Ascon Tecnologic - KX6 - ENGINEERING MANUAL - 

PAG. 18

Now, proceed as follows:

1. 

Push the 

 button for more than 3 seconds.

2. 

The upper display will show 

PASS

 while the middle 

display will show 

0

.

3. 

By 

 and 

 buttons set a password equal to 

-81

.

4. 

Push 

 button. 

The instrument will show the acronym of the first 
configuration parameter group 

]

inP

.

5. 

By 

 button select the group of the first parameter of 

your list.

6. 

By 

 button select the first parameter of your list 

7. 

The upper display will show the acronym of the parameter  
while the middle display will show his current promotion 
level. The promotion level is defined by a letter followed 
by a number.  The letter can be:

c

:  It shows that this parameter is 

NOT

 promoted 

and it is present only in configuration. 
In this case the number is forced to zero.

A

:  It shows that this parameter has been promoted 

to the limited access level. 
The number will show the position in the limited 
access list.

o

:  It shows that the parameter has been promoted 

to the Operator level. 
The number will show the position in the limited 
access list.

8. 

By 

 and 

 buttons assign to this parameter the 

desired position.

Note: 

 Setting a value different from 0 the letter 

c

 will change 

automatically to 

A

 and the parameter is automatically 

promoted to the limited access level.

9. 

In order to modify the level from limited access 
to operator and vice versa, push 

 button and, 

maintaining the pressure, push 

 button. 

The letter will change from 

A

 to 

o

 and vice versa.

10. 

Select the second parameter that you want to add to the 
assistance level and repeat step 6, 7 and 8.

11. 

Repeat steps 5, 6, 7, 8 until the list has been completed.

12. 

When you need to exit from promotion procedure, push 

 button and maintain the pressure for more than 10 s.  

The instrument will show the “standard display”.

Note: 

When you set the some number to two parameter, the 
instrument will use only the last programmed parameter.

Example:

 In the previous example, I have set for SP2 a 

promotion value equal to A3.
If now I set for SP3 a promotion value equal to 

o3

, the 

Limited Access list and the operator list becomes.

Parameter

Promotion 

Limited Access

Operator

- OPEr - 

o 1

OPEr

OPEr

- SP - 

o 2

SP

SP

- SP3 - 

o 3

SP3

SP3

- A.SP - 

A 4

A.SP

- AL1 - 

o 5

AL1

AL1

8  OPERATIVE MODES

As we said at paragraph 6.1, when the instrument is 
powered, it starts immediately to work according to the 
memorized parameter value.
In other words, the instrument has one status only, the “run 
time” status.
During “run time”  we can force the instrument to operate 
in three different modes: Automatic mode, Manual mode or 
Stand by mode:

 

In 

Automatic mode

 the instrument drives automatically 

the control output according to the parameter value set 
and the set point/measured value.

 

In 

Manual mode

 the upper display shows the measured 

value while the middle display shows the power output 
[preceded by 

H

 (for heating) or 

C

 (for cooling)], MAN is lit 

and the instrument allows you to set manually the control 
output power.  

No Automatic action will be made

.

 

In 

Stand by

 mode the instrument operates as an indicator. 

It will show on the upper display the measured value and 
on the middle display the set point alternately to the “

St.bY

” 

messages and forces the control outputs to zero.

As we have seen, it is always possible to modify the value 
assigned to a parameter independently from the operative 
modes selected.

8.1  Modify a parameter during 

“Operator level”

The instrument is showing the “standard display”.

1. 

Press the 

 button.

2. 

The upper display will show the acronym of the first 
parameter promoted to this level while the middle display 
will show its value.

3. 

By 

 and 

 button assign to this parameter the 

desired value.

4. 

Press the 

 button in order to memorize the new value 

and go to the next parameter.

5. 

When you want to come back to the “standard display” 
push the 

 button for more than 5 seconds.

Note: 

The parameter modification of the Operator level 
is subject to a time out.  If no button is pressed for 
more than 10 seconds, the instrument goes back to 
the “standard display” and the new value of the last 
selected parameter will be lost.

8.2  Enter the “Limited access level”

The instrument is showing the “standard display”.

1. 

Press the 

 button for more than 5 seconds;

2. 

The upper display will show 

PASS

 while the middle 

display will show 

0

;

3. 

By 

 and 

 buttons set the value assigned to 

[73] PAS2 (Level 2 password).

Notes: 1. 

The factory default password for configuration 
parameters is equal to 20.

2. 

Operator and assistange level of Parameter 
modification are protected by a time out.  If 
no button is pressed for more than 10 second 
the instrument comes automatically back to 
the Standard display, the new value of the last 
selected parameter is lost and the parameter 
modification procedure is closed.

Содержание KX6

Страница 1: ...ng exposed terminals and wiring on the back Select a mounting location having the following characteristics 1 It should be easily accessible 2 There is minimum vibrations and no impact 3 There are no...

Страница 2: ...e the 2 retainers To re insert the controller in its housing reverse the extraction procedure 2 3 General notes about wiring 1 Do not run input wires together with power cables 2 External components l...

Страница 3: ...Common 24 VAC DC Notes 1 The isolated input DI2 must be used in one of the modes determined by the link High level input 110 220 VAC Low level input 24 VDC VAC 2 Logic input 2 is isolated by the meas...

Страница 4: ...ot exceed 1 5 km at 9600 baud 2 7 Power Supply Power Supply 11 12 Supply Voltage 100 240 VAC 15 10 Notes 1 Before connecting the instrument to the power line make sure that line voltage is equal to th...

Страница 5: ...e Temperature drift It is part of the global accuracy Operating temperature 0 50 C 32 122 F Storage temperature 30 70 C 22 158 F Humidity 20 85 RH not condensing Electromagnetic compatibility and safe...

Страница 6: ...on parameters is protected by a password Note The instrument will show only the parameters consistent with the specific hardware and in accordance with the value assigned to the previous parameters e...

Страница 7: ...nd the OEM parameter set has NOT been loaded 2 Using the serial link it is always possible to send to the address 13H the corretct password in order to obtain the desired action 481 for the Factory se...

Страница 8: ...es automatically in MAN mode Removed the burnout condition the instrument remains in MAN mode until Auto mode is selected by OPEr parameter a command by serial link digital imput or by the key pressur...

Страница 9: ...vailable Always Range When at least one output is programmed as con trol output nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAo Absolute band alarm with alarm indication out...

Страница 10: ...19 AL1t is different from SE br Range 1 9999 engineering units Notes 1 The hysteresis value is the difference between the Alarm threshold value and the point the Alarm automatically resets 2 When the...

Страница 11: ...ange and stand by LbA group Loop break alarm General note about LBA alarm The LBA operate as follows applying the 100 of the power output to a process the process variable after a time due to the proc...

Страница 12: ...nditions e g set point change during tune execution etc Note Fast auto tune can start only when the measured value PV is lower than SP 1 2 SP Available When 39 cont PID or 3Pt Range 4 8 where 4 Oscill...

Страница 13: ...th a power output equal to the value it will use at steady state instead of zero and the undershoot will become very little in theory equal to zero Available When 39 cont PID or 3Pt Range 100 0 100 0...

Страница 14: ...rument returns at P cAL parameter 5 During the potentiometer calibration the instrument detects the real valve stroke time and stores it in the Str t Stroke time parameter At the end of the automatic...

Страница 15: ...e master zone and it uses a set point equal to 210 C The second zone has a local set point equal to 45 C The third zone has a local set point equal to 45 C The fourth zone has a local set point equal...

Страница 16: ...of the instrument control alarms etc 81 dSPu Status of the instrument at power up Available Always Range AS Pr Starts in the same way it was prior to the power down Auto Starts in Auto mode oP 0 Start...

Страница 17: ...of the configuration procedure is completed In order to exit from configuration parameter procedure proceed as follows Push button Push button for more than 10 s The instru ment will come back to the...

Страница 18: ...en the instrument is powered it starts immediately to work according to the memorized parameter value In other words the instrument has one status only the run time status During run time we can force...

Страница 19: ...no buttons for more than 10 seconds 8 4 Automatic Mode 8 4 1 Keyboard function when the instrument is in Auto mode Performs the action programmed by 75 uSrb button function during RUN TIME parameter...

Страница 20: ...ped from stand by to auto modes the instrument will start automatically the alarm masking the soft start functions and the auto tune if programmed 9 ERROR MESSAGES 9 1 Out of range signals The upper d...

Страница 21: ...aults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 3 Maintenance This instrument does not requires periodical recalibration and it have no con...

Страница 22: ...7 SP1 SP2 selection oFF 10 diF2 Digital Input 2 function oFF 11 di A Digital Inputs Action DI2 only if configured 0 DI1 direct action DI2 direct action 1 DI1 reverse action DI2 direct action 2 DI1 dir...

Страница 23: ...tand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in out of range condition 0 AL2 group no Param Description Dec Point Values Default 27 AL2t Alarm 2 type...

Страница 24: ...r up and after a set point change 5 Evo tune with automatic restart at every power up 6 Evo tune with automatic start the first power up only 7 Evo tune with manual start 8 Evo tune with automatic res...

Страница 25: ...n tunE Auto tune self tune enabling A single press longer than 1 se cond starts the auto tune oPLo Manual mode The first pressure puts the instrument in manual mode oPLo while a second one puts the in...

Страница 26: ...ransmitted Master nonE Retransmission not used the instrument is a slave rSP The instrument becomes a Master and retransmits the operative set point PErc The instrument become a Master and it retransm...

Страница 27: ...Ascon Tecnologic KX6 ENGINEERING MANUAL PAG 27...

Страница 28: ...Ascon Tecnologic KX6 ENGINEERING MANUAL PAG 28...

Отзывы: