background image

 

 
 
 

 

 
  
 
 

INSTALLATION  INSTRUCTIONS 

 

AND 

 

OPERATION  MANUAL 

 
 
 
 

FS-36EP, 56EP, 76EP Series 

(v2) 

(380V/400V/415V) 

 

Rolling

 

Fire Door Operators 

 

 

UL325-2010 Compliant 

 
 

Restricted Duty Operators 

 

SMART Control 

 
 
 

Summary of Contents for FS-36EP Series

Page 1: ...INSTALLATION INSTRUCTIONS AND OPERATION MANUAL FS 36EP 56EP 76EP Series v2 380V 400V 415V Rolling Fire Door Operators UL325 2010 Compliant Restricted Duty Operators SMART Control ...

Page 2: ...has exposed moving parts If the operator must be mounted less 8 ft 2 44 m above the floor then exposed moving parts must be protected by covers or guarding Contact the manufacturer 6 Do not connect the door operator to the source of power until instructed to do so 7 Locate the control station open close stop push button key station or the like a within sight of the door b at a minimum height of 5 ...

Page 3: ...PM 3 4 hp Door Speed 6 8 per sec average typical Brake Solenoid actuated brake ENTRAPMENT PROTECTION Sensing Edge Optional Sensing device attached to the bottom edge of the door Non Contact Device Optional Photo eye device Per the requirements of UL Standard 325 the door operator is setup for constant pressure to close the door As an alternative the door may be provided with a monitored entrapment...

Page 4: ...y for changes in installation positions NOTE Any change in mounting position may result in a change of operator rotation and consequently in a change of control functions Consult factory for any changes LS and RA mounting positions are LH operators RS and LA positions are RH operators Operators mounted in alternate positions LA RA require the long mounting legs in lieu of the standard short mounti...

Page 5: ...E Any change in mounting position may result in a change of operator rotation and consequently in a change of control functions Consult factory for any changes LS and RA mounting positions are LH operators RS and LA positions are RH operators Operators mounted in alternate positions LA RA require a straight mounting bracket in lieu of the standard off set bracket ...

Page 6: ...yout of the mounting holes on the bracket are correct 3 Bolt the operator mounting plate to the door bracket plate 4 Attach and tighten the three mounting legs to the mounting plate for 1 3 and 1 2 hp only 5 Mount the operator to the three legs and tighten for 1 3 and 1 2 hp only For 3 4 hp mount the operator base to the mounting plate Figure 1 for 1 3 hp and 1 2 hp Figure 2 for 3 4 hp ...

Page 7: ...r 1 3hp and 1 2hp see Figure 2 for the 3 4hp 7 The shelf or bracket must provide adequate support for the operator Prevent play between the operator and the door shaft The operator must be securely attached with the drive shaft parallel to the door shaft It may be necessary to field brace the operator bracket Door Sprocket Operator Drive Sprocket Correct Incorrect Figure 1 for 1 3 hp and 1 2 hp Do...

Page 8: ...uded in the operator may be used for adjustment See figure 1 S1 location for 1 3 hp and 1 2 hp See figure 2 T1 T2 for 3 4 hp 2 Once the drive chain has been tightened and the base leg screws have been set and then tighten the operator screws S1 Drive Chain Door Sprocket Drive Sprocket 1 4 S1 Drive Chain Door Sprocket Drive Sprocket 1 4 Figure 1 for 1 3 hp and 1 2 hp Drive Chain Door Sprocket Drive...

Page 9: ...ams in place adjust the limit switch cam E or F until the micro switch C or D clicking sound is heard 5 If the limit switch cam cannot be rotated to its desired position release the lever and move the door away from the desired position then adjust the limit switch cam to its desired position It may be necessary to repeat this step until the exact position has been reached 6 Repeat step 3 and 4 fo...

Page 10: ...he control panel 6 A separate fuse line of adequate capacity is needed for the operator 7 The operator must be properly grounded The ground screw painted green is located inside the control panel 8 For an operator system or external device requiring field installed wiring between a Class 2 output of an operator and an external device the type of wiring shall be R C AVLV2 8 AWM min 22 AWG rated 60 ...

Page 11: ...max above floor Entrapment Device Options Sensing Module Device Manufacturer Model ELR 2 wire resistive sensing edge Miller Edge Inc End of Line resistor type edge must have model number with Suffix T2 ME110 ME111 ME120 ME123 ME112 ME113 ME116 ME117 MT21 MU21 MT22 MU22 MC22 MU33 MC271 CPT223 MEL TXYY MEL RXYY RB G K10 ASO GE225 GE125 GE245 GE F45 GE F50 GE F56 GE F65 GE F85 GE F115 IR Monitored ph...

Page 12: ...uit as power wiring 4 Any wire connected to the control panel must be protected by conduit or other means to ensure the safety and permanency of the wiring Do not use radio controls with your operator unless some type of entrapment protection device has been installed Failure to do so may result in death or serious injury to person s trapped beneath the door Changing from left hand to right hand o...

Page 13: ...GE L1 L2 L3 Three phase power source See operator plate for correct voltage A 3 0 1 3 S10 S9 S8 S7 S11 S6 S5 Open Close 1 Stop 2 Open 3 Close 4 Com 9 10 Moving 10 10A Alarm Warning Signal 24VDC 11 12 Alarm Connection N C Dry Contact 24VDC MAX 0 5A 1 2 3 4 9 10 10A 11 12 31 32 E5 E6 36 37 P5 P6 CN29 CN28 CN9 CN10 JUMP FOR ENABLING RECLOSE TIMER CN28 CN29 ALARM TEST JUMPER CN9 CN10 CN26 Optional ext...

Page 14: ...ies 380V 400V 415V REVISION 0000 DATE 03 22 2021 B Auxiliary Function R3 R2 R1 R1 R2 R3 Radio control 24VAC Push button 24VAC B 2 Open door B 1 Close door Stop door STOP CLOSE OPEN B STOP CLOSE OPEN STOP CLOSE OPEN ...

Page 15: ... 1 setup T1 T2 C 1 C S17 S18 S16 S15 1 Timer 1 Mid open timer Timer starts counting when door leaves close limit Door stops after opening for set time Pressing open again at mid open position will cause door to open limit Timer 2 Close timer Timer is active when door stops and is not at close limit 2 Standard Mode Cycle counter ...

Page 16: ...ent is saved T1 T2 Min 1 Sec Set the desired time Max 99 Sec T1 T2 Mid Open Timer T1 T2 Max 99 Sec Min 1 Sec T1 T1 T1 T1 T1 4 To Set Timer 2 Reclose Timer Press T2 and hold for 5 seconds Display will flash Use or to increase or to decrease time Press T2 to save setting Without pressing no adjustment is saved Min 1 Sec T2 T1 T2 Min 1 Sec Set the desired time T1 T2 T1 T2 Timer to Close T2 T2 T2 T2 T...

Page 17: ...ON Close limit switch activated OFF Close limit switch not activated LED10 SLS AUX close limit contact ON Door at AUX close limit OFF Not at AUX close limit LED9 DEVICE Device light ON When the sensing device connected on terminal CN2 E5 E6 P5 P6 is normal OFF Sensing device disconnected failed or damaged LED30 VVS VVS Flashing Alarm warning signal or terminal CN2 1 4 not connected OFF Normal Cond...

Page 18: ...17 FS EP Series 380V 400V 415V REVISION 0000 DATE 03 22 2021 ...

Page 19: ...FS EP Series 380V 400V 415V REVISION 0000 DATE 03 22 2021 18 ...

Page 20: ...FS EP Series 380V 400V 415V REVISION 0000 DATE 03 22 2021 19 ...

Page 21: ...FS EP Series 380V 400V 415V REVISION 0000 DATE 03 22 2021 20 ...

Page 22: ... a month After adjusting either the force or the limit of travel retest the door operator s safety features Failure to adjust the operator properly may cause severe injury or death 5 For products having a manual release if possible use the manual release only when the door is closed Use caution when using this release when the door is open Weak or broken springs may cause the door to fall rapidly ...

Page 23: ...ETE Refer to the fire door installation instructions for connection of the release assembly or consult NFPA 80 and the authority having jurisdiction for fusible link location s and method Fusible link connection location Fusible link connection hole Remove cotter pin after installation Illustration only not drawn to scale See product for actual details ...

Page 24: ...losing Removing pressure from the CLOSE key position will cause the door to stop If a sensing edge is not installed on the bottom of the door and removing pressure from the CLOSE button or key switch position does not cause the door to stop this condition must be corrected immediately Improper operation could result in serious injury or death to person s trapped beneath the door 3 Door may also be...

Page 25: ...oper operation and full closure per NFPA 80 Do not lubricate motor Motor bearings are rated for continuous operation Inspect and service whenever a malfunction either door or operator is observed or suspected Before servicing always disconnect power supply to the operator Replace fuses only with those of the same type and rating All replacement parts must be obtained from the door manufacturer per...

Page 26: ...g module Secondary and Third Sensing Devices connect on 1st and 2nd sensing modules Parallel connection or AND Harness Part No ADA DA111 WH001 OR Harness Part No ADA DA111 WH002 Serial connection Primary Sensing Device Connection 1 2 3 or 2 3 1 Unplug the jumper connector to add modules Plug back the jumper connector if no additional module is used QST FS EP ADAPTER 5 Warning Power OFF When Connec...

Page 27: ...ON B2 OPEN Key switch B2 COM Warning Please Remove Jump Pin First See A A Remove Jump pin OPEN CLOSE STOP OPEN CLOSE KEY REQUIRED TO REMOVE COVER S T O P S T O P R BK R WH OPEN CLOSE NC NO C NC NO C STOP WH WH GR KEY SWITCH COM OPEN CLOSE KEY REQUIRED TO REMOVE COVER S T O P S T O P Key Switch with Stop Button and 3 Button Stations Key Switch with Stop Button Control Wiring for Key Switch with Sto...

Page 28: ...WH WH B2 B1 OPEN CLOSE STOP KEY ON OFF OPEN CLOSE STOP KEY LOCKOUT 3 2 BUTTON B1 B2 1 2 3 4 OPEN OPEN CLOSE CLOSE B2 B1 STOP B2 STOP B1 R BK GR KEY LOCKOUT 3 BUTTON 1 2 3 4 OPEN CLOSE STOP Key switch Key switch R WH GR BK STOP CLOSE OPEN ON OFF R2 R1 RADIO R3 R2 R1 Ceiling Pull Switch Station 1 4 CLOSE OPEN CLOSE OPEN R1 R3 R2 GR WH 3 2 1 WH BK GR WH BK Control Connections Diagrams 1 2 3 4 1 2 3 4...

Page 29: ...FS EP Series 380V 400V 415V REVISION 0000 DATE 03 22 2021 28 APPENDIX 4 1 NO 2 OFF ON PK PK ...

Reviews: