Ascon Tecnologic - KX6 - ENGINEERING MANUAL - 

PAG. 13

PV

SP

time

2

1

3

Available: 

When [39] cont = PID or 3Pt.

Range: 

0... 2.00.

Note: 

Fast auto-tune calculates the Fuoc parameter while 
the oscillating one sets it equal to 0.5.

[47] tcH - Cycle time of the heating output

Available: 

When at least one output is programmed in order 
to be the heating output (H.rEG),  
[56] cont = PID.

Range: 

1.0... 130.0 seconds.

[48] rcG  - Power ratio between heating and  

cooling action (relative cooling gain)

The instrument uses the same PID parameter set for heat 
and for cool action but the efficiency of the two actions are 
usually different.
This parameter allows to define the ratio between the efficiency 
of the heating system and the efficiency of the cooling one.
An example will help us to explain you the philosophy.
Consider one loop of a plastic extruder.  The working 
temperature is equal to 250°C.
When you want to increase the temperature from 250 
to 270°C (

D

T = 20°C) using 100% of the heating power 

(resistor), you will need 60 seconds.
On the contrary, when you want to decrease the temperature 
from 250 to 230°C (

D

T = 20°C) using 100% of the cooling 

power (fan), you will need 20 seconds only.
In our example the ratio is equal to 60/20 = 3 ([67] rcG = 3) 
and it say that the efficiency of the cooling system is 3 time 
more efficient of the heating one.

Available: 

When two control action are programmed  
(H.rEG and c.rEG) and [39] cont = PID.

Range: 

 0.01... 99.99

Note: 

Auto-tune functions calculate this value.

[49] tcc - Cycle time of the cooling output

Available: 

When at least one output is programmed in order 
to be the cooling output (c.rEG), [56] cont = PID.

Range: 

1.0... 130.0 seconds.

[50] rS - Manual reset (integral pre-load)

It allows to drastically reduce the undershoot due to a 
hot restart.  When your process is steady, the instrument 
operates with a steady power output (e.g.: 30%).
If a short power down occurs, the process restarts with a 
process variable close to the set point while the instrument 
starts with an integral action equal to zero. 
Setting a manual reset equal to the average power output (in our 
example 30%) the instrument will start with a power output equal 
to the value it will use at steady state (instead of zero) and the 
undershoot will become very little (in theory equal to zero).

Available: 

When [39] cont = 

PID

 or 

3Pt

.

Range: 

-100.0... +100.0%.

[51] Str.t - Servomotor stroke time

Available: 

When [39] cont = 

3Pt

.

Range: 

5... 300 seconds;

Note: 

When a open loop 

with

 potentiometer input is selected, 

this parameter ia automatically calculated by the “auto-
matic calibration system” (see [48] P.cAL parameter).

[52] db.S - Servomotor dead band

Available: 

When [39] cont = 

3Pt

.

Range: 

0... 100%.

[53] OP.L  - Minimum power output 

Available: 

When: [39] cont = 

PID

[39] cont = 

3Pt

 and [58] Pot = 

Pot.o

[39] cont = 3Pt and [58] Pot = 

Pot.c

.

Range: 

-100... [54]OP.H%.

[54] OP.H  - Maximum power output

Available: 

When: [39] cont = 

PID

[39] cont = 

3Pt

 and [58] Pot = 

Pot.o

[39] cont = 3Pt and [58] Pot = 

Pot.c

.

Range: 

[53] OP.L ... 100%.

[55] St.P  - Maximum power output used during 

soft start

Available: 

When: [39] cont = 

PID

[39] cont = 3Pt and [58] Pot = 

Pot.c

.

Range: 

-100... +100%.

Notes: 1. 

When St.P parameter have a positive value, the 
limit will be applied to the heating output(s) only.

2. 

When St.P parameter have a negative value, the 
limit will be applied to the cooling output(s) only.

3. 

When a program with automatic start at power 
up and soft start function are programmed, the 
instrument performs the soft start and than the 
program function.

4. 

The auto-tune function will be performed after soft 
start function.

5. 

The Soft start function is available also when ON/
OFF control is used.

[56] SSt - Soft start time

Available: 

When: [39] cont = 

PID

;  

[39] cont = 

3Pt

 and [58] Pot = 

Pot.c

.

Range: 

oFF 

Function not used;

0.01... 7.59  hh.mm;
inF 

Soft start always active.

[57] SS.tH - Threshold for soft start disabling

Available: 

When: [39] cont = 

PID

[39] cont = 

3Pt

 and [58] Pot = 

Pot.c

.

Range: 

-1999... 9999 engineering units.

Notes: 1. 

When the power limiter has a positive value (the 
limit is applied to the heating action) the soft start 
function will be aborted when the measured value 
is greater or equal to SS.tH parameter.

2. 

When the power limiter has a negative value (the 
limit is applied to the cooling action) the soft start 
function will be aborted when the measured value 
is lower or equal to SS.tH parameter.

[58] Pot - Potentiometer enabling 

Available: 

When [39] cont = 

3Pt

.

Range: nonE

 

Potentiometer not used;

Pot.o

 

Potentiometer used for indication only;

Pot.c

 

Potentiometer used for feedback.

Содержание KX6

Страница 1: ...ng exposed terminals and wiring on the back Select a mounting location having the following characteristics 1 It should be easily accessible 2 There is minimum vibrations and no impact 3 There are no...

Страница 2: ...e the 2 retainers To re insert the controller in its housing reverse the extraction procedure 2 3 General notes about wiring 1 Do not run input wires together with power cables 2 External components l...

Страница 3: ...Common 24 VAC DC Notes 1 The isolated input DI2 must be used in one of the modes determined by the link High level input 110 220 VAC Low level input 24 VDC VAC 2 Logic input 2 is isolated by the meas...

Страница 4: ...ot exceed 1 5 km at 9600 baud 2 7 Power Supply Power Supply 11 12 Supply Voltage 100 240 VAC 15 10 Notes 1 Before connecting the instrument to the power line make sure that line voltage is equal to th...

Страница 5: ...e Temperature drift It is part of the global accuracy Operating temperature 0 50 C 32 122 F Storage temperature 30 70 C 22 158 F Humidity 20 85 RH not condensing Electromagnetic compatibility and safe...

Страница 6: ...on parameters is protected by a password Note The instrument will show only the parameters consistent with the specific hardware and in accordance with the value assigned to the previous parameters e...

Страница 7: ...nd the OEM parameter set has NOT been loaded 2 Using the serial link it is always possible to send to the address 13H the corretct password in order to obtain the desired action 481 for the Factory se...

Страница 8: ...es automatically in MAN mode Removed the burnout condition the instrument remains in MAN mode until Auto mode is selected by OPEr parameter a command by serial link digital imput or by the key pressur...

Страница 9: ...vailable Always Range When at least one output is programmed as con trol output nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAo Absolute band alarm with alarm indication out...

Страница 10: ...19 AL1t is different from SE br Range 1 9999 engineering units Notes 1 The hysteresis value is the difference between the Alarm threshold value and the point the Alarm automatically resets 2 When the...

Страница 11: ...ange and stand by LbA group Loop break alarm General note about LBA alarm The LBA operate as follows applying the 100 of the power output to a process the process variable after a time due to the proc...

Страница 12: ...nditions e g set point change during tune execution etc Note Fast auto tune can start only when the measured value PV is lower than SP 1 2 SP Available When 39 cont PID or 3Pt Range 4 8 where 4 Oscill...

Страница 13: ...th a power output equal to the value it will use at steady state instead of zero and the undershoot will become very little in theory equal to zero Available When 39 cont PID or 3Pt Range 100 0 100 0...

Страница 14: ...rument returns at P cAL parameter 5 During the potentiometer calibration the instrument detects the real valve stroke time and stores it in the Str t Stroke time parameter At the end of the automatic...

Страница 15: ...e master zone and it uses a set point equal to 210 C The second zone has a local set point equal to 45 C The third zone has a local set point equal to 45 C The fourth zone has a local set point equal...

Страница 16: ...of the instrument control alarms etc 81 dSPu Status of the instrument at power up Available Always Range AS Pr Starts in the same way it was prior to the power down Auto Starts in Auto mode oP 0 Start...

Страница 17: ...of the configuration procedure is completed In order to exit from configuration parameter procedure proceed as follows Push button Push button for more than 10 s The instru ment will come back to the...

Страница 18: ...en the instrument is powered it starts immediately to work according to the memorized parameter value In other words the instrument has one status only the run time status During run time we can force...

Страница 19: ...no buttons for more than 10 seconds 8 4 Automatic Mode 8 4 1 Keyboard function when the instrument is in Auto mode Performs the action programmed by 75 uSrb button function during RUN TIME parameter...

Страница 20: ...ped from stand by to auto modes the instrument will start automatically the alarm masking the soft start functions and the auto tune if programmed 9 ERROR MESSAGES 9 1 Out of range signals The upper d...

Страница 21: ...aults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 3 Maintenance This instrument does not requires periodical recalibration and it have no con...

Страница 22: ...7 SP1 SP2 selection oFF 10 diF2 Digital Input 2 function oFF 11 di A Digital Inputs Action DI2 only if configured 0 DI1 direct action DI2 direct action 1 DI1 reverse action DI2 direct action 2 DI1 dir...

Страница 23: ...tand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in out of range condition 0 AL2 group no Param Description Dec Point Values Default 27 AL2t Alarm 2 type...

Страница 24: ...r up and after a set point change 5 Evo tune with automatic restart at every power up 6 Evo tune with automatic start the first power up only 7 Evo tune with manual start 8 Evo tune with automatic res...

Страница 25: ...n tunE Auto tune self tune enabling A single press longer than 1 se cond starts the auto tune oPLo Manual mode The first pressure puts the instrument in manual mode oPLo while a second one puts the in...

Страница 26: ...ransmitted Master nonE Retransmission not used the instrument is a slave rSP The instrument becomes a Master and retransmits the operative set point PErc The instrument become a Master and it retransm...

Страница 27: ...Ascon Tecnologic KX6 ENGINEERING MANUAL PAG 27...

Страница 28: ...Ascon Tecnologic KX6 ENGINEERING MANUAL PAG 28...

Отзывы: