Ascon Tecnologic - K Series - ENGINEERING MANUAL -Vr. 9.0 PAG. 32
no.
Para-
meter
Description
Dec.
Range
Default
Vis.
Promo.
56
HSEt
Hysteresis of the ON/OFF control
dP
0... 9999 ( E.U.)
1
A-27
57
cPdt
Time for compressor protection
0
From 0 (oFF) to 9999 (s)
oFF
C-0
58
Pb
Proportional band
dP
0... 9999 (E.U.)
50
A-28
59
int
Integral time
0
From 0 (oFF) to 9999 (s)
200
A-29
60
dEr
Derivative time
0
From 0 (oFF) to 9999 (s)
50
A-30
61
Fuoc
Fuzzy overshoot control
2
0.00... 2.00
0.50
A-31
62
H.Act
Heating output actuator
0
SSr =
SSR
rELY = Relay
SLou = Slow actuators
SSr
A-32
63
tcrH
Heating output cycle time
1
0.1... 130.0 (s)
20.0
C-0
64
PrAt
Power ratio between heating and cool-
ing action
2
0.01... 99.99
1.00
A-34
65
c.Act
Cooling output actuator
0
SSr =
SSR
rELY = Relay
SLou = Slow actuators
SSr
A-35
66
tcrc
Cooling output cycle time
1
0.1... 130.0 (s)
20.0
C-0
67
rS
Manual reset (Integral pre-load)
1
-100.0... 100.0 (%)
0.0
C-0
68
od
Delay at power ON
2
From 0.00 (oFF) to 99.59 (hh.mm)
oFF
C-0
69
St.P
Maximum power output used during
soft start
0
-100... +100 (%)
0
C-0
70
SSt
Soft start time
2
From 0.00 (oFF) to 8.00 (inF) (hh.mm)
oFF
C-0
71
SStH
Threshold for soft start disabling
dP
-1999... +9999 (E.U.)
9999
C-0
]
SP Group (Set Point Parameters)
no.
Para-
meter
Description
Dec.
Range
Default
Vis.
Promo.
72
nSP
Number of used set points
0
1... 4
1
A-38
73
SPLL Minimum set point value
dP
From -1999 to SPHL
-1999
A-39
74
SPHL Maximum set point value
dP
From SPLL to 9999
9999
A-40
75
SP 1
Set point 1
dP
From SPLL to SPLH
0
O-41
76
SP 2
Set point 2
dP
From SPLL to SPLH
0
O-42
77
SP 3
Set point 3
dP
From SPLL to SPLH
0
O-43
78
SP 4
Set point 4
dP
From SPLL to SPLH
0
O-44
79
SPAt
Selection of the active set point.
0
From 1 (SP 1) to nSP
1
O-45
80
SP.rt
Remote set point type
0
RSP = The value coming from serial link is used as
remote set point
trin =
The value will be added to the local set point
selected by SPAt and the sum becomes the
operative set point
PErc = The value will be scaled on the input range
and this value will be used as remote set point
trin
C-0
81
SP.Lr Local/remote set point selection
0
Loc =
local
rEn =
remote
Loc
C-0
82
SP.u
Rate of rise for POSITIVE set point change
2
0.01... 100.00 (inF) Engineering units per minute
inF
C-0
83
SP.d
Rate of rise for NEGATIVE set point change 2
0.01... 100.00 (inF) Engineering units per minute
inF
C-0