6.4 TURN-OFF
PROCEDURE
6.4.1 Systems
Not Equipped With The Seamless Transfer Option
Transfer power from the converter to the generator. This must be performed in a “break-before-
make” method, that is, at no time can the generator(s) and shore power converter be operated in
parallel.
Disable the Auto-Restart feature if enabled.
Press the
CONVERTER POWER OFF
(11) button. The red Converter Power OFF indicator LED
(11A) should now be lit. If the SUMMARY DISPLAY is active, it should indicate CONVERTER:
OFFLINE. Power has now been removed from the output, but the system remains active. The
system is now in the “standby” state.
Next press the
SHORE POWER OFF
(10) button. The red Shore Power indicator LED (10A)
should now be lit. This will initiate the inverter shutdown. The system will complete the shutdown
process within 10 seconds.
Turn the Disconnect Switch (14) to the OFF position. Open the shore power (input) circuit breaker
or switch to the converter.
The converter is now shut down.
Содержание AC36V-1
Страница 15: ...AC36V 1 3 AC45V 1 3 AC54V 1 3 Operations Manual 15 5 1 MECHANICAL INSTALLATION cont FIGURE 2 MECHANICAL OUTLINE...
Страница 16: ...AC36V 1 3 AC45V 1 3 AC54V 1 3 Operations Manual 16 5 1 MECHANICAL INSTALLATION cont FIGURE 3 CONTROLS...
Страница 34: ...AC36V 1 3 AC45V 1 3 AC54V 1 3 Operations Manual 34 6 5 REMOTE COMMUNICATIONS cont FIGURE 7 RS 232C PINOUT...
Страница 56: ...AC36V 1 3 AC45V 1 3 AC54V 1 3 Operations Manual 56 8 DIAGNOSTICS cont FIGURE 8 STATUS WORD BIT DEFINITIONS...