41
2
nd
Step:
Indoor WB
˚C
Indoor DB
˚C
Outdoor DB,˚C
35
TC (kW)
....
....
........................
42.10
17
25
x
5
y
5
19
16
44.55
37.60
31.63
z
5
12.85
13.03
Total capacity, TC
Sensible capacity, SHC
Interpolation Method:
⇒
19ºC – 16ºC
=
44.55kW – 42.10kW
44.55kW – x
5
kW
19ºC – 17ºC
⇒
x
5
= 42.92kW
To obtain the Total capacity, Sensible capacity and Power Input for
(a) Indoor Condition:
25°C DB,
17°C WB
Outdoor Condition:
35°C DB
SHC (kW)
PI (kW)
Interpolation Method:
⇒
19ºC – 16ºC
=
31.63kW – 37.60kW
31.63kW – y
5
kW
19ºC – 17ºC
⇒
y
5
= 35.61kW
Power Input, PI
Interpolation Method:
⇒
19ºC – 16ºC
=
13.03kW – 12.85kW
13.03kW – z
5
kW
19ºC – 17ºC
⇒
z
5
= 12.91kW