Ascon tecnologic K48 Скачать руководство пользователя страница 8

Ascon Tecnologic - K Series - ENGINEERING MANUAL - Vr. 9.0

 PAG. 8

7 = 

Timer Run [transition] a short closure al-
lows to start timer execution;

8 = 

Timer reset [transition] a short closure 
allows to reset timer count;

9 = 

Timer run/hold [Status]. 
- Contact closed = timer RUN; 
- Contact open = timer Hold,

10 = 

Program Run [transition]. 
The first closure allows to start program 
execution but a second closure restart the 
program execution from the beginning.

11 = 

Program Reset [transition].  A contact clo-
sure allows to reset program execution.

12 = 

Program Hold [transition].  The first closure 
allows to hold program execution and a 
second closure continue program execution.

13 = 

Program Run/Hold [status].  When the con-
tact is closed the program is running.

14 = 

Program Run/Reset [status]. 
- Contact closed = Program run; 
- Contact open = Program reset;

15 = 

Instrument in Manual mode (Open Loop) 
[status];

16 = 

Sequential set point selection [transition] 
(see “Note about digital inputs”);

17 = 

SP1/SP2 selection [status];

18 = 

Binary selection of the set point made by 
digital input 1 (less significant bit) and digi-

tal input 2 (most significant bit) [status];

19  = 

Digital input 1 will work in parallel to the 

 

button while digital input 2 will work in paral-
lel to the 

 button;

20 = 

Timer Run/Reset.

Notes about digital inputs:

1. 

When 

diF1

 or 

diF2

 is equal to 5 the instrument 

operates as follows:

• 

When the contact is open, the control action is an hea-
ting action and the active set point is SP1.

• 

When the contact is closed, the control action is a coo-
ling action and the active set point is SP2.  

2. 

When 

diF1

 = 18, 

diF2

 setting is forced to 18. 

diF2

 can not be associated with any other function.

3. 

When 

diF1

 = 

diF2

 = 18 the set point selection will be 

in accordance with the following table:

Dig In1

Dig. In2

Operative set point

Off

Off

Set point 1

On

Off

Set point 2

Off

On

Set point 3

On

On

Set point 4

4. 

When 

diF1

 = 19, 

diF2

 setting is forced to 19. 

diF2

 can not be associated with any other function.

5. 

When a “Sequential set point selection” is used, every 
closure of of the logic input increases the value of 

SPAT

 

(active set point) of one step. 
The selection is cyclic -> SP1 -> SP2 -> SP3 -> SP4.

]

out Group - Output parameters

[12] o1F - Out 1 function

Available: 

Always.

Range: 

nonE =  Output not used.  With this setting, Out 1 

status can be driven directly from serial link;

H.rEG = Heating output;
c.rEG =  Cooling output;
AL = 

Alarm output;

t.out =  Timer output;
t.HoF =  Timer out - OFF in Hold;
P.End =  Program end indicator;
P.HLd =  Program hold indicator;
P. uit =  Program wait indicator;
P.run =  Program run indicator;
P.Et1 =  Program Event 1;
P.Et2 =  Program Event 2.
or.bo =  Out-of-range or burn out indicator;
P.FAL =  Power failure indicator;
bo.PF =  Out-of-range, burn out and Power Failure 

indicator;

diF1 =  The output repeates the digital input 1 status;
diF2 =  The output repeates the digital input 2 status;
St.By =  Stand By status indicator;
on = 

Out 1 forced to ON.

Notes: 1. 

When two or more outputs are programmed in the 
same way, these outputs will be driven in parallel.

2. 

The power failure indicator will be reset when the 
instrument detects an alarm reset command by 

 button, digital input or serial link.

3. 

When no control output is programmed, all the 
relative alarm (when present) will be forced to 

nonE

 (not used).

[13] o1.AL - Alarms linked up with Out 1

Available: 

When [12] o1F = AL.

Range: 

0... 31 with the following rule:
+1 = 

Alarm 1;

+2 = 

Alarm 2;

+4 = 

Alarm 3;

+8 = 

Loop break alarm;

+16 =  Sensor break (burn out).

Example 1:

 Setting 3 (2 + 1) the output will be driven by the 

alarm 1 and 2 (OR condition). 

Example 2:

 Setting 13 (8 + 4 + 1) the output will be driven by 

alarm 1 + alarm 3 + loop break alarm.

[14] o1Ac - Out 1 action

Available: 

When [12] o1F is different from 

nonE

.

Range: 

dir = 

Direct action;

rEU =  Reverse action;
dir.r = 

Direct action with reversed LED indication;

rEU.r =  Reverse action with reversed LED indication.

Notes: 1. 

Direct action:

 The output repeats the status of 

the driven element.

Example:

 The output is an alarm output with direct 

action.  When the alarm is ON, the relay will be 
energized (logic output 1).

2. 

Reverse action:

 The output status is the opposite 

of the status of the driven element.

Example:

 The output is an alarm output with 

reverse action.  When the alarm is 

OFF

, the relay 

will be energized (logic output 1).  This setting is 
usually named “fail-safe” and it is generally used 
in dangerous process in order to generate an 
alarm when the instrument power supply goes 
OFF or the internal watchdog starts.

Содержание K48

Страница 1: ...n 5 The ambient temperature is in accordance with the operative temperature 0 50 C 6 The relative humidity is in accordance with the instrument specifications 20 85 The instrument can be mounted on pa...

Страница 2: ...ut circuit Current injection 25 A Line resistance Not compensated 2 2 5 V and mV Input mV V _ _ 2 1 Input impedance 1 M Accuracy 0 5 of Span or 1 dgt 25 C 2 2 6 mA Input 0 4 20 mA input wiring for pas...

Страница 3: ...te This output is not isolated A double or reinforced isolation between instrument output and power supply must be assured by the external solid state relay 2 3 3 Output 3 OP3 Relay Output 6 5 NO C Co...

Страница 4: ...splay updating time 500 ms Sampling time 130 ms Resolution 30000 counts Total accuracy 0 5 F S V 1 digit 25 C of room temperature Electromagnetic compatibility and safety requirements Compliance Direc...

Страница 5: ...rol output is equal to 0 and can be manually modified by and buttons Stand by mode St bY The display alternately shows the measured value and the message St bY or od The instrument does not perform an...

Страница 6: ...complete list of the default parameter is available in Appendix A 5 7 All parameters configuration In the following pages we will describe all the parameters of the instrument However the instrument...

Страница 7: ...instrument will use the Zero value 2 When ON OFF control is programmed and an out of range is detected the instrument will perform the safety output value using a fixed cycle time equal to 20 seconds...

Страница 8: ...tion is cyclic SP1 SP2 SP3 SP4 out Group Output parameters 12 o1F Out 1 function Available Always Range nonE Output not used With this setting Out 1 status can be driven directly from serial link H rE...

Страница 9: ...Power failure indicator bo PF Out of range burn out and Power Failure indicator diF1 The output repeates the digital input 1 status diF2 The output repeates the digital input 2 status St By Stand By s...

Страница 10: ...n other words when the initial alarm condition disappears PWR ON AL1 PV time off off Ab1 1 Ab1 0 off off ON ON ON 2 A Latched alarm manual reset is an alarm that remains active even if the conditions...

Страница 11: ...s programmed as control output nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAb Absolute band alarm SE br Sensor break Note The relative alarm are relative to the current set...

Страница 12: ...for a time longer than 46 AL3d time but the reset is immediate 47 AL3o Alarm 3 enabling during Stand by mode and out of range indications Available When 40 AL3t ia different from nonE Range 0 Never 1...

Страница 13: ...if the set point is close to the ambient temperature 2 The fast type auto tune is suitable when The process is very slow and you want to be operative in a short time When an high overshoot is not acc...

Страница 14: ...oling gain The instrument uses the same PID parameter set for heat and for cool action but the efficiency of the two actions are usually different This parameter allows to define the ratio between the...

Страница 15: ...imit is applied to the cooling action the soft start function will be aborted when the measured value is lower than or equal to SS tH parameter SP Group Set point parameters The SP group will be avail...

Страница 16: ...lers The Slave zones use it as a set point trim The first zone is the master zone and it uses a set point equal to 210 C The second zone has a local set point equal to 45 C The third zone has a local...

Страница 17: ...tatus of two events An event can drive an output and make an action during one or more specific program steps Some additional parameters allow to define the time scale the automatic RUN conditions and...

Страница 18: ...t 2 00 00 off off off off 10 00 on off off off 01 00 off on off off 11 00 on on off off Display Ramp Soak Event 1 Event 2 Event 1 Event 2 00 10 off off on off 10 10 on off on off 01 10 off on on off 1...

Страница 19: ...1 parameter 113 Pr St Program status Available When 89 Pr F is different from nonE Range run Program Run HoLd Program Hold rES Program reset Note This parameter allows to manage program execution by a...

Страница 20: ...is equal to in finite the limit is always active and it can be used also when ON OFF control is selected 118 AdE Bargraph deviation Available Always Range oFF Bargraph not used 1 9999In engineering u...

Страница 21: ...shold not used 1 999 days 1 999 hours CAL Group User calibration group This function allows to calibrate the complete measuring chain and to compensate the errors due to Sensor location Sensor class s...

Страница 22: ...L1 AL2 A 6 AL2 Pb A 7 Pb Int A 8 Int dEr A 9 dEr Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The display alternately shows PASS and 0 3 By and buttons set a pas...

Страница 23: ...and the parameter modification procedure is closed When you desire to remove the time out e g for the first configuration of an instrument you can use a password equal to 1000 plus the programmed pas...

Страница 24: ...preceded by a P letter P84 3 4 Push button again When the wattmeter function is running the display shows U followed by the measured energy Note The energy calculation will be in accordance with the 1...

Страница 25: ...set manual modes during self tune execution the self tune function will be aborted 4 During manual mode all functions not related with the control wattmeter indipendent timer worked time etc continue...

Страница 26: ...ment to our company The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of altern...

Страница 27: ...and Under our C 0 9 oPE Safety output value 0 100 100 0 C 0 10 diF1 Digital input 1 function 0 oFF No function 1 Alarm Reset 2 Alarm acknowledge ACK 3 Hold of the measured value 4 Stand by mode 5 HEAt...

Страница 28: ...k alarm 16 Sensor break burn out AL1 A 17 14 o1Ac Out 1 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 15 o2F Out 2 function 0 Non...

Страница 29: ...r break burn out AL2 A 23 20 o3Ac Out 3 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 21 o4F Out 4 function 0 NonE Output not use...

Страница 30: ...and by mode 0 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by no C 0 AL2 Group Alarm 2 Parameters no Para meter Description Dec Range Default Vis...

Страница 31: ...0 LbA Group Loop Break Alarm Parameters no Para meter Description Dec Range Default Vis Promo 48 LbAt LBA time 0 From 0 oFF to 9999 s oFF C 0 49 LbSt Delta measure used by LBA during Soft start dP Fro...

Страница 32: ...om 0 00 oFF to 8 00 inF hh mm oFF C 0 71 SStH Threshold for soft start disabling dP 1999 9999 E U 9999 C 0 SP Group Set Point Parameters no Para meter Description Dec Range Default Vis Promo 72 nSP Nu...

Страница 33: ...e end program indication 2 From 0 00 oFF to 100 00 inF minutes and seconds oFF A 72 93 Pr S1 Set point of the first soak dP From SPLL to SPHL 0 A 73 94 Pr G1 Gradient of the first ramp 1 0 1 1000 0 in...

Страница 34: ...r time down PErc Percent of the power output used during soft start when the soft start time is equal to in finite the limit is always active can be used also when ON OFF control is selected nonE A 95...

Страница 35: ...urs with threshold nonE A 97 127 UoLt Nominal voltage of the load 0 1 999 Volt 230 A 98 128 cur Nominal current of the load 0 1 999 A 10 A 99 129 h Job Threshold of the worked hours days 0 From 0 oFF...

Страница 36: ...Ascon Tecnologic K Series ENGINEERING MANUAL Vr 9 0 PAG 36...

Отзывы: