Ascon Tecnologic - K Series - ENGINEERING MANUAL -Vr. 9.0 PAG. 31
]
AL3 Group (Alarm 3 Parameters)
no.
Para-
meter
Description
Dec.
Range
Default
Vis.
Promo.
40
AL3t
Alarm 3 type
0
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAb = Absolute band alarm
SE.br = Sensor break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdE = Relative band alarm
nonE
C-0
41
Ab3
Alarm 3 function
0
0... 15:
+1 =
Not active at power ON
+2 =
Latched alarm (manual reset)
+4 =
Acknowledgeable alarm
+8 =
Relative alarm not active at set point change
0
C-0
42
AL3L
- For High and low alarms, it is the low
limit of the AL3 threshold
- For band alarm, it is low alarm th-
reshold
dP
From -1999 to AL3H ( E.U.)
-1999
C-0
43
AL3H
- For High and low alarms, it is the
high limit of the AL3 threshold
- For band alarm, it is high alarm
threshold
dP
From AL3L to 9999 (E.U.)
9999
C-0
44
AL3
Alarm 3 threshold
dP
From AL3L to AL3H (E.U.)
0
C-0
45
HAL3
Alarm 3 hysteresis
dP
1... 9999 (E.U.)
1
C-0
46
AL3d
Alerm 3 delay
dP
From 0 (oFF) to 9999 (s)
oFF
C-0
47
AL3o
Alarm 3 enabling during Stand-by
mode
0
0 =
Never
1 =
During stand by
2 =
During overrange and underrange
3 =
During overrange, underrange and stand-by
no
C-0
]
LbA Group (Loop Break Alarm Parameters)
no.
Para-
meter
Description
Dec.
Range
Default
Vis.
Promo.
48
LbAt
LBA time
0
From 0 (oFF) to 9999 (s)
oFF
C-0
49
LbSt
Delta measure used by LBA during Soft
start
dP
From 0 (oFF) to 9999 (E.U.)
10
C-0
50
LbAS
Delta measure used by LBA
dP
1... 9999 ( E.U.)
20
C-0
51
LbcA
Condition for LBA enabling
0
uP =
Active when Pout = 100%
dn =
Active when Pout = -100%
both = Active in both cases
both
C-0
]
rEG Group (Control parameters)
no.
Para-
meter
Description
Dec.
Range
Default
Vis.
Promo.
52
cont
Control type
0
Pid =
PID (heat and/or cool)
On.FA = ON/OFF asymmetric hysteresis
On.FS = ON/OFF symmetric hysteresis
nr =
Heat/Cool ON/OFF control with neutral zone
Pid
A-25
53
Auto
Autotuning selection
0
-4 = Oscillating auto-tune with automatic restart at
power ON and after all set point change
-3 = Oscillating auto-tune with manual start
-2 = Oscillating auto-tune with auto-matic start at the
first power ON only
-1 = Oscillating auto-tune with auto-matic restart at
every power ON
0 = Not used
1 = Fast auto tuning with automatic restart at every
power ON
2 = Fast auto-tune with automatic start at the first
power ON only
3 = FAST auto-tune with manual start
4 = FAST auto-tune with automatic restart at power
ON and after a set point change
2
C-0
54
Aut.r
Manual start of the Autotuning
0
oFF = Not active
on =
Active
oFF
A-26
55
SELF
Self tuning enabling
0
YES = Active
no =
Not active
no
C-0