5.  CONFIGuRATION PROCEDuRE

5.1  Introduction

When the instrument is powered, it starts immediately to work 
according to the parameters values loaded in its memory.
The instrument behaviour and its performances are 
governed by the value of the stored parameters.
At the first start up the instrument uses a “default” parameters 
set (factory parameter set); this set is a generic one (e.g. a 
TC J input is programmed).
We recommend to modify the parameter set to suit your 
application (e.g. set the right input type, Control strategy, 
define an alarm, etc.).
To change these parameters you will need to enter the 
“Configuration procedure”.

WARNING! 

[6] Unit

 (Engineering Unit) parameter allows to 

set the temperature units in accordance with 
the user needs (°C/°F).   

Be careful!

 Do not change the Engineering Unit 

during process control as the temperature values 
inserted by the user (thresholds, limits etc.) are 
not automatically rescaled by the instrument.

5.1.1  Access levels to the parameter 

modifications and their password

The instrument have one complete parameter set.  We call 
this set “Configuration parameter set” (or “Configuration 
parameters”).
The access to the configuration parameters is protected by a 
programmable password (password level 3).
The configuration parameters are collected in various 
groups.  Every group defines all parameters related with a 
specific function (e.g. control, alarms, output functions).

Note: 

The instrument will show only the parameters consistent 
with the specific hardware and in accordance with the 
value assigned to the previous parameters (e.g. if you 
set an output as “not used” the instrument will mask all 
other parameters related with this output).

5.2  Instrument behaviour at Power ON

At Power ON the instrument can start in one of the following 
mode depending on its configuration:

Auto mode

 without program functions:

 

The display shows the measured value;

 

The decimal figure of the less significant digit is OFF;

 

The instrument is performing the standard closed loop control.

Manual mode (oPLo)

:

 

The display alternately shows: the measured value and the 
message 

oPLo

;

 

The instrument does not perform Automatic control;

 

The control output is equal to 0% and can be manually 
modified by 

 and 

 buttons.

Stand by mode (St.bY)

:

 

The display alternately shows the measured value and the 
message 

St.bY

 or 

od

;

 

The instrument does not perform any control (the control 
outputs are OFF);

 

The instrument is working as an indicator.

Auto mode with automatic program start up

:

 

The display shows one of the following information:

• 

The measured value;

• 

The operative set point (when it is performing a ramp);

• 

The time of the segment in progress (when it is perfor-
ming a soak);

• 

The measured value alternate with the message 

St.bY

.

• 

In all cases, the decimal figure of the less significant 
digit of the display is lit.

We define all the above described conditions as “

Standard 

display

”.

5.3  Entering the configuration mode

1. 

Push the 

 button for more than 3 seconds.

The display alternately shows 

PASS

 and 

0

.

2. 

Using 

 and 

 buttons set the programmed password.

Notes: 1. 

The factory default password for configuration 
parameters is equal to 30.

2. 

All parameter modification are protected by a time 
out. If no button is pressed for more than 10 second 
the instrument returns automatically back to the 
Standard display, the new value of the last selected 
parameter is lost and the parameter modification 
procedure is closed.  Sometimes can be useful to 
enter the parameter configuration procedure with 
no timeout (e.g.: the first time an instrument is 
configured).  In this case, use a password equal to 
the previously set pa 1000 digits  
(e.g.: 1000 + 30 [default] = 1030). 
It is always possible to manually end the parameter 
configuration procedure (see the next paragraph).

3. 

During parameter modification the instrument 
continues to  control the process.  In certain 
conditions, when a configuration change can 
produce a heavy bump to the process, it is 
advisable to temporarily stop the control during the 
programming operations (the control output will be 
Off).  In this case, use a password equal to 2000 + 
the programmed value (e.g. 2000 + 30 = 2030). 
The control will restart automatically when the 
configuration procedure will be manually closed.

3. 

Push the 

 button. 

If the password is correct the display shows the acronym 
of the first parameter group preceded by the symbol “

]

”.

In other words the upper display shows: 

]

inP

.

The instrument is in configuration mode.

5.4  Exiting the configuration mode

Push the 

 button for more than 5 seconds, the instrument 

will return to the “Standard display”.

Содержание K48

Страница 1: ...n 5 The ambient temperature is in accordance with the operative temperature 0 50 C 6 The relative humidity is in accordance with the instrument specifications 20 85 The instrument can be mounted on pa...

Страница 2: ...ut circuit Current injection 25 A Line resistance Not compensated 2 2 5 V and mV Input mV V _ _ 2 1 Input impedance 1 M Accuracy 0 5 of Span or 1 dgt 25 C 2 2 6 mA Input 0 4 20 mA input wiring for pas...

Страница 3: ...te This output is not isolated A double or reinforced isolation between instrument output and power supply must be assured by the external solid state relay 2 3 3 Output 3 OP3 Relay Output 6 5 NO C Co...

Страница 4: ...splay updating time 500 ms Sampling time 130 ms Resolution 30000 counts Total accuracy 0 5 F S V 1 digit 25 C of room temperature Electromagnetic compatibility and safety requirements Compliance Direc...

Страница 5: ...rol output is equal to 0 and can be manually modified by and buttons Stand by mode St bY The display alternately shows the measured value and the message St bY or od The instrument does not perform an...

Страница 6: ...complete list of the default parameter is available in Appendix A 5 7 All parameters configuration In the following pages we will describe all the parameters of the instrument However the instrument...

Страница 7: ...instrument will use the Zero value 2 When ON OFF control is programmed and an out of range is detected the instrument will perform the safety output value using a fixed cycle time equal to 20 seconds...

Страница 8: ...tion is cyclic SP1 SP2 SP3 SP4 out Group Output parameters 12 o1F Out 1 function Available Always Range nonE Output not used With this setting Out 1 status can be driven directly from serial link H rE...

Страница 9: ...Power failure indicator bo PF Out of range burn out and Power Failure indicator diF1 The output repeates the digital input 1 status diF2 The output repeates the digital input 2 status St By Stand By s...

Страница 10: ...n other words when the initial alarm condition disappears PWR ON AL1 PV time off off Ab1 1 Ab1 0 off off ON ON ON 2 A Latched alarm manual reset is an alarm that remains active even if the conditions...

Страница 11: ...s programmed as control output nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAb Absolute band alarm SE br Sensor break Note The relative alarm are relative to the current set...

Страница 12: ...for a time longer than 46 AL3d time but the reset is immediate 47 AL3o Alarm 3 enabling during Stand by mode and out of range indications Available When 40 AL3t ia different from nonE Range 0 Never 1...

Страница 13: ...if the set point is close to the ambient temperature 2 The fast type auto tune is suitable when The process is very slow and you want to be operative in a short time When an high overshoot is not acc...

Страница 14: ...oling gain The instrument uses the same PID parameter set for heat and for cool action but the efficiency of the two actions are usually different This parameter allows to define the ratio between the...

Страница 15: ...imit is applied to the cooling action the soft start function will be aborted when the measured value is lower than or equal to SS tH parameter SP Group Set point parameters The SP group will be avail...

Страница 16: ...lers The Slave zones use it as a set point trim The first zone is the master zone and it uses a set point equal to 210 C The second zone has a local set point equal to 45 C The third zone has a local...

Страница 17: ...tatus of two events An event can drive an output and make an action during one or more specific program steps Some additional parameters allow to define the time scale the automatic RUN conditions and...

Страница 18: ...t 2 00 00 off off off off 10 00 on off off off 01 00 off on off off 11 00 on on off off Display Ramp Soak Event 1 Event 2 Event 1 Event 2 00 10 off off on off 10 10 on off on off 01 10 off on on off 1...

Страница 19: ...1 parameter 113 Pr St Program status Available When 89 Pr F is different from nonE Range run Program Run HoLd Program Hold rES Program reset Note This parameter allows to manage program execution by a...

Страница 20: ...is equal to in finite the limit is always active and it can be used also when ON OFF control is selected 118 AdE Bargraph deviation Available Always Range oFF Bargraph not used 1 9999In engineering u...

Страница 21: ...shold not used 1 999 days 1 999 hours CAL Group User calibration group This function allows to calibrate the complete measuring chain and to compensate the errors due to Sensor location Sensor class s...

Страница 22: ...L1 AL2 A 6 AL2 Pb A 7 Pb Int A 8 Int dEr A 9 dEr Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The display alternately shows PASS and 0 3 By and buttons set a pas...

Страница 23: ...and the parameter modification procedure is closed When you desire to remove the time out e g for the first configuration of an instrument you can use a password equal to 1000 plus the programmed pas...

Страница 24: ...preceded by a P letter P84 3 4 Push button again When the wattmeter function is running the display shows U followed by the measured energy Note The energy calculation will be in accordance with the 1...

Страница 25: ...set manual modes during self tune execution the self tune function will be aborted 4 During manual mode all functions not related with the control wattmeter indipendent timer worked time etc continue...

Страница 26: ...ment to our company The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of altern...

Страница 27: ...and Under our C 0 9 oPE Safety output value 0 100 100 0 C 0 10 diF1 Digital input 1 function 0 oFF No function 1 Alarm Reset 2 Alarm acknowledge ACK 3 Hold of the measured value 4 Stand by mode 5 HEAt...

Страница 28: ...k alarm 16 Sensor break burn out AL1 A 17 14 o1Ac Out 1 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 15 o2F Out 2 function 0 Non...

Страница 29: ...r break burn out AL2 A 23 20 o3Ac Out 3 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 21 o4F Out 4 function 0 NonE Output not use...

Страница 30: ...and by mode 0 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by no C 0 AL2 Group Alarm 2 Parameters no Para meter Description Dec Range Default Vis...

Страница 31: ...0 LbA Group Loop Break Alarm Parameters no Para meter Description Dec Range Default Vis Promo 48 LbAt LBA time 0 From 0 oFF to 9999 s oFF C 0 49 LbSt Delta measure used by LBA during Soft start dP Fro...

Страница 32: ...om 0 00 oFF to 8 00 inF hh mm oFF C 0 71 SStH Threshold for soft start disabling dP 1999 9999 E U 9999 C 0 SP Group Set Point Parameters no Para meter Description Dec Range Default Vis Promo 72 nSP Nu...

Страница 33: ...e end program indication 2 From 0 00 oFF to 100 00 inF minutes and seconds oFF A 72 93 Pr S1 Set point of the first soak dP From SPLL to SPHL 0 A 73 94 Pr G1 Gradient of the first ramp 1 0 1 1000 0 in...

Страница 34: ...r time down PErc Percent of the power output used during soft start when the soft start time is equal to in finite the limit is always active can be used also when ON OFF control is selected nonE A 95...

Страница 35: ...urs with threshold nonE A 97 127 UoLt Nominal voltage of the load 0 1 999 Volt 230 A 98 128 cur Nominal current of the load 0 1 999 A 10 A 99 129 h Job Threshold of the worked hours days 0 From 0 oFF...

Страница 36: ...Ascon Tecnologic K Series ENGINEERING MANUAL Vr 9 0 PAG 36...

Отзывы: