37
Safety Devices- Heatpump (R410a)
OPEN
kPa/psi
CLOSE
kPa/psi
OPEN
kPa/psi
CLOSE
kPa/psi
DISCHARGE THERMOSTAT SETTING
°C / °F
A5RT90BR
A5RT120BR
YES
MODEL
SAFETY
DEVICE
PHASE SEQUENCER
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
TYPE
TYPE
120 / 248
NC, Auto Reset
NC, Auto Reset
124 / 18
193 / 28
4137 / 600
3309 / 480
OPEN
kPa/psi
CLOSE
kPa/psi
OPEN
kPa/psi
CLOSE
kPa/psi
DISCHARGE THERMOSTAT SETTING
°C / °F
TYPE
TYPE
120 / 248
NC, Auto Reset
NC, Auto Reset
124 / 18
193 / 28
4137 / 600
3309 / 480
A5RT150BR
A5RT180BR
YES
MODEL
SAFETY
DEVICE
PHASE SEQUENCER
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
Содержание A5RT 120 BR
Страница 1: ...A5RT 2010 A5RT 90 BR A5RT 120 BR A5RT 150 BR A5RT 180 BR Models R410A Rooftop Packaged B Series...
Страница 22: ...20 Control Module Of Unit A5RT90BR Control Module Of Unit A5RT120BR...
Страница 23: ...21 Control Module Of Unit A5RT150BR Control Module Of Unit A5RT180BR...
Страница 51: ...49 Model A5RT150BR All dimensions are in mm CENTER OF GRAVITY...
Страница 52: ...50 Model A5RT180BR All dimensions are in mm CENTER OF GRAVITY...
Страница 53: ...51 Model A5RT90BR 9 WIRING DIAGRAMS...
Страница 54: ...52 Model A5RT120BR...
Страница 55: ...53 Model A5RT150BR...
Страница 56: ...54 Model A5RT180BR...