24
23
22
25
HOT
COM
Breaker Switch
T1 Terminal
Block