LBA application example: 

 

LbAt (LBA time) = 120 seconds (2 minutes);

 

LbAS (delta LBA) = 5°C.

The machine has been designed in order to reach 200°C 
in 20 minutes (20°C/min).
When the PID demands the 100% of the power, the 
instrument starts the time count.
During time count if the measured value increases 
more than 5°C, the instrument restarts the time count.  
Otherwise if the measured value does not reach the 
programmed delta (5°C in 2 minutes) the instrument will 
generate the alarm.

]

rEG Group - Control parameters

The rEG group will be available only when at least one 
output is programmed as control output (H.rEG or C.rEG).

[52] cont - Control type

Available: 

When at least one output is programmed as con-
trol output (H.rEG or C.rEG).

Range:  • 

When two control actions (heat 

and

 cool) are 

programmed:

Pid = 

PID (heat 

and

 cool);

nr = 

Heat/Cool ON/OFF control with neutral zone

HSEt
HSEt

SP

PV

time

OUTH.rEG

(heating)
OUTc.rEG

(cooling)

off

ON

ON

off

off

ON

• 

When one control action (heat 

or

 cool) is pro-

grammed:

Pid = 

PID (heat 

or

 cool)

On.FA = ON/OFF asymmetric hysteresis
On.FS = ON/OFF symmetric hysteresis

HEAt - On.FS

OUT
H.rEG

SP

PV

HSEt

HSEt

time

HEAt - On.FA

OUT
H.rEG

SP

PV

HSEt

time

off

off

C ooL - O n.FS

OUT
H.rEG

SP

PV

HSEt

HSEt

time

C ooL - O n.FA

OUT
C.rEG

SP

PV

HSEt

time

ON

ON

ON

ON

ON

ON

off

off

off

off

off

off

ON

ON

ON

ON

ON

ON

Notes: 1. 

ON/OFF control with asymmetric hysteresis: 
- OFF when PV 

☺²

 SP; 

- ON when PV 

±

 (SP - hysteresis).

2. 

ON/OFF control with symmetric hysteresis: 
- OFF when PV 

²

 (SP +  hysteresis); 

- ON when PV 

±

 (SP -  hysteresis).

[53] Auto - Auto tune selection

Ascon Tecnologic has developed two auto-tune algorithms:

1. 

The 

oscillating auto-tune

 is the usual auto-tune and:

• 

It is more accurate;

• 

Can start even if PV is close to the set point;

• 

Can be used even if the set point is close to the ambient 
temperature.

2. 

The 

fast type auto-tune

 is suitable when:

• 

 The process is very slow and you want to be operative 
in a short time;

• 

When an high overshoot is not acceptable;

• 

In multi loop machinery where the fast method reduces 
the calculation error due to the effect of the other loops.

Note: 

Fast auto-tune can start only when the measured 
value (PV) is lower than (SP + 1/2SP).

Available: 

When [49] cont  = PID

Range: 

From -4 to 4 where:
-4 = 

Oscillating auto-tune with automatic restart 
at Power ON (after soft start) and after 

all

 

set point change;

-3 = 

Oscillating auto-tune with manual start;

-2 = 

Oscillating auto-tune with automatic start at 
the first Power ON only;

-1 = 

Oscillating auto-tune with automatic restart 
at every Power ON;

0 = 

Not used;

1 = 

Fast auto tuning with automatic restart at 
every Power ON;

2 = 

FAST auto-tune with automatic start at the 
first Power ON only;

3 = 

FAST auto-tune with manual start;

4 = 

FAST auto-tune with automatic restart at 
Power ON (after soft start) and after a set 
point change.

Note: 

The auto-tune is inhibited during program execution.

[54] Aut.r - Manual start of the auto-tune

Available: 

When [52] cont = PID.

Range: 

oFF = The instrument is not performing the auto-tune;
on = The instrument is performing the auto-tune.

[55] SELF - Self-tune enable

The self-tuning is an adaptive algorithm able to optimize 
continuously the PID parameter value.
This algorithm is specifically designed for all process 
subjected to big load variation able to change heavily the 
process response.

Available: 

When [52] cont = PID.

Range: 

YES =  Self-tune active;
on = 

Self-tune not active.

[56] HSEt - Hysteresis of the ON/OFF control

Available: 

When [52] cont is different from PID.

Range: 

0... 9999 in engineering units.

[57] cPdt - Time for compressor protection

Available: 

When [52] cont = nr.

Range: 

OFF = Protection disabled;
1... 9999 seconds.

[58] Pb - Proportional band

Available: 

When [52] cont = PID and [55] SELF = no.

Range: 

1... 9999 engineering units.

Note: 

Auto-tune functions calculate this value.

Содержание K48

Страница 1: ...n 5 The ambient temperature is in accordance with the operative temperature 0 50 C 6 The relative humidity is in accordance with the instrument specifications 20 85 The instrument can be mounted on pa...

Страница 2: ...ut circuit Current injection 25 A Line resistance Not compensated 2 2 5 V and mV Input mV V _ _ 2 1 Input impedance 1 M Accuracy 0 5 of Span or 1 dgt 25 C 2 2 6 mA Input 0 4 20 mA input wiring for pas...

Страница 3: ...te This output is not isolated A double or reinforced isolation between instrument output and power supply must be assured by the external solid state relay 2 3 3 Output 3 OP3 Relay Output 6 5 NO C Co...

Страница 4: ...splay updating time 500 ms Sampling time 130 ms Resolution 30000 counts Total accuracy 0 5 F S V 1 digit 25 C of room temperature Electromagnetic compatibility and safety requirements Compliance Direc...

Страница 5: ...rol output is equal to 0 and can be manually modified by and buttons Stand by mode St bY The display alternately shows the measured value and the message St bY or od The instrument does not perform an...

Страница 6: ...complete list of the default parameter is available in Appendix A 5 7 All parameters configuration In the following pages we will describe all the parameters of the instrument However the instrument...

Страница 7: ...instrument will use the Zero value 2 When ON OFF control is programmed and an out of range is detected the instrument will perform the safety output value using a fixed cycle time equal to 20 seconds...

Страница 8: ...tion is cyclic SP1 SP2 SP3 SP4 out Group Output parameters 12 o1F Out 1 function Available Always Range nonE Output not used With this setting Out 1 status can be driven directly from serial link H rE...

Страница 9: ...Power failure indicator bo PF Out of range burn out and Power Failure indicator diF1 The output repeates the digital input 1 status diF2 The output repeates the digital input 2 status St By Stand By s...

Страница 10: ...n other words when the initial alarm condition disappears PWR ON AL1 PV time off off Ab1 1 Ab1 0 off off ON ON ON 2 A Latched alarm manual reset is an alarm that remains active even if the conditions...

Страница 11: ...s programmed as control output nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAb Absolute band alarm SE br Sensor break Note The relative alarm are relative to the current set...

Страница 12: ...for a time longer than 46 AL3d time but the reset is immediate 47 AL3o Alarm 3 enabling during Stand by mode and out of range indications Available When 40 AL3t ia different from nonE Range 0 Never 1...

Страница 13: ...if the set point is close to the ambient temperature 2 The fast type auto tune is suitable when The process is very slow and you want to be operative in a short time When an high overshoot is not acc...

Страница 14: ...oling gain The instrument uses the same PID parameter set for heat and for cool action but the efficiency of the two actions are usually different This parameter allows to define the ratio between the...

Страница 15: ...imit is applied to the cooling action the soft start function will be aborted when the measured value is lower than or equal to SS tH parameter SP Group Set point parameters The SP group will be avail...

Страница 16: ...lers The Slave zones use it as a set point trim The first zone is the master zone and it uses a set point equal to 210 C The second zone has a local set point equal to 45 C The third zone has a local...

Страница 17: ...tatus of two events An event can drive an output and make an action during one or more specific program steps Some additional parameters allow to define the time scale the automatic RUN conditions and...

Страница 18: ...t 2 00 00 off off off off 10 00 on off off off 01 00 off on off off 11 00 on on off off Display Ramp Soak Event 1 Event 2 Event 1 Event 2 00 10 off off on off 10 10 on off on off 01 10 off on on off 1...

Страница 19: ...1 parameter 113 Pr St Program status Available When 89 Pr F is different from nonE Range run Program Run HoLd Program Hold rES Program reset Note This parameter allows to manage program execution by a...

Страница 20: ...is equal to in finite the limit is always active and it can be used also when ON OFF control is selected 118 AdE Bargraph deviation Available Always Range oFF Bargraph not used 1 9999In engineering u...

Страница 21: ...shold not used 1 999 days 1 999 hours CAL Group User calibration group This function allows to calibrate the complete measuring chain and to compensate the errors due to Sensor location Sensor class s...

Страница 22: ...L1 AL2 A 6 AL2 Pb A 7 Pb Int A 8 Int dEr A 9 dEr Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The display alternately shows PASS and 0 3 By and buttons set a pas...

Страница 23: ...and the parameter modification procedure is closed When you desire to remove the time out e g for the first configuration of an instrument you can use a password equal to 1000 plus the programmed pas...

Страница 24: ...preceded by a P letter P84 3 4 Push button again When the wattmeter function is running the display shows U followed by the measured energy Note The energy calculation will be in accordance with the 1...

Страница 25: ...set manual modes during self tune execution the self tune function will be aborted 4 During manual mode all functions not related with the control wattmeter indipendent timer worked time etc continue...

Страница 26: ...ment to our company The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of altern...

Страница 27: ...and Under our C 0 9 oPE Safety output value 0 100 100 0 C 0 10 diF1 Digital input 1 function 0 oFF No function 1 Alarm Reset 2 Alarm acknowledge ACK 3 Hold of the measured value 4 Stand by mode 5 HEAt...

Страница 28: ...k alarm 16 Sensor break burn out AL1 A 17 14 o1Ac Out 1 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 15 o2F Out 2 function 0 Non...

Страница 29: ...r break burn out AL2 A 23 20 o3Ac Out 3 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 21 o4F Out 4 function 0 NonE Output not use...

Страница 30: ...and by mode 0 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by no C 0 AL2 Group Alarm 2 Parameters no Para meter Description Dec Range Default Vis...

Страница 31: ...0 LbA Group Loop Break Alarm Parameters no Para meter Description Dec Range Default Vis Promo 48 LbAt LBA time 0 From 0 oFF to 9999 s oFF C 0 49 LbSt Delta measure used by LBA during Soft start dP Fro...

Страница 32: ...om 0 00 oFF to 8 00 inF hh mm oFF C 0 71 SStH Threshold for soft start disabling dP 1999 9999 E U 9999 C 0 SP Group Set Point Parameters no Para meter Description Dec Range Default Vis Promo 72 nSP Nu...

Страница 33: ...e end program indication 2 From 0 00 oFF to 100 00 inF minutes and seconds oFF A 72 93 Pr S1 Set point of the first soak dP From SPLL to SPHL 0 A 73 94 Pr G1 Gradient of the first ramp 1 0 1 1000 0 in...

Страница 34: ...r time down PErc Percent of the power output used during soft start when the soft start time is equal to in finite the limit is always active can be used also when ON OFF control is selected nonE A 95...

Страница 35: ...urs with threshold nonE A 97 127 UoLt Nominal voltage of the load 0 1 999 Volt 230 A 98 128 cur Nominal current of the load 0 1 999 A 10 A 99 129 h Job Threshold of the worked hours days 0 From 0 oFF...

Страница 36: ...Ascon Tecnologic K Series ENGINEERING MANUAL Vr 9 0 PAG 36...

Отзывы: