●  Refrigerant is a high pressure gas and mistakes in use or handling will lead to a serious accident.

Risk of overfilling

The pressure of the refrigerant varies depending on the ambient 
temperature when the refrigerant is filled in a cylinder.

At this time, lowering of the liquid level by evaporation and rising 
of the liquid level by specific volume increase occur at the same 
time and balance.

At this time, rising of the liquid level by liquefaction and lowering 
of the liquid level by specific volume decrease occur at the same 
time and balance.

The  right  graph  shows  the  relation  between  the  pressure 
(saturation  pressure)  and  the  temperature  (saturation 
temperature) for each kind of refrigerant.

This relation between the saturation pressure and the saturation 
temperature  is  found  when  both  liquid  and  vapor  exist  in  a 
cylinder.    Normally  the  inside  of  the  cylinder  is  under  this 
condition and this chart is useful for field operation.

When  a  cylinder  is  almost  full  with  liquid  and  no  vapor,  the 
pressure rises rapidly even with a slight increase in temperature.

This phenomenon must be avoided in any circumstances.

1)Relation between the temperature and the pressure of refrigerant in a cylinder

Temperature 

rises

Some liquid refrigerant 

evaporates

Pressure rises

Temperature 

drops

Some vapor refrigerant 

liquefies

Pressure drops

RECOVERY CYLINDER

RECOVERY CYLINDER

-30

0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

-0.1

Saturation pressure of liquid refrigerant

(MPa)

(Gauge pressure)

-20 -10 0 10

Saturation temperature of liquid refrigerant (℃)

20 30 40 50 60

R12
R502
R22
R134a
R407C
R410A
R404A
R507A

Saturation pressure and saturation temperature 

of each type of refrigerant

Temperature and pressure

 of refrigerant in cylinder

Saturated

vapor

Saturated

liquid

Saturated

vapor

Saturated

liquid

R22

23.8kg/cm

2

 /337.85psi

at 60℃

R22

11.1kg/cm

2

 /158.05psi

at 30℃

R12

6.6kg/cm

2

 /94.25psi

at 30℃

R12

14.8kg/cm

2

 /210.25psi

at 60℃

Solar

radiation

heat

Содержание ECOsaver V240SP

Страница 1: ...REFRIGERANT RECOVERY MACHINE ECOsaver V240SP INSTRUCTION MANUAL Please read this manual before operating...

Страница 2: ...her Air Conditioning Equipment 8 HOW TO USE 10 Preparation before Operation 10 Liquid Vapor Recovery Procedure 12 Push Pull Recovery Procedure 16 Recovery Procedure of R410A or When the Pressure of Re...

Страница 3: ...d smoking during the work in process Cigarette light may creates Carbon Oxy Chloride and ignite fire Use protective eye glass and hand glove when disconnecting hoses If Freon gas was touch your skin o...

Страница 4: ...generator is not large enough it may lead to heating smoking or fire See the machine plate or this manual for the detailed specifications Do not setup the machine at location where gasoline thinner or...

Страница 5: ...por recovery procedure the compressor may be damaged Do not let visitors touch the machine Do not use the machine when the result is unpredictable Do not use the machine for purposes other than the or...

Страница 6: ...he store where the machine was purchased Use our cylinders that are expressly made for recovery and recycling Evacuation should not be done when the Auto stop run switch is at the Auto stop position A...

Страница 7: ...g hose BLUE 152cm Power cord Shoulder strap Filter Valve Auto stop run switch Start switch Tank full lamp Recovery complete lamp VAPOR RECOVERY START PURGE OFF LIQUID RECOVERY COMPONENTS OF THE MACHIN...

Страница 8: ...032F ES006 Shoulder Strap ES253 Power cord ES305 Instruction manual IM0436 Operation manual IM0437 Model ECOsaver V240SP Code No ES641 Recovery method Compressed vapor recovery method Push Pull metho...

Страница 9: ...Cordless Vacuum Pump 1 5CFM VP151 Useful where has no power source Cooling unit CL3 3 8 ES801 Improves the efficiency of recovery in summer climate recovery in a large volume or recovery of R410A by u...

Страница 10: ...ase of refrigerant when Disconnecting hose Quick charging valve A Y18975 Can be used without leaking refrigerant Recovery speed improves without Schrader Charging hose plus with SealRight fitting Vari...

Страница 11: ...o START The temperature of the cylinder may rise when the ambient temperature is high or R410A is recovered Lower the temperature and pressure of the cylinder according to page 11 4 Helpful Informatio...

Страница 12: ...of the system Heat up the accumulator by a heat gun or give it vibration if it is frozen Recover from multiple systems in one time How to avoid rise in temperature and pressure in the cylinder Put the...

Страница 13: ...quid Vapor Recovery Procedure 1 Connection of the hoses and cords System to be recovered Safety cable Manifold Filter When a cylinder with float sensor is used When a cylinder without float sensor is...

Страница 14: ...vacuum set the valve of the recovery machine to the PURGE position When the discharge pressure reaches to vacuum again connect the hose to the liquid port of the cylinder Close the ball valve of the...

Страница 15: ...ecovered Set the valve of the recovery machine to the START position Open Liquid valve of the cylinder and High Pressure valves Liquid side of manifold and the system Valve operation Operation End of...

Страница 16: ...r switch to the ON position Push the Start switch Please refer to P20 How to Restart the Recovery Machine if the unit does not run smoothly and restart the unit Turn the valve of the recovery machine...

Страница 17: ...cannot be applied Ask the manufacturer of the system if not clear 1 Connection of the hoses and cords Safety cable When a cylinder with float sensor is used High Low Safety cable Filter Sight glass op...

Страница 18: ...ition Do not set the Auto stop run switch to the Auto stop position Air may be left in the machine If the Auto stop position is selected the recovery machine will stop automatically Set to the Run pos...

Страница 19: ...RECOVERY position Set the Auto stop run switch to the Auto stop position Make sure there is no liquid flow in the sight glass Valve operation Operation End of operation Set the valve of the recovery m...

Страница 20: ...linder Turn the valve slowly to the VAPOR RECOVERY position Adjust suction pressure with valve to 3 5 kg cm2 43 5 72 5psi Close the vapor valve of the cylinder when the pressure in the cylinder drops...

Страница 21: ...n Set the Power switch of the recovery machine to the OFF position and reset the breaker after approximately 5 minutes Restart the recovery machine according to How to Restart the Recovery Machine 1 W...

Страница 22: ...linder is under this condition and this chart is useful for field operation When a cylinder is almost full with liquid and no vapor the pressure rises rapidly even with a slight increase in temperatur...

Страница 23: ...mp is on and the recovery machine stops when the cylinder is turned upside down Check the overfilling prevention function in case a cylinder with float sensor is used Connect the Safety cable to the c...

Страница 24: ...on Set the Auto stop run switch to the Run position Set the Power switch to the ON position Push the Start switch Make sure the air is sucked f r o m t h e s u c t i o n p o r t and discharged from th...

Страница 25: ...re in the cylinder is high Cool down the cylinder The piston seal is worn out Repair The cylinder valve is damaged Repair The hose has a core depressor Remove the core depressor in the hose The refrig...