VIPEDIA-12 – Installation Guide
U-0641-0344.doc – Issue: 06 complete, approved
Page 19 of 44
⑩
CONTROL: Fault/Voice Alarm Relays and ASL BMB01 Serial Interface
1
2
3
4
5
6
7
8
CONTROL
Standard RJ45 jack
Pin CAT5 Cable (EIA 568-B)
Signal
Description
1 white/orange
Relay
1
N/C
Fault relay 1 N/C contact
2
orange
Relay 1 COM
Fault relay 1 COM contact
3
white/green
Relay 1 N/O
Fault relay 1 N/O contact
4
blue
Relay 2 COM
Voice Alarm relay COM contact
5
white/blue
Relay 2 N/O
Voice Alarm relay N/O contact
6
green
Relay 2 N/C
Voice Alarm relay N/C contact
7 white/brown
BMB
DXP
BMB control data / EIA RS485 9600 baud
(Data+)
8
brown
BMB DXN
As above but Data-
•
Relay 1 (Fault relay): NO contacts closed in normal operation, open on fault
•
Relay 2 (Voice Alarm relay): NO contacts open in normal operation, closed on Voice
Alarm
⑪
AUDIO INPUTS 1 to 12: Audio Inputs and RS485 Serial Interfaces 1 to 12
AUDIO INPUTS
1 TO 6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
AUDIO INPUTS
7 TO 12
AUDIO INPUTS 1 to 12:Standard RJ45 jack
Pin CAT5 Cable (EIA 568-B)
Signal
Description
1
white/orange
AUDIO IN+
Balanced Audio Input (+ve)
2
orange
AUDIO IN-
Balanced Audio Input (-ve)
3
white/green
DXP
Microphone control data
EIA RS485 19200 baud (Data+)
4 blue
+SUPPLY
+V DC supply output (as supply input,
fused at 350 mA per pair, i.e, inputs 1-2,
3-4, 5-6, 7-8, 9-10, and 11-12)
5
white/blue
+SUPPLY
Same as above
6
green
DXN
Microphone control data
EIA RS485 19200 baud (Data-)
7
white/brown
0V
0 V supply
8
brown
0V
Same as above
•
Power supply only if one or both inputs of the pair is/are configured as microphone
•
Fire microphones with hardwired PTT and Speak Now (input 1 or 2) should be
powered from an external power supply, i.e. not from the VIPEDIA-12