2.3 Outputs
Safety notes:
•
To avoid electrical shocks, connect power line at last.
•
For supply connections use No. 16 AWG or larger wires
rated for at last 75°C.
•
Use copper conductors only.
•
SSR outputs are
not
isolated. A reinforced isolation must
be assured by the external solid state relays.
2.3.1 Output 1 (OuT1)
Relay Output
12
11
NO
C
Contact rating:
• 8 A/250 V cos
j
=1;
• 3 A/250 V cos
j
=0.4.
Operation:
1 x 10
5
.
SSR Output
SSR
12
11
-
+
Logic level 0:
Vout < 0.5 VDC;
Logic level 1:
• 12 V ±20% @ 1 mA;
• 10 V ±20% @ 20 mA.
Note:
This output is
not
isolated. A double or reinforced
isolation between instrument output and power supply
must be assured by the external solid state relay.
2.3.2 Output 2 (OuT2)
Relay Output
10
9
NO
C
Contact rating:
• 8 A /250 V cos
j
=1;
• 4 A /250 V cos
j
=0.4.
Operation:
1 x 10
5
.
SSR Output
SSR
10
9
-
+
Logic level 0:
Vout < 0.5 VDC;
Logic level 1:
• 12 V ±20% @ 1 mA;
• 10 V ±20% @ 20 mA.
Note:
This output is
not
isolated. A double or reinforced
isolation between instrument output and power supply
must be assured by the external solid state relay.
2.3.3 Output 3 (OP3)
Relay Output
6
5
NO
C
Contact rating:
• 5 A /250 V cos
j
= 1;
• 2 A /250 V cos
j
= 0.4.
Operation:
1 x 10
5
.
SSR Output
SSR
6
5
-
+
Logic level 0:
Vout < 0.5 VDC;
Logic level 1:
• 12 V ±20%, 15 mA max.;
• 10 V ±20% @ 20 mA.
Note:
This output is
not
isolated. A double or reinforced
isolation between instrument output and power supply
must be assured by the external solid state relay.
2.4 Power Supply
Power Supply
7
8
Supply Voltage:
• 24 VAC/DC (±10%);
• 100... 240 VAC (±10%).
Current consumption:
5 W max.
Notes: 1.
Before connecting the instrument to the power
line, make sure that line voltage is equal to the
voltage shown on the identification label;
2.
To avoid electrical shock, connect power line at
the end of the wiring procedure;
3.
For supply connections use No. 16 AWG or larger
wires rated for at last 75°C.
4.
Use copper conductors only.
5.
The polarity of the power supply has no importance;
6.
The power supply input is NOT fuse protected.
Please, provide a T type 1A, 250 V fuse externally.