3.  Electrical Connections and Final Setup Continued

Step 5:

   Adjust Closing Position Magnet (See Fig. 3) - With door in 

the closed position, use finger to slide Closed Position 
Magnet so it aligns directly with the Reed Switch.

Step 6:

   Adjust Open Position Magnet - Use fingers to slide Open 

Position Magnet 180° from Open Position Magnet.

Step 7:

   Flip Breaker Switch to “RESET” to turn power on.  Jump 

terminals 1 and 2 (as shown in Fig. 2) to activate door.  Note 
open position of the door.  Allow door to close.

Step 8:

   Use finger to readjust the Open Position Magnet to desired 

door open position.  

Step 9:

   Repeat Step 7 to verify door open position.  

Step 10: 

Make all connections necessary for any accessories to the  

4-position Accessory Terminal (see Pages 9 - 11).

Step 11:

 Make necessary adjustments to inverter (see Page 9).   

Replace cover and cover screws.

Reed Switch

Closed Position 
Magnet

Open Position

Magnet

Position Ring

 Figure 3

Low Voltage

Control

Wiring

Incoming

Power

Input Power Configurations

CONCEALED WIRING

SURFACE  WIRING

Optional Bracket
(for surface wiring)

Ground
Lead

Power
Leads

Ground
Screw
(Green)

Cable
Clamps

Conduit
by Others
(from top)

“T1” Power
Input
Terminal

Ground Wire Connection

 – Ground wire must be secured to backplate 

under  head  of  (green)  ground  screw  nearest  to  “T1”  Power  Input 
Terminal.  Screw labeled “GND”.

Terminal

Description

HOT

25

23

24

22

COM

Common power lead

Hot power lead

Circuit Breaker

Switch

Circuit Breaker

Common connection to Circuit Breaker / 
Inverter

Thread  conduit  fitting(s)  into  backplate  as  shown.    A  second 
conduit fitting is required for low voltage control wiring.  CHECK 
LOCAL CODES.  Pull conduit out of header and attach to conduit 
fittings  before  mounting    Operator  to  door  frame.    Attach 
incoming  ground  wire  to  backplate  with  ground  screw  as 
illustrated in “Surface Wiring” illustration to the Right.

An optional bracket  is provided for use with surface wiring.  
Remove the two cable clamps screws and slip the bracket under 
the cable clamps.  Push the cable clamp screw through the 
bracket holes and tighten.  ½” conduit fittings can now be 
installed on the bracket.  Attach incoming ground wire to 
backplate with ground screw as illustrated below.

24

23

22

25

HOT

COM

Breaker Switch

T1 Terminal
Block

Page 8

Содержание Norton 5700 Series

Страница 1: ...tallation and Instruction Manual Item No Description 1 Back plate 2 Door Closer 1601LAP or 1601BFLAP 3 Motor Assembly 5700M 4 Inverter 5700IN 5 Cover 5700COV 6 On Off switch 7 Circuit Breaker 8 120VAC...

Страница 2: ...cle before beginning the installation Use of an auxiliary door stop by others is always recommended An incorrectly installed or improperly adjusted door operator can cause property damage or personal...

Страница 3: ...X DRIVE SOCKET SCREW SLIDE ARM TUBE SLIDE ARM ROD ADA ANSI UL Information AmericansWith Disabilities Act A D A These door operators can be installed and adjusted to conform with A D A regulations ANSI...

Страница 4: ...ge Step 2 Using template above locate and prepare holes in the frame door Frame A Prepare six 6 holes for 1 4 20 machine screws or No 14 x 2 3 4 70mm wood screws Blind rivet nuts by others are suggest...

Страница 5: ...ments as necessary to the Sweep Speed S valve and Latch Speed L valve See Fig 2 below for location of valves Turn valves clockwise to reduce speed counter clockwise to increase speed Opening Cycle Adj...

Страница 6: ...Ceiling Clearance 1 3 4 44mm Min 2 1 4 57mm Max Door Thickness For frame reveals less than 3 76mm the arm adjusting rod can be field cut to a length of 9 1 2 241mm measured from centerline of connect...

Страница 7: ...ustments as necessary to the Sweep Speed S valve and Latch Speed L valve See Fig 6 below for location of valves Turn valves clockwise to reduce speed counter clockwise to increase speed Opening Cycle...

Страница 8: ...tion Magnet Open Position Magnet Position Ring Figure 3 Low Voltage Control Wiring Incoming Power Input Power Configurations CONCEALED WIRING SURFACE WIRING Optional Bracket for surface wiring Ground...

Страница 9: ...ease P1 Closing Speed CW Increase CCW Decrease H O TM Hold Open Time 5 30 Seconds CW Increase CCW Decrease P2 Opening Speed CW Increase CCW Decrease H O TQ Motor Torque at Hold Open Position CW Increa...

Страница 10: ...Strike Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts Notes 1 Power input to Door Operator Unit is at T1 Power Input Terminal not shown 120VAC 60Hz 2 Unit s Relay Rating f...

Страница 11: ...Unit s Relay Rating 30VDC 1A or 125VAC 5A Jumper Settings Place jumper to upper position for normally closed operation or to lower position for normally open operation JMP503 NC NO Jump activation inp...

Страница 12: ...ty Inc an ASSA ABLOY Group company All rights reserved Reproduction in whole or in part without the express written permission of Yale Security Inc is prohibited ASSA ABLOY 80 9357 0001 020 09 13 Page...

Отзывы: